From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
RO-03-80-27-1P, RO-3-80-27-1P, NUDOCS 8012010289
Download: ML20037B773 (2)


Text

.

PHILADELPHIA ELECTRIC COMPANY Peach Bottom Ato=ic Power Station Delta, Pennsylvania 1731k November 2% 1980 Mr. Boyce H. Grier Office of Inspection and Enforcement Region 1 United States Regulatory Cossaission 631 Park Avenue ICZag of Prussia, PA 19h06

SUBJECT:

REPORTABLE OCCURRENCE - PROMPT NCf"IIIICATIO)'

Confi29mine R. S. Fleischmann's Conversation with Mr. Cowgill on November 24, 1980.

Reference:

Docket No. 50-277 Peach Botton Unit 3 Technical Specification

Reference:

3.5.C Report Ec. 3-80-27/IP Occurrence Date:

November 2h. 1980 Identification of Occurrence:

i With the Unit operating at 995 power while performing HPCI Surveillance Test 6.5 MD-3-23-1k EPCI Steam to Turbine Valve kept driving in the close direction causing the valve fuses to blev.

Conditions Prior to Occurrence:

Unit 3 operating at essentially full power; Unit 2 operating at T9 25 power.

Apoarent cause of Occurrence:

The torque switch which opens the feed to the close circuit of the valve fathd to open, which caused the motor to keep driv-ing the valve in the clamed direction until the motor fuses blev.

Analysis of Occurrence:

The Unit 3 HPCI system was inoperable for approvintely one half hour until tame fuses were replaced.

During this time all other Unit 3 BCCS systems were sparshle.

Due to the short period of inoperability safety significance is

=4=4=a1.

[ool 3

s_.

Currective Action:

I O

[ EThe EPCI valve h 3-23-lk elosing torque switch was inspected, readjusted and n-N valve was stroked satisfactorily.

= mE=..

__.....r REE 8o12010.2W m

s

o t-e

~2-

,Trevious Failures.

~coe e

Very truly yours,

-? ! An

/ & 87'

v. T. Ullrich Station Stgerintendent WTU: cat I