ML20040B459
| ML20040B459 | |
| Person / Time | |
|---|---|
| Site: | Summer |
| Issue date: | 01/14/1982 |
| From: | Nichols T SOUTH CAROLINA ELECTRIC & GAS CO. |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| REF-PT21-82-550-000 PT21-82-550, PT21-82-550-000, NUDOCS 8201260070 | |
| Download: ML20040B459 (3) | |
Text
- - _.
=
O 1
j USNRC Pr' r o
- n,, n r. ;. ' C '. -
SOUTH CAROLINA ELECTRIC-a gas' COMPANY
',r^
~,
N
[
PO$Y Of f tCE 804 764 CotuMem SOUTH CAROLINA 392I8 "2 JAN 18 Aa: 14 4
T. C. NicHots, Jn.
January 14, 1982 vc nu m. m.oc.oo,cucum u,,ca. on... e.,
,y t
\\
-. 8 u s James P. O'Reilly, Director
(
U. S. Nuclear Ib3ulatory Ocmnissial t
Regia. II, Suite 3100
^,p
.f 101 Marietta Street, N. W.
N, j
Atlanta, GA 30303 N;O
Subject:
V. C. Suniner Nuclear Statiot Docket No. 50/395 Rockbestos campany Cable Fafety llazard Final Report NE File: 3.1051
Dear Mr. O'Reilly:
01 June 18, 1981 and July 30, 1981 Ibckbestos Canpany salt SCE&G letters indicating that Rockbestos solid dielectric coaxial cmstructio1s nny exhibit failure due to shorting of the cmter i
conductor to the braided shield whm tested under II)CA calditials, i
'Ihey requested that SCE&G ideitify the Ibckbestos twinaxial cable
- that was installed within cmtainmmt in Class 1E applicatial.
01 July 13,1981, Mr. Virgil Brownlee of NIC Region II was notified of a potmtial significant deficietcy or substantial safety hazard cnicerning laboratory test failure of qualified Type 'IWinax Cable. 01 Atgust 12, 1991 an interim report or the above iten was seit to Mr. O'Reilly.
SCC &G idcntified the Ibckbestos 'IWinax cable that are 1E circuits and are located within the reactor building that could experielce an alvirmnuit with temperature above 230'F.
'Ihese cables are being replace 3 by qualified Brand Rex cables.
SCE&G is ideitifying the above item as a substantial safety hazard under 10CFR21 and the details of the safety hazard are described in the attached reporting form. 'Ihis is calsidered a final
{
report of the matter.
Very truly yours,
/
i T. C. Nichols, Jr.
t 1
8201260070 j Q %
( # O g.C# b i
j s
Mr. James P. O'Reilly Page to Jantury 14, 1982
'IB:'IC4: tdh cc:
J. P. O'Reilly V. C. Stnaner T. C. Nichols, Jr.
G. H. Fischer H. N. Cyrus H. T. Babb D. A. Nauman M. B. W1itaker, Jr.
W. A. Williams, Jr.
O. S. Bradham R. B. Clary M. N. Browne A. R. Kocn H. Radin O. W. Dixm, Jr.
Site Q. A.
G. J. Braddick J. K. Skolds J. B. Knotts, Jr.
B. A. Bursey J. C. Ruoff I&E (Washingtcn)
Docummt Rinagement Branch
- (55e, 21, LER cnly)
G. G. Littleholes NPCF File
- s 10CFR - SUBSTANTIAL SAFETY HAZARD 1.
Name and Address of Reporting Individual Tcm Brewer South Carolina Electric md Gas Company P. O. Box 764 Columbia, SC 29218 2.
Idettificatim of Basic Compmelt Rockbestos twinax cable used in IE circuits in reactor building whidi could see elvirotnuit temperature greater than 230'F.
3.
Ideitificatial of Firm Supplying Ccrement
%e Rockbestos Canpany New Havet, Cmnecticut 06504 4.
Nature of Defect, Substantial Safety Hazard Created, and Evaluatial Rockl:estos Co. informed SCE&G that Rockbestos Twinax cable is qualified to the requirenants of TEEE - 383-1974, except that it is not qualifiel at tenperature e':ceeding 230 F for periods exceeding 30 secmds. SCE&G review of 1E cable showed the three 1E circuits in the reactor building used Rockbestos twinax cable. %ese cables annect the acoustic detectors which mmitor the three pressurizer safety valves 8010A, B & C.
In a IDCA mvirmmett the above three cables for the acoustic mmitor circuits could have beat lost.
5.
Date Informaticn of Defect Was Obtained - Jme 18 and July 30, 1981 6.
Nunber and Incatim of Defect ihree circuits + hat had Rockbestos twinax cable in the reactor building.
7.
Corrective Actim Replace the subject cables with fully qualified cables.
8.
Advice to Purchasers or Licmsees Replace Ibckbestos cables as idettifiel in Rockbestos letters dated Jme 18,1981, July 30,1981, and Noveaber 9, 1981.