Final Deficiency Rept Re Nonsafety Solenoid Valve Energized by 125-volt Dc IE Bus,Initially Reported on 810812.Control Circuit Has Sufficient Isolation to Meet Separation Requirement.Notice Issued to Relabel Drawings
ML20039F425
Person / Time
Site: Summer 
Issue date: 01/04/1982
From: Nichols T
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8201120446
Download: ML20039F425 (2)


Text

I a o s

So0 TOC RdbNA" ELECTRIC & gas COMPANY i

n ".- ' ' ',o.e o e k,c..o.,..

CotuMe A, south CAmouN A 29218

==n,tm......c

.o,c m y; g 1 8

>g U '. 0 3 T. C. NicH o Ls. J a.

% 1..o

.,,c..

January 4,1982 Mr.. Jams P. O'Reilly, Director U. S. Nuclear Ibgulatory Camissicn Regicn II, Suite 3100 101 Marietta Street, N. W.

Atlanta, GA 30303

Subject:

Virgil C. Su:mer Nuclear Station Docket No. 50/395 Final Report Nuclear Ihgineering File: 3.1051

Dear Mr. O'Reilly:

Ch August 12, 1981, Mr. Virgil Brownlee of N10. Regicn II was notified of a potmtial significant deficimcy cn the subject "Ncn Safety Solenoid valve is mergized by 125 volt DC 1E Bus".

In interim letter addressing the above subject was sent Septetter 14, 1981.

A system revies of the problem by TE&G's architect and engineers showed that the solenoid valve was ncn-safety related and indeed it was being fed by 1E 125 DC bus. Inspecticn of the electrical elemmtary diagrams showed that the ccntrol circuit dcys have sufficist isolaticn to meet the separaticn requiremmts as outline, in Ocnstructicn Guideline for Electrical Circuit Ihysical Separaticn.

An algineering change notice NCN 1819 was writtm to relabel the circuit drawings for informaticnal purprees. No hardware or circuit changes had to be made because all regi.iranmts were originally satisfied.

'Iherefore, because of the above reascns this iten is not reportable inder 10CFR50.55 (e) or 10CFR21. 'ILis is crnsidered a final report of this matter.

I

/

op Very truly yours,

/

/

y llGCEtygg C

[' 'q e

g.

T. C. Nichols, Jr.

2 2 ISO 2A ST

,g a c p* e (s

/, 'hyrry TEZ7 3

Ol' g

8 2 0112'04Mp n &$> 7 s

/

L

7 g,

O

,_-o Mr. James P. O'Reilly Page two January 4, 1982

'IB:'ICN:tdh oc:

J. P. O'Reilly V. C. Sunener T. C. Nichols, Jr.

G. H. Fischer H. N. Cyrus H. T. Babb D. A. Naunan M. B. ittitaker, Jr.

W. A. Williams, Jr.

O. S. Bradham R. B. : Clary M. N. Browse A. R. Koal H. Radin O. W. Dixtn, Jr.

Site Q. A.

G. J. Braddick J. K. Skolds J. B. Knotts, Jr.

B. A. Bursey J. C. Ruoff I&E (Washingtcn)

Docunst Management Branch

  • (55e, 21, LER (nly)

NPCF File e

i

_._____________________________.__.___.__________________--_.__;