Responds to NRC Re Violations Noted in IE Insp Rept 50-309/81-24.Corrective Actions:Procedure for Design Change & Alteration Revised to Include Checkoff Provisions
ML20039B635
Person / Time
Site: Maine Yankee
Issue date: 11/23/1981
From: Randazza J
Maine Yankee
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20039B631 List:
References
FMY-81-172, NUDOCS 8112230332
Download: ML20039B635 (2)


Text

.

2.C.2.ll MAME ikHARHEE Alumi;, POL'KR09MPARU*

EDISON DRIVE AUGUSTA, MAlNE 04336

[pdj (207) 623-3521 NovembJr 23, 1981 FMY 81-172 thited States Nuclear Regulatory Commission Office nf Inspection und Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention:

Mr. Ronald C. Haynes, Director Refelences:

(a) License No. DPR-36 (Docket No. 50-309)

(b) USNRC Letter to MYAPC dated October 30, 1981 Inspection 50-309/81-24

Subject:

Response to IE Inspection 50-305'/31-24

Dear Sir:

In raply to Reference (b), the following information is hereby submitted.

ITEM OF NONCOMPLIANCE 10 CFR 50, fcpendix B. Criterion III, Design Control, states, in part,

" Measures shall be established to assure that applicable regulatory requirements and the design basis... for those structures, systems, and components are correctly translated into specifications, drawings, procedures, and instructions.

Design changes, including field changes shall be subject to design control measures commensurate with those applied to the original desiqn..."

The Yankee Operational Quality Assurance Program (YOQAP-1A) Sectim III states, in part, "A.

This section of the Operational Quality Assurance Program establishes measures to assure that the design of and changes to structures, systems, l

and components... are contro11eo.

C.1 Satisfaction of this criterion shall be assured through implementation of:

b.

Application of suiteole design controls to such activities as l

... seismic, stress... analyses; e.

Subjection of design... changes... to the same design controls l

and approvals that were applicable to the original design."

l s

The Maine Yankee FSAR states, in part, in Section 9.6.1, "The pumps, heat exchangers and interconnecting piping are designed to meet seismic criteria."

8112230332 811215 PDR ADOCK 05000309 G

PDR L

l

  • ~

MAINE YANKEE ATOMIC POWER COMPANY thited States Nuclear Regulatory Commission November 20, 1981 Attn: Mr. Ronald C. Hayn's Page Two e

Contrary to the above, as of September 4,1961, the measures established to assure that plant design changes are controlled, permitted modification, in Septenber 1980, and subsequent operation of two component cooling heat exchangers, which are required to meet seismic criteria, without completion of a seicmic analysis.

This is a Severity Level IV Violation.

(Supplement I.D.3)

RESPONSE

Upon disclosure that the required seismic analysis had not been completed the heat exchangers in question were removed from service.

The ten inch unanalyzed NNS piping was disconnected prior to returning the heat exchangers to service. Subsequently, the seismic analyses haie been completed with the result that failure of the NNS piping would not cause a failure of the heat exchanger. Results of this analysis are available for inspection.

The procedure for design change and alteration has been changed to include check off provisions to ensure that all design requirements have been met and documented prior to placing a system in service.

Maine Yankee personnel responsible for plant changes have been trained in these procedural changes and reminded of the importance of obtaining the reouired documentation prior to system operation.

We trust this information is satisfactory. Should you have any further auestions, please feel free to contact us.

Very truly yours, MAINE YANKEE ATOMIC POWER COMPANY N

  • he, _

John B. Randazza Vice President, Operations 1

JBR/bjp STATEOFMAI,NKg;)g j g

)ss COUNTY OF KENNEBEQ)ii.

1 gpe n

Then personally appedreB'before me, J. B. Randazza, who, being duly sworn, did state that he is a Vice President of Maine Yankee Atomic Power Company, that he is duly authorized to execute and file the foregoing request in the name and on the behalf of Maine Yankee Atomic Power Company, and that the statements therein are true to the best of his knowledge and belief.