Notice of Violation from Insp on 800902-05 & 15-30
ML20037C412
Person / Time
Site: Limerick  
Issue date: 10/17/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20003A730 List:
References
50-352-80-17, 50-353-80-15, NUDOCS 8102050798
Download: ML20037C412 (2)


Text

.

O APPENDIX A NOTICE OF VIOLATION.

Philadelphia Electric Company Docket No. 50-352 This refers to the inspection conducted by the Resident Inspector assigned to the Limerick Generating Station, Unit 1, Limerick, Pennsylvania, of activities authorized by NRC License No. CPPR-106.

During this inspection conducted on September 2-5 and 15-30,1980 the following apparent items of noncompliance were identified:

A.

Appendix R. of 10 CFR 50, Criterion V, etates in part:

" Activities affecting quality...shall be accomplished in yardance with these instructions, procedures or drawings..."

The Limerick PSAR, Appendix 0, Quality Assurance Program, paragraph D.6.4 states, in part, that:

"Bechtel Construction Department...is responsible for construction of the plant to approved engineering specifications, drawings, and procedures...".

The Bechtel Job Rule G-28, Revision 18 in Section 5.2 states, in part, that:

"The lead area engineer is responsible for issuing the Rebar cutting tool. Each area's drill shall be kept out of general circulation and shall be used only with the approval of the lead area engineer."

Contrary to the above the Crafts were drilling into a seismic Class I block wall No. 62 (Ref. Drawing C-762) without the required written approval of the lead area engineer.

This item is an infraction.

B.

Appendix B, of 10 CFR 50, Criterion V, states in part: " Activities affecting quality...shall be accomplished in accordance with these instructions, procedures or drawings...".

The Limerick PSAR, Appendix D, Quality Assurance Program, paragnph D.6.4 states, in part, that:

"Bechtel Construction Department... is responsible for construction of the plant to approved engineering specifications, drawings, and procedures...".

The Bechtel design specification E-1412, sheet 1.3.1 entitled " Wire and cable notes and details" depicts typical (two) methods for protecting cables from sharp edges of the cable trays (side rails and ends). The two methods consist of the use of adhesive backed neoprene gasket material or slit air hose.

%7

)

Appendix A 2

Contrary to the above, as of September 18, there were five cable trays (Nos. lATX01, lATXA32,1CTTA24, ICTSA06 and 1BTVA05) that had cables coming i

out of the trays which were not protected from the edges of the trays.

j This item is an infraction.