Notice of Violation from Insp on 930406-08.Violation Noted: Sufficient Records Were Not Maintained to Furnish Evidence of Reviews of Effect of Replacement Cylinder Liners for a EDG on EDG Support Sys or Fuel Consumption
ML20036B069
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 05/12/1993
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20036B064 List:
References
50-271-93-10, NUDOCS 9305180125
Download: ML20036B069 (1)


Text

_

NOTICE OF VIOLATION Vermont Yankee Nuclear Power Corp.

Docket No. 50-271 i

Vermont Yankee License No. DPR-3 During an NRC inspection conducted on April 6-8,1993, a violation of NRC requirements was identified. In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C, the violation is listed below:

10 CFR Part 50, Appendix B, Criterion XVII - Quality Assurance Records, and the licensee's accepted quality assurance program, requires that sufficient records shall be maintained to furnish evidence of activities effecting quality. The records shall include the results of reviews.

Contrary to the above, sufficient records were not maintained to furnish evidence of reviews in that Equivalency Evaluation 92-036, dated April 4,1992, stated that improved heat transfer was a critical characteristic of replacement cylinder liners for the 'A' emergency diesel generator (EDG) but no record of the review was made concerning the effect on emergency diesel generator support systems or fuel consumption.

This is a Severity Level IV violation (Supplement I).

t i

j Pursuant to the provisions of 10 CFR 2.201, Vermont Yankee Nuclear Power Corporation is hereby required to submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administrator, Region I, and a copy to the NRC Resident Inspector at the facility 3

that is the subject of this Notice, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). This reply should be clearly marked as a " Reply to a Notice of Violation" and should include for each violation: (1) the reason for the violation, or, if contested, the basis for disputing the violation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieved. If an adequate reply is not received I

within the time specified in this Notice, an order or a Demand for Information may be issued i

to show cause why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to extending the response time.

Dated at King of Prussia, PA I

this//6 day of May,1993 3

f f

5 i

9305180125 930512 DR ADOCK 05000271 2

PDR 0FFICIAL RECORD COPY A:VY9310. INS i

-