Final Deficiency Rept Re Defective Ite Circuit Breakers, Initially Reported on 810828.Replacement Parts Which Correct Problem Have Been Received & Will Be Installed as Const Schedule Permits
ML20038C143
Person / Time
Site: Fermi 
Issue date: 11/25/1981
From: Wells D
DETROIT EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50.55E, F2S81-54713, NUDOCS 8112100136
Download: ML20038C143 (1)


Text

D O

Donald A. Wells g.=

g h

3[2$7 b

2000 Second Avenue

(~

'=ed Edison ne-2 ocos iss>

f U.s. eucuma tanArost Q Co""*25" 7

Q ovember 25, 1981 F2S81-54713 s.y\\

Q Mr. James G. Keppler, Director Region III U.S. Nuclear Regulatory Ccumission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Subject:

Final Report of 10CFR50.55(e) Item on Defective ITE Circuit Breakers (#47)

Dear Mr. Keppler:

This is Detroit Edison's final report on the Defective ITE Circuit Breakers.

The problem was originally reported to Mr. J. Smith of NRC-Region III by Detroit Edison's Mr. H.A. Walker, Supervisor-Construction Quality Assurance, on August 28, 1981.

This item involved 1600 AMP ITE circuit breakers. In order to address IE-Information Notice 80-31 which was written on Gould-Brown Boveri 600 AMP I

breakers, Detroit Edison had implemented a field test procedure requiring the reccanended tests. This test procedure was used to test, not'only the 600 AMP breakers covered in the information notice, but other ITE Gould breakers as well. In testing ITE, 1600 AMP, Type K-1600 S and K-DO-N 1600 a breakers, failures occurred on two breakers similar to the failure described.

in the referenced information notice.

Replacement parts which correct the problem have been received on site and are being installed as construction schedules permit. Testing of ITE break-ers for this problem is continuing, however, no further failures have occured.

If you have questions concerning this matter, please contact Mr. H.A. Walker,.

Supervisor-Construction Quality Assurance.

Very truly yours, D

l 7

l D'

DAW / HAW /cp cc: Mr. Victor Stello, Jr., Director Office of Inspection and Enforcement Division of Reactor Inspection Programs Washington, D.C. 20555 Mr. Bruce Little, Resident Inspector U.S. Nuclear Regulatory Ccmnission Resident Inspector's Office 6450 North Dixie Highway Newport, Michigan 48160 8112100136 811125' I