ML20040F307

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in IE Insp Repts 50-295/81-23 & 50-304/81-19.Lowest Factor of Safety Given in Should Be 4.3 Not 4.4.Change Does Not Affect Conclusion Re Safety
ML20040F307
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 01/19/1982
From: Lentine F
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20040F275 List:
References
IEB-79-02, IEB-79-2, NUDOCS 8202090063
Download: ML20040F307 (1)


Text

r

[^'N Commonwealth Edisoo

.m

) one Firu Natsoret Ptut, Chicago, librois i

( O J AddressReply to: Post Office bot /M

~

(j Chicago, Illinois 60690 January 19, 1982 Mr. James G. Keppler, Regional Administrator Directorate.of Inspection and Enforcement - Region III U.S.' Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137

Subject:

Zion Station Units 1 and 2 Response to I.E.

Inspection Report Nos. 50-295/81-23 and 50-304/81-19 NRC Docket Nos. 50-295 and 50-304 References (a):

January 8, 1982, letter from F. G. Lentine to J. G. Keppler.

(b):

December 9, 1981, letter from R. L. Spessard to Cordell Reed.

Dear Mr. Keppler:

In reference (a), Commonwealth Edison responded to an item of noncompliance regarding the calibration of torque wrench multi-pliers at Zion Station.

Included in the response was an assessment of. the effect of using an uncalibrated torque wrench multiplier on work performed under I.E.Bulletin 79-02.

This is to inform you that that assessment contained an error.

The assessment stated that of the expansion anchored base plates 'that could have been affected by use of an uncalibrated torque wrench multiplier, one base plate had a factor of safety of 4.0, and the the lowest f actor of safety for the remainder of that group was 4.4.

The' lowest factor of safety for the remainder of the group should have been stated as 4.3.

This change does not change our conclusion that there are more than adequate conservatisms in the design and behavior of concrete expansion anchors to account for any misapplied torque values on a minimum number of expansion anchored base plates.

Please address any questions concerning this matter to this o f fice.

Very truly yours, f$

C F.

G. Lentine Nuclear Licensing Administrator occ:

Zion Resident Inspector JAN 25 g 1m 3266N' 8202090063 820203 PDR ADDCK 05000295 Q

PDR