V 9%c F 71l' DES ( % 2 ns

'A.P.)

DEC 17 1981 o

x 9

9>

s MECENCO 9

Mr. Ja:aes R. Patrick, Jr., Deputy Chief

' C NOO I

Cotapliance Branch, Enforcement Division ugg$7 J-Environmental Protection Agency, Region IV

'b r.c 345 Courtland Street, NE.

ff Atlanta, Georgia 30365

/

g s

Dear Mr. Patrick:

NOTIFICATION OF NONCOMPLIANCE WIT 11 EITLUENT LIMITATIONS - NPDES PERMIT No. AL0022000 - BROWNS FERRY NUCLEAR PLANT Description of the discharge--Discharge No. L y> - Sewage treattaent plant effluent.

Sc:npleu collected on December 9,1981 and reported by the laboratory on December 14 and 15, 1931, exceeded maximuta permit litaita-tions as shown below:

(

Parameter Concentration Maximum Liraitation 80D5 48 mg/l 45 mg/l

\\

Suspended solids 49 mg/l 45 mg/l 3)

Fecal colifonn

>2000 N/100 ml 400 N/100 n

.Cause and period of the noncompliance--As stated in previous noncotapliance tcports, this 30,000 gpd sewage treatment system is hydraulically over-loaded due to increases in normal and outage maintenance personnel.

On December 9,1981 the instantaneous flow at the titae of sampling was approxirately 62,496 gpd.

In addition to this high flow, chlorination putaps were not injecting chlorine into the effluent due to nonfunctioning diaphrams in the chlorination pumps, which resulted in insufficient disinf ection.

The overload together with lack of chlorination caused ineffective treatment resulting in these excursions.

Steps taken to reduce. elilainate, and prevent recurrence of the noncomplying discharges--The f aulty diaphrams of the chlorination injection pumps were replaced on December 9, 1981. Consultations on modifylug the sewage treatment system are in progress, and we will operate the trentrient system as ef ficiently au possiblo until the syntaa is modified.

i Sincerely, M

g ohamed 1 Ph.D.

M v

}

Assistant Manager of Natural 8201270417 811217 Reuourcea (Environment)

PDR ADOCK 05000259 S

pop jg cc: See page 2 g i f)

2 J Mr. James R. Patrick, Jr.

DEC 17 1981

\\,0L

,L SRW:Pl!P

'~

cc: Alabama Water Improvement Comissica Public Health Services Building Montgomery, Alabama 36130 ARMS, 640 CST 7.-C R. H. Brooks, 141 EB-K

11. J. Green,1750 CST 2-C M. Hines,108 OS WilA-M L. M. Mills, 400 CST 2-C H. S. Sanger, Jr., E11B33C-K G. L. Sherer, 170 OS WllA-M

~1his was prepared principally by J. D. Bukley

.,..s.

SRW: JAG me: Director Division of Licensing U.S. Nuclear Reculatory Comminnion Washington, DC 20555 t