Final Deficiency Rept Re Under Designed Applications of Item M-26 Hilti 1-inch Diameter wedge-type Expansion Anchors, Initially Reported 801117.Five Supports Requiring Expansion Anchor Plate Mods Revised.Also Reported Per Part 21
ML20040A563
Person / Time
Site: Zimmer
Issue date: 12/30/1981
From: Borgmann E
CINCINNATI GAS & ELECTRIC CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-PT21-80 10CFR-050.55E, 10CFR-50.55E, QA-1537, NUDOCS 8201210245
Download: ML20040A563 (2)


Text

--_

THE CINCINNATI GAS & ELECTRIC COMPANY eN -

CINCINN ATI. OHIO 4 52o1 December 30, 1981 QA-1537 E. A. BoRGM ANN vaC C PRE S#DEh?

g\@ -tm U. S. Nuclear Regulatory Commission .

Region III f $ '

799 Roosevelt Road 3r 3csiVED g 3

Glen Ellyn, Illinois 60137 -

fi J AN 2 01987.* {1 I Attention: Mr. James G. Keppler, Director c)

UNmaa g p RE: WM. H. ZIMMER NUCLEAR POWER STATION UNIT I 4 @

[

50.55(e) - ITEM M-26 HILTI ANCHORS, DOCKET No. 50-358, CONSTRUCTION PERMIT CPPR-88, i W. O. #57300, JOB E-5590 - FILE NRC-8 l Gentlemen:

i This letter constitutes a final report on the subject anchors.

On November 17, 1980, the Cincinnati Gas & Electric Company telephu '

Mr. Paul Barrett of the NRC, regarding a potential 10CFR50.55(e) condition i concerning 1" diameter wedge-type expansion anchors. 5 i Hilti Incorporated Fastening Systems decreased the recommended ultimrte 1 loads for 1" diameter anchors with embedded depth of 6D or greater, resulting in potentially under designed applications of these anchors. Hilti subsequently t filed a report in accordance with 10CFR Part 21.

After a detailed investigation, the architect-engineer identified 44 l' supports which utilize 1" diameter Ililti Kwik Bolt Anchors with an embedded length as reported by Hilti. These were the only supports utilizing 1"  :

diameter Hilti Bolts of embedment greater than 6D. Five supports required expansion anchor plate modifications; the remainder required no change. .

Drawings for the following five supports have been revised and reissued: [

1HPt91 SR HP-03 Sheet 53, Rev. B 2/27/81  :

1Ril759 SR RH-21 ,

Sheet 80, Rev. C 2/27/81 .

, t IVC 070 HR VG-01 Sheet 85,-Rev. B 2/26/81  ;

IVQO10 SR VG-01 Sheet 77, Rev. B 3/31/81 1WS036 SR WS-13 Sheet 35, Rev. C 3/20/81  ;

1 ,

R2012103.W r!

JAN 18 382 Si e!

O

_ . - - . .ZE2 7

0 Mr. James G. Keppler U. S. Nuclear Regulatory Commission Region III December 30, 1981 - QA-1537 Page #2 We trust this fulfilla the requirements as a final report under 10CFR50.55(e).

Very truly yours, THE CINCINNATI GAS & ELECTRIC COMPANY

' 1-E. A. BORGMANN SENIOR VICE PRESIDENT FKP:ec ec: NRC Resident Inspector Attn: W. F. Christianson NRC Office of Inspection & Enforcement Washington, D. C. 20555