ML20040D362
| ML20040D362 | |
| Person / Time | |
|---|---|
| Site: | Zimmer |
| Issue date: | 01/20/1982 |
| From: | Borgmann E CINCINNATI GAS & ELECTRIC CO. |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| REF-PT21-81 10CFR-050.55E, 10CFR-50.55E, QA-1594, NUDOCS 8202010219 | |
| Download: ML20040D362 (2) | |
Text
o e
x,W.y THE CINCINNATI GAS & ELECTRIC COhf PANY sW CINCINN ATI.OMIO 4520t January 20, 1982 QA-1594 E. A. BORG M AN N sf NIOR VeCE PRE $ GENT Wt iN p
U. S. Nuclear Regulatory Commission J/
MCEP$O 9
2 91982>. 'Z Region III
-l 799 Roosevelt Road S
U Glen Ellyn, Illinois 60137 TQ.
2r A
rs 4
Attention:
Mr. J. G. Keppler 9
,/y.
-gi \\
Director RE:
WM. H. ZIMMER NUCLEAR POWER STATION - UNIT I 10CFR50.55(e) - ITEM E ROCKBESTOS COAXIAL CABLE - DOCKET NO. 50-358, CONSTRUCTION PERMIT CPPR-88, W.O. #57300 JOB E-5590 FILE NO. NRC-7 Gentlemen:
This letter will close out the referenced potentially reportable deficiency initially identified to Mr. W. F. Christianson'of the NRC.
The deficiency, originally reported to the NRC on May 15, 1981 by General Atomic Co., under 10CFR21, involves Rockbestos series RSS-6-105 and RSS-6-110 coaxial cable. The center conductor may short out to the braided shield when exposed to continuous temperatures above 2300F.
It has been determined that the only area of the plant in which safety related systems may be exposed to such high continuous temperatures is inside the Primary Containment. An investigation has determined that no such cable has been installed in this area. To prevent possible inadvertent installation, all defective cable presently in the warehouse-has been tagged accordingly.
We feel that the Commission has already been adequately informed of this defect under 10CFR21 and that because no cable has been installed in the Containment, this item is not considered to be reportable under 10CFR50.55(c).
8202010219 820120
/ O PDR ADOCK 05000358 y,\\N 2 5 1982 S
i Mr. J. G. Keppler a
Director Region III January 20, 1982 QA-1594 Page 2 We trust the above will be found acceptable to fulfill the requirements of 10CFR50.55(e).
Very truly yours, THE CINCINNATI GAS & ELECTRIC COMPANY k
"g$ '"
By E. A. BORGMANN SENIOR VICE-PRESIDENT FKP:ac cc: NRC Resident Inspector Attn:
W. F. Christianson NRC Office of Inspection & Enforcement Washington, D.C.
20555
- - - - - - _ - - - - - - - - - - - - - - - - - - - - _ -