March 30,1993 Docket Nos. 50-321 DISTRIBilTION and 50-366
- Docket File-L. Berry-PDII-3 RF K.Jabbour Mr. W. G. Hairston, III NRC/ Local PDRs OGC 15B18 Senior Vice President -
S.Varga E. Jordan MNBB3302 Nuclear Operations G.Lainas ACRS (10)'
Georgia Power Company D.Matthews' E.Merschoff, RII P. O. Box 1295 0.Chopra 7E4 D. Thatcher 7E4 Birmingham, Alabama 35201
Dear Mr. Hairston:
SUBJECT:
CLOSURE OF RESPONSE TO GENERIC LETTER 91-06 HATCH NUCLEAR PLANT, UNITS 1 AND 2 (TAC NOS. M81448 AND M81449)
On April 29, 1991, the NRC issued Generic Letter (GL) 91-06, " Resolution of Generic Issue A-30, ' Adequacy of Safety-Related DC Power Supplies.'" The GL implemented the staff's resolution of Generic Issue (GI) A-30 as part of the resolution of GI-128, " Electrical Power Reliability." The GL requested that licensees provide written responses to several questions to allow the staff to determine whether any additional actions were required.
By letter of October 18, 1991, Mr. J. T. Beckham, Jr., Georgia Power Company, l
submitted certified responses to each of the questions of GL 91-06. The staff has reviewed these responses and finds that they satisfy the reporting requirements of the GL. This completes the staff's activities associated with the subject TACs.
Sincerely,
/s/
Kahtan N. Jabbour, Project Manager Project Directorate 11-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc:
See next page
/l,, /f n
PDII-31/Lb PDII-3/P)4 d PDI-3/PMcL( PDhh mN L.BERh K.JABBb A. JOHNSON D.lNTHEYS N
h/
/93 1 / 3 0/93
%/$0 /93
.3/f0/93 DATE 0FFICIAL RECORD COPY FILE NAME: G:\\ hatch \\ hat 81448.1tr 9304070227 930330 r+ g g p e.
[n w y,,.g, 7,
DR ADOCK 0500 1
a
\\
i o\\q
Ys
-?
ymy d
[,
, ?g UNITED SVATES
[ kri.' i j NUCLEAR REGULATORY COMMISSION
- y gpg e
wasmNoTou, o c 20sss-omi
/
March 30, 1993 ~
%.. '. =
Docket Nos. 50-321 and 50-366 Mr. W. G. Hairston, III Senior Vice President -
Nuclear Operations Georgia Power Company P. O. Box 1295 Birmingham, Alabama 35201
Dear Mr. Hairston:
SUBJECT:
CLOSURE OF RESPONSE TO GENERIC LETTER 91-05 HATCH NUCLEAR PLANT, UNITS 1 AND 2 (TAC NOS. M81448 AND M81449)
On April 29, 1991, the NRC issued Generic Letter (GL) 91-06, " Resolution of Generic Issue A-30, ' Adequacy of Safety-Related DC Power Supplies.'" The-GL implemented the staff's resolution of Generic Issue (GI) A-30 as part of the resolution of GI-128, " Electrical Power Reliability." The GL requested that licensees provide written responses to several questions to allow the staff to determine whether any additional actions were required.
By letter of October 18, 1991, Mr. J. T. Beckham, Jr., Georgia Power. Company, submitted certified responses to each of the questions of GL 91-06. The. staff has reviewed these responses and finds that they satisfy the reporting requirements of the GL.
This completes the staff's activities associated with the subject TACs.
Sincerely,
( d=.u. Lii n Kahtan N. Jabbour, Project Manager Project Directorate 11-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc:
See next page
k, j
y l
Mr. W. G. Hairston, III_
Georgia Power Company Edwin I - Hatch-Nuclear Plant i
cc-Mr Ernest L. Blake, Jr.
Mr. R. P. Mcdonald
-l Shaw, Pittman, Potts and Trowbridge Executive Vice President -
2300 N Street, NW.
Nuclear Operations Washington, DC 20037 Georgia Power Company P. O. Box 1295 Mr. J. T. Beckham Birmingham, Alabama 35201 Vice President - Plant Hatch
+
Georgia Power Company Mr. Alan R. Herdt, Chief
-l P. O. Box 1295 Project Branch #3 Birmingham, Alabama 35201 U. S. Nuclear Regulatory Commission 101 Marietta Street, NW, Suite 2900 Mr. S. J. Bethay Atlanta, Georgia 30323-Manager Licensing - Hatch i
Georgia Power Company Mr. Dan H. Smith, Vice President P. O. Box 1295 Power Supply Operations Birmingham, Alabama 35201 Oglethorpe Power Corporation 2100 East Exchange Place Mr. L. Sumner Tucker, Georgia 30085-1349 General Manager, Nuclear Plant Georgia Power Company Charles A. Patrizia, Esquire 1
Route 1, Box 439 Paul, Hastings Janofsky & Walker Baxley, Georgia 31513 12th Floor 1050 Connecticut Avenue, NW.
1 Resident Inspector Washington, DC 20036 f
U. S. Nuclear Regulatory Commission Route 1, Box 725 Baxley, Georgia '31513 1
Regional Administrator, Region II U. S. Nuclear Regulatory Commission I