ML20040E354

From kanterella
Jump to navigation Jump to search
Public Version of Revision 5 to Emergency Operating Procedure 1202.44, Natural Emergencies
ML20040E354
Person / Time
Site: Arkansas Nuclear  
Issue date: 11/28/1980
From:
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML20040E352 List:
References
1202.44-01, 1202.44-1, NUDOCS 8202040220
Download: ML20040E354 (1)


Text

.

ge-m

- ~.

e.

PLAf 4T M ANU AL SECTiOti:

PROCEDUREMCPK PLAN TITLE:

}

rao:

g F " CP CY OPERATING NATimAL EMERGENCIES 1202.44 d'

ARKAMSAS NUCLEAR ONE SE siol s' cATE ii/:azao N

. CHANGE DATE 6.1 Earthquake 6.1.1 Symptoms A.

0.Olg Earthquake Trigger Alarm B.

0.lg Earthquake Trigger Alarm C.

Noticeable Abnormal Vibration in Major Structures 6.1.2 Immediate Actions A.

If ar.y two earthquake annunciators are in slow or fast flash and are verified as actual, take immediate action to bring both Unit One and Two to hot shutdown.

B.

If the 0.lg Earthquake Trigger Alarm actuates, refer to 1903.10, " Emergency Action Lcvel Eesponse," and declare

. an Alert.

s.

e,

,-n c oo k,. a.>.m pg a r,.,0 co m r ye,. W rw...

w mi

.ts A.,. r rig o...,w g g, h r, n p gg s

Follow-Up Actionsy m p,,cycy gey g.,opg,,

3yp gg 6.1.3 "r.nc-th n,,2..n.. o e cf, eg ec_% n,a.

A.

Perform a visual inspection of systems, components and structures to assess if any major damage has occurred.

B.

Assess if an emergency situation exists in accordance with the criteria of 1903.10, " Emergency Action Level Response."

C.

If inspections of systems reveal damage, attempt to secure the system or components as soon as practical.

Recovery actions shall be directed by the Duty Emer-gency Coordinator.

D.

Monito.r plant conditions to determine if an Emergency Action Level must be declared or upgraded.

[

n

(

[5N@0N7 7 0 2 0 1,: 3,,.

nsnnn CE-8202040220 820201 PDR ADOCK 05000313 F

PDR

_