M Docket No. 50-397 p

50.55(e) Report Washington Public Power Supply System P.O. Box 968 3000 GeorgeWashingtonWay Richland, Washington 99352 (509)372-5000 November 12, 1981 G02-81-0463 Docket No. 50-397 gg \\ E lh' Mr. R. H. Engelken, Director

,e Nuclear Regulatory Commission iO L@

^

\\

Office of Inspection and Enforcement J-Q "Qp 'f 2 3198;w t-ia Lane a

Suite 210 Walnut Creek, California 94596

'G J

iu

Dear Mr. Engelken:

^

9 og

Subject:

SUPPLY SYSTEM NUCLEAR PROJECT N0. 2 POTENTIALLY REPORTABLE 10CFR50.55(e) CONDITION N0. 142 DIESEL GENERATOR BUILDING HVAC SYSTEM

Reference:

Letter G02-81-165, dated July 1,1981, RG Matlock (Supply System) to RH Engelken (NRC), same subject The reference letter advised you that a reportable 10CFP.50.55(e) condition existed regarding tornado depressurization effects on tha Diesel Generator Building HVAC System, and that a final report would be submitted by Novem-ber 15,1981, describing required plant modifications.

Our further review of this condition has resulted in the conclusion that even though portions of the HVAC ductwork could collapse under the postulated tornado pressure drop,~the system would still operate in the recirculation mode to provide room cooling to maintain the diesel generator electrical equipment within its operable temperature range. Therefore, the condition described in the Reference has been determined to be not reportable under 10CFR50.55(e).

Very truly yours, I

b Program Director, WNP-2 EAF:kjf cc: WS Chin - BPA ND Lewis - EFSEC, Olympia TA Mangelsdorf - Bechtel 982 AI Cygelman - B&R Site 954W RE Snaith - B&R NY JJ Verderber - B&R NY AD Toth - NRC Resident Inspector JC Plunkett, Jr. - NUS Corporation RA Schwencer - NRC

' MNDEc

[bO.)

E. Beckett - Nuclear Projects, Inc.

WNP-2 Files gI

ll pi 8i ACM IO 3

au:i -

8ii1240628 eiii12 02AG13 PDR ADOCK 0500039 5