ML20040F070

From kanterella
Jump to navigation Jump to search
Fifth Interim Rept of Significant Const Deficiency 28 Re Undersize 2-inch & Below Schedule 160 Socket Welds.Addl Time Needed to Complete Corrective action.Tompkins-Beckwith,Inc to Complete Repair by 820201.Final Rept Submitted by 820301
ML20040F070
Person / Time
Site: Waterford Entergy icon.png
Issue date: 01/29/1982
From: Mclendon G
LOUISIANA POWER & LIGHT CO.
To: Jay Collins
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, Q-3-A35.07.28, NUDOCS 8202080283
Download: ML20040F070 (1)


Text

I OUISIANA f 342 OctAnONOt sincer POWE R & L1GH T/ P O BOX 6008

  • NEW ORLEANS LOUIStANA 70174 * (504) 366 2345

00$ s?S40) u January 29, 1982 G. D. McLENDON Senior Vice President W3K-82-0049 Q-3-A35.07.28 Mr. John T. Collins, Regional Administrator, Region IV U. S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76012

SUBJECT:

Waterford SES Unit No. 3 p

'/

Docket No. 50-382 e

Significant Construction Deficiency No. 28 RECI'~

Y "Two-Inch and Below Schedule 160 Socket Welds Undersl @'

FEB 5 1982 > ;1..

Fifth Interim Report n 2_: t.

't

~

Reference:

LP&L Letter W3K81-0382 to USNRC dated October 19, 1 1.2 j,,,

.Q

Dear Mr. Collins:

'b /j]-

g The referenced letter indicated that a report would be submitted on Significant Construction Deficiency No. 28 by January 29, 1982.

Presently, Tompkins-Beckwith, Inc. (T-B) has completed their reinspection of all two-inch and under schedule 160 socket velds. Based upon this inspection, 579 welds required repair.

T-B anticipates the completion of this repair to be February 1, 1982.

In order to complete the corrective action on this Significant Construction Deficiency, additional time is required. Therefore, a final report will be submitted by March 1, 1982.

If you have any questions, please advise.

Very truly yours, GDMcL/LLB/grf 7.__

a

% hj (b), k =liY / U ' t

\\

i i

J cc: 1) Director Office of Inspection & Enforcement jf I

f U. S. Nuclear Regulatory Commission f@

l l982

{

Washington, D. C. 20555

}

2) Director Office of Management Information and Program Control U. S. Nuclear Regulatory Commission Washington, D. C. 20555 8202080283 820129 PDR ADOCK 05000382

/g S

PDR l