l THE CINCINNATI GAS & ELECTRIC COMI%NY CTI~
ZIMMER NUCLEAR POWER STATION, P.O. BOX 201, MOSCOW, OHIO 45153 CINCINN ATL OHIO 45200 January 20, 1982 QA-1596 E. A. BoRG M AN N st NtOR viC E PRESIDE NT 9
R e
U.S. Nuclear Regulatory Commission Region III 36gETi.
g 799 Roosevelt Road p
f) 2 Glen Ellyn, Illinois 60137 T gggdkm,g[%[
2x F
r kdQeg Attention:
Mr. J. G. Keppler, Director cf N /
$<~
RE:
WM. H. ZIMMER NUCLEAR POWER STATION UNIT-1
/ f 10CFR50.55(e) - ITEM M INCOMPLETE 4
HYDRAULIC ANALYSIS OF CRD PIPING - DOCKET NO. 50-358, CONSTRUCTION PERMIT CPPR-88, W.O. 57300, JOB E-5590, FILE #NRC-8 Gentlemen:
This letter constitutes an interim report to the subject deficiences originally reported to the NRC Senior Site Resident Inspector as a po-tentially reportable deficiency under 10CFR50.55(e).
The design included an inadequate review of Control Rod Drive (CRD)
Piping for valve opening hydraulic transient loads. This deficiency was originally identified by Reactor Controls Incorporated (RCI), the original CRD design engineer, in their October 14, 1981, letter to the NRC Office of Inspection and Enforcement.
Sargent & Lundy Engineers (S&L) has been contracted by CG&E to perform a reanalysis of the CRD hydraulic systems for both dynamic and hydraulic transient loads.
An initial evaluation has determined that valve opening hydraulic transient loads (water hammer) may subject the piping and suspension system to stresses which could result in the degradation of CRD system reliability.
This condition is considered to be reportable under 10CFR50.55(e).
The reanalysis by S&L has determined that no pipe routing changes will be cequired. They have, however, determined that supports will require modification to accommodate these transient loads.
8202020311 820120 PDR ADOCK 05000358 S
PDR JAN 2 8 082
U.S. Nuclear Regulatory Commission
- Region III Mr. J. G. Keppler January 20, 1982 Page #2 The reanalysis is scheduled to be completed and drawings _ released for construction prior to February 28, 1982. A follow up report will be sub-mitted after completion of this reanalysis and drawing release.
We trust this letter will be found acceptable as an interim report under 10CFR50.55(e).
Very truly yours, THE CINCINNATI GAS & ELECTRIC COMPANY By E. A. Borgmann SENIOR VICE-PRESIDENT-FKP/bjs cc: NRC Resident Inspector Attn:
W. F. Christianson NRC Office of Inspection & Enforcement Washington,- D.C.
20555