Responds to NRC Re Violations Noted in IE Insp Rept 50-382/81-29.Corrective Actions:Protective Barriers for Electrical Penetrations Installed & Nightly Insps Initiated
ML20040D687
Person / Time
Site: Waterford 
Issue date: 01/13/1982
From: Mclendon G
LOUISIANA POWER & LIGHT CO.
To: Madsen G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20040D686 List:
References
W3K82-0012, W3K82-12, NUDOCS 8202020158
Download: ML20040D687 (3)


Text

,

0

,o LOUISIANA f,42 OuAnONOe Srnter P O W E F1 & L l G H T/ P O BOX 6008

  • NEW ORLEANS LOUISIANA 70174 = [504) 366-2345 MlOCLE SOUTH UiluTIES SYSTEM January 13, 1982 G D. McLENDON Senior Vice President W3K82-0012 Q-3-A35.02.01 bk5N g l g g%lj; hl Mr. G. L. Madsen, Chief, Reactor Projects Branch, Region IV j

, !J U. S. Nuclear Regulatory Commission L

i 611 Ryan Plaza Drive, Suite 1000 st Arlington, Texas 76012

SUBJECT:

Waterford SES Unit No. 3 USNRC Inspection Report 50-382/Rpt. 81-29

Dear Mr. Madsen:

The following information regarding the violation cited by the USNRC Inspectors in IE Inspection Report No. 50-382/Rpt. 81-29 dated December 11, 1981, is herewith submitted.

A.

Failure To Follow Procedures For The Protection Of Electrical Penetration Assemblies Criterion V of Appendix B to 19CFR50 requires that activities affecting quality be prescribed by documented instructians, procedure s, or drawings of a type appropriate to the circumstances, and that they shall be accomplished in accordance with these instructions, procedures, or l

drawings.

Ebasco CMI 28, Revision 8, " Care and Maintenance Instructions for Electrical Penetration Assemblies", require s that, during in place storage penetration assemblies be provided with adequate protection from damage and deterioration as a result of conditions or activities in the vicinity.

Contrary to the above, during a plant tour on November 2,1981, the NRC inspector discovered protective barriers absent from Class IE electrical penetrations 107SB and 10lSA. Penetrations in such an unprotected condition are subject to damage due to adjacent construction activities.

This is a Severity Level V violation (Supplement II.E).

1.

Corrective Action Taken and the Results Achieved:

Immediate action was initiated by LP&L and the Contractor to assure 8202020158 820121

{DRADOCK 05000382 PDR

o...s Mr. G. L. Madsen Page 2' that the electrical penetrations were protected. Alliprotective' barriers are installed and. damaged penetrations documented.'

2) Corrective Action Taken to Preclude Repetition:

Contractor Quality Control has increased the surveillance of the Electrical Penetrations from a monthly to a weekly basis. The construction supervisor instructed the craf ts to replace the barriers af ter completing' their work.

The Contractor has assigned. a Quality Control Inspector to _ inspect nightly all Electrical Penetrations to verify that protective barriers have been installed.

3) Date When Full Corrective Action Will Be Achieved:

The Care and Maintenance of Electrical Penetrations is an on going activity

.until completion of the project.

Presently the Contractor is in.

compliance.

If you have any questions concerning this response, please advise.

Very truly yours, kN G. D. McLendon Senior Vice President GDMcL:RGB:ncd

O a,

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter of

)

)

Louisiana Power & Light Company

) Docket No. 50-382 Waterford 3 Sttam Electric Station

)

AFFIDAVIT G. D. McLendon being duly sworn, hereby deposes and says that he is Senior Vice President of Louisiana Power & Light Company; that he is duly authorized to sign and file with the Nuclear Regulatory Commission the attached response (W3K82-0012) to the Notice of Violation identified in NRC Inspection Re, ort 81-29; that he is f amiliar with the content thereof; and that the matters set forth therein are true and correct to the best of his knowledge, information and belief.

M G. D. McLendon Senior Vice President STATE OF LOUISIANA)

)

ss PARISH OF ORLEANS )

tar blic in and for the Parish and State

), f before me, @A //y Pu/ /Af r/

,1982 Subscribed and sw 3 day of

.)

above named this,

I

/

,A e

/

,e l

,r,

sntl

/

  1. 36 " 'No Ph lic

~

L/

My Commission expires // /7//

/[6