April 19, 1993 i
o.
Mr. Thomas Northrup Vice-President of Engineering Rochester Instrument Systems 255 North Union Street Rochester, NY.
14605 3
Dear Mr. Northrup:
Enclosed for your information is a copy of TR-2158-5/92, Rev.1, "A Test Plan for Fault Testing of Nuclear Power Plant Electronic Isolation Devices," dated March 3, 1993 (Enclosure 1).
Brookhaven National Laboratory, under contract from NRC, has recently completed testing of a representative sample of isolation devices, including i
Rochester Model SC-1302, used in nuclear power plants. The tests were performed in accordance with the Test Plan, TR-2158-5/92, Rev. 1.
Enclosed for your review and comment is a copy of the test results summary for Model 50-1302 (Enclosure 2).
Consideration will be given to your comments if received by May 28, 1993.
The final NUREG/CR report will be issued in July 5
1993.
4 Sincerely, Originalnvn,>
a Satish K. Aggamal.,< Program Manager Electrical and Mechanical Engineering Branch.
Office of Nuclear Regulatory Research cc:
F. Rowan, Rochester J. Taylor, BNL (w/o encl)
DISTRIBUTION-I L. Shao (w/o encl)
J. Craig (w/o encl)
M. Vagins (w/o encl)
J. Wermiel (w/ encl 2)
R. Baer (w/ encl 2)
J. Vora (w/o. enc 1)
PDR _ '
(w/ encl 2)'
Concurrence: o 3000M ggA-EMEB:RES SAggarwal:fr 04/17/93 OFFICIAL RECORD COPY FILENAME: g:\\ groups \\de\\emeb\\aggarwal\\northrup
}
93o503o14t 930419
[/0 Ii PDR ORG NREA
N..
.~:
.(
ISOLATION DEVICE TEST PROGRAM FIN-2158 MAKE:
RIS MODEL:
SC-1302 S/N:
PES 20541A-002 TEST RUN: RA-3-2 DATE:
1/21/93 1/2 Cycle Funct Energy
. Test
' l RESISTANCE BARRIER CAPACITANCE
-#~
Test Passed Run MC open ckt both iso barrier Fregncy Voltage Voltage open ckt DUT conn iso barrier No. Lvl Gohms Gohms Gohms Appl'd open ckt acrss DUT ma' ma pfarads P/F micro joules
.~
(1) 0.1 20.6 11.2 24.6 50000 2.92 2.92 0.57 1.09 571.9 P
0.002 (2) 0.2 1123 40.1 623 50000 2.91 2.64 0.58 1.23 848.8 P
0.001
-(3) 03 137.5 36.7 50.1 50000 2.92 2.81 0.57 1.21 749.9 P
0.003 (4).0.4 28.0 14.2 28.8 50000 2.92 2.81 0.55 1.21 767.9 P
0.005 (5) 0.5 39.1 22.5 53.1 50000 2.01 1.90 037 0.76 689.4 F
0.092 (6) 0.6 273 16.6 42.1 50000 2.01 1.90 038 0.77 6803 F
0.540 (7) 0.7 273 16.6 42.1 50000 2.01 1.90 038 0.76 685.5 F
0320 (8) 0.8 27.1 17.2 47.2 50000 2.01 1.90 038 0.76 679.6 F
0.200 (9) 0.9 28.0 14.9 31.7 50000 2.01 1.90 038 0.77 679.8 F
0.230 (10) 1.0 27.1 17.1 46.1 50000 2.01 1.90 038 0.76 679.0 F
0.225 (11) 1.1 15.0 10.9 40.5 50000 2.01 1.90 037 0.76 6953 F
0.250 (12) 23.5 14.1 34.9 50000 2.01 1.90 037 0.77 694.4 F
energy 100 damage
=
level
,ig e,~.
--.-m
-r--
w
.ru ww-ww w e$w w. e -u
.-.i.e-w.w.v,,,
.--,.v a--s-
,1m-
,...,e sw,,e--
3i-t44-aw-e,,--r,
,rw.
+m,..--we wee-,--.ee
[
OQ ISOIATION DEVICE TEST PROGRAM FIN L2158 TEST RESULTS
SUMMARY
I DEVICD Rochester SC-1302 TYPD Transformer Modulation with Voltage Input DRAR TEST RUN:
RA-3-2 DATE COMPLETED: 1/21/93 i
DEVICE CHAR ACTERISTICS Barrier Resistance - Range 24-62 Gohns Barrier Capacitance - Range 571-848 pfarad Functional Test ' Failed between.4 and.5 MCF (40 and 50 volts)
Energy Passed " s C.54 p Joules (Damage Threshold = 100 Joules) l Summarv Device was tested at Maximum Credible Fault levels from 0-130 volts at 10% steps. De device failed functionally (would not transmit signal) between 40 and 50 volts. The device maintained its isolation characteristics throughout testing, and passed more energy than the first device tested, but well below the damage threshold level.
1 Notes Functional Test verifies whether Isolation Device has capability to transmit a voltage signal from safety circuit to non-safety circuit.
Energy pass through measures energy that is transmitted through the isolation device from the non-safety side to the safety side caused by the fault.
.____._-_________;