ML20042A160

From kanterella
Jump to navigation Jump to search
Telecopy of Ro:On 820317,momentary Loss of RHR Occurred While in Mode G.Caused by Dropped Piece of Sheet Metal Which Hit 111 Inverter Output Breaker,Causing Loss of Instrument Feed to RHR Hi Pressure Switch
ML20042A160
Person / Time
Site: Zion File:ZionSolutions icon.png
Issue date: 03/18/1982
From: Graesser K
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8203230157
Download: ML20042A160 (1)


Text

SENT_

TELETYPE / TELEGRAM Date March la, 198 Tinne TO:

Mr. James G. Keppler Regional Director Gffice of Inspection & Enforcement Region III U.S. Nuclear Regulatory Connission Glen Ellyn, Illinois 60137 CUBJECT:

74OMENTARY Loss of RHR while in mode G.

Zion Station, Unit No.

1

, Docket No.

50-295 This is to confirin a conversation with _ Joe Waters cf your office on 3/17/82 at 1340 hours0.0155 days <br />0.372 hours <br />0.00222 weeks <br />5.0987e-4 months <br /> concerning (date)

(time)

A momentary lose of RHR while in mode G. A contracter workinn in the Aux.

electric room dropped a neice of sheet metal which hit the 111 inverter etcout breaker.

This caused a loss of instrument feed to the _RtfR Hi prenmuro switch causing it to indicate high therefore causing __lM_V RH O

C702 to _close (suction to RHR oumes).

RHR nump was trinned.

The inver-ter cutput was reclosed,_IMOV-RH8702 onened and 1A RHR oump started in Icos than three minutes.

This will be investigated and reported as required by section 6.6.B.3 of the Technical Specifications.

[g/ pg4" g -

[g K.L. Greenser Superintendent 8203230157 8 Eion Station g

gDR ADOCK 05hhohh5 PDR Sillo\\

.