4

.

During his review of the event report and licensee

followup actions, the inspector determined that the

licensee had not prepared an investigative report for

review by the Operations Committee. .This was not in

accordance with requirements of Procedure SACD3.6,

Operating Occurrences and Events, which is an implement-

ing procedure for Section 18.2 of the licensee Quality

Assurance Plan, Revision 6, to ensure that event

investigation and reporting is timely.

Failure to prepare and' review an investigative report

for event P-RO-81-23 is considered to be a noncompli-

ance with 10 CFR 50, Appendix B, Criterion V, as

described in the Appendix of the-letter forwarding this

report.

b.

P-R0-81-27

No. 11 Shic'_d Building Vent System Inoperable (Closed)

The inspector reviewed the event report and the cor-

rective actions as stated in the event report. During

the review the inspector noted that the licensee had

identified an event where a system was returned to

service without performing all the necessary sur-

veillance requirements.

At approximately 0301 on November 21, 1981 the No. 11

Shield Building Ventilation System (SBVS) was taken

out of service for charcoal filter replacement of the

Pre, Absolute, and Charcoal (PAC) filter. Prior to

placing the No. 11 SBVS ("A" train) out of service

the No. 12 ("B" train) was tested satisfactorily for

operability.

Work Request Authorization (WRA) No. E6602-ZS-Q and

Radiation Work Permit (RWP) No. S-731 documented the

authorization to perform the actual work to replace

the charcoal filter trays. After completing the

charcoal filter replacement SP-1073 (Shield Building

Ventilation System Functional Test) was performed and

No. 11 SBVS raturned to service.

The WRA specifically noted in the Explanation and

Special Instructions section to perform SP-1080 (No.

11 Shield Building Ventilation System Charcoal Filter

Iodine Removal Efficiency, DOP and Freon Test) after

replacing the filters on the No. 11 SBVS PAC filter.

The filters were replaced on~ 11/12/81 but SP-1080 was

not performed until 11/16/81. Technically the No. 11

SBVS was not operable until the SP-1080 was performed.

However, the surveillance was completed satisfactorily

-6-