4 April 12, 1990 l
Docket No. 50-382 Mr. J. G. Dewease Senior Vice President - Nuclear Operations Louisiana Power and Light Coppany Post Office Box 60340 New Orleans, Louisiana 70160
Dear Hr. Dewease:
SUBJECT:
EllERGENCY DIESEL GENERATOR FUEL DIL - STORAGE TANK SAMPLING WATERFORD STEAM ELECTRIC STATION, UNIT 3 (TAC NO. 76159)
By letter dated March 27, 1990, Louisiana Power and Light Company (LP&L) requested approval of an alternate test method for sampling diesel fuel oil in the storage tanks. The request is based on the LP&L position that.the alternative sampling technique will provide an acceptable sample and the need to subject the technician to an obvious safety hazard is unwarranted.
3 He have reviewed the LP&L request and agree that the current procedure for sampling imposes a safety hazard to the technician. The proposed alternate samplingtechniquewillutilizethevalvesdesignatedEGF-110A(B)todrawoff a sarple after "several liters of fuel oil" have been flushed from the line.
The transfer pump will have been run in a recirculation mode prior to the sampling to clear the pump and recirculation line. LP&L should assure that sufficient oil has been drained off before taking the sample; several liters as mentioned should be checked to see that this volume sufficiently flushes the lineouttothevalvesdesignatedEGF.111A(B).
We are also aware that LP&L will investigate the use of a new sampling nethod and ASTil code for particulates. LP&L should proceed with those investigations and inform this office of the results.
Based on our review of the LP&L request, we find the proposal acceptable.
Pursuant to ASTM D270 1975, Section 11, LP&L is authorized to obtain samples by the described process from valves EGF-110A(B) in lieu of the requirement to obtain samples from the top of the tank.
I Sincerely, Frederick J.- Hebdon, Director l
9004260177 900412 Project Directorate IV PDR ADOCK 050003e2 Division of Reactor Projects - III, F
PDC IV, Y and Special Projects Office of Nuclear Reactor Regulation cc: See next page DISTRIBUTION,
I f" Docket J11ed NRC PDR Local PDR PD4 Reading
~
G. Holahan MS 13E4 F. Hebdon P. Noonan D. Wigginton OGC-Rockville E. Jordan MS MHBB 3701 ACRS (10) MS P-315 PD4 Plant File E. Tomlinson MS 11F23
- See previous concurrence.
<\\
l
+
UTC 7 PD4/L
- PD4/PR'
- 0TSB*
- PD4/D, 7.....
L.I......:............:.
Wigginton:bj:ETomlinson:FHehdn NAME :PNoona r
DATE :04////90
- 04/h/90 l
- 04/11/90
- 04/it./90
~
OFFltIN. RECORD copy Docunent riameT~R3 LTR/76159 02
.~
e.v p uoy e.
,(
fo UNITED STATES
'g
_[
g NUCLEAR REGULATORY COMMISSION l
WASHINGTON, D. C. 20545
, r,,
April 12, 1990 Dccket No. 50-382 f
Mr. J. G. Dewease Senior Vice President - Nuclear Operations Louisiana Power and Light Company Post Office Box 60340
{
New Orleans, Louisiana 70160
Dear Mr. Dewease:
SUBJECT:
EMERGENCY DIESEL GENERATOR FUEL OIL - STORAGE TANK SAMPLING WATERFORD STEAM ELECTRIC STATION, UNIT 3 (TAC NO. 76159)
_By letter dated March 27, 1990, LouisianaPowerandLight' Company (LP&L) requested approval of en alternatt test methed for sampling diesel fuel oil in the.
storage tanks. The request is based en the LP&L position that the alternative sampling technique will provide an acceptable sarple and the need to subject the technician to an obvious safety hazard is unwarranted.
He have reviewed the LP&L request und agree that the current procedure for sampling imposes a safety hazard to the technician. The proposed alternate-sanpling technique will utilize the valves designated EGF-110A(B) to draw off j
e serple after "several liters of fuel oil" have been flushed fron. the line.
The transfer purp will have been run in a recirculation mode prior to the sampling to clear the pump and recirculation line.
LP&L should assure that sufficient oil has been drained off before taking the sample; several liters as rentioned shculd be checked to see that this volume sufficiently flushes the lineouttothevalvesdesignatedEGF-111A(B).
We are also aware that LP&L will investigate the use of a new sampling method and ASTM code for particulates. LP&L should proceed with those investigations and inform this office of the results.
Based on our review of the LP&L request, we find the proposal. acceptable.
Pursuant to ASTM D270-1975, Section 11, LP&L is authorized to obtain samples bythedescribedprocessfromvalvesEGF-110A(B)inlieuoftherequirementto obtain san >ples from the top of the tank.
1 Sincerely,
)
Frederick J. Hebcon, Director Project Directorate IV Divisien of Reactor Projects - III, IV, Y and Special Projects i
Office of Nuclear Reactor Regulation.
cc: See next pace 1
April 12, 1990 Docket flo. 50-382-Mr. J. G. Dewease Senior Vice President - Nuclear Operations Louisiana Power and Light Conpany Post Office Box 60340
- New Orleans, Louisiana.70160
Dear Mr. Dewease:
SUBJECT:
EMERGENCY DIESEL GENERATOR FUEL OIL - STORAGE TANK SAMPLING-i WATERFORD STEAM ELECTRIC STATION, UNIT 3 (TAC NO.. % 59)
By letter dated March 27, 1990, LouisianaPowerandLightCompany(LP&L) requested approval of an alternate test method for sampling diesel fuel 011Lin the storage tanks. The request is based'on'the LP&L position ~that the alternative sampling technics < 11 provide an acceptable sample and the need to subject t
the technician n m obvious safety hazard is unwarranted.
We have reviewed the LP&L request art agree.that-the current procedure for sampling irposes a safety hazard *c the technician. The proposed alternate' san.pling technique will utilize the valves designated EGF-110A(B) to draw off.
a sample after "several liters of fuel oil".have been flushed frcm the.line.
The transfer pump will have be a run in a recirculation mode prior to the sampling to clear the pump and recirculation line.
LP&L should assure that sufficient oil has been drained off before taking the saniple; several liters as rer.tioned should be checked to see that this volume sufficiently flushes the line out to the valves designated EGF.111A(B).
We are also awarn that LP&L will investigate the use of a new sampling niethod er.d ASTli code for particulates.
LP&L should proceed with those-investigations-and inform this office of the results, o
Based on our review of the LP&L request, we find the proposal acceptable.
Pursuant to ASTM D270-1975, Section 11, LP&L is authorized to obtain samples by the described process from valves EGF.110A(B) in lieu of-the requirement'to s
obtain semples from the top of the tank.
Sincerely, Frederick J. Hebdon, Director Project Directorate IV l
Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation cc:
See next page DISTRIBUTION Docket File NRC PDR Local PDR PD4 Reading l
G. Holahan MS 13E4 F. Hebdon P. Noonan D. Wi ginton
- OGC-Rockville E. Jordan MS MNBB 3701 ACRS 10)MSP-315 i
FD4 Plant File E. Tomlinson MS 11F23 i
- See previous concurrence.
1
\\
1 5Ft~iPDT/[A
- PD4/PP.
- 0TSB*
'iftf4/W s....:.....
..:............:....g
.Wigginton:bj:ETomlinson:FHebdin,....:............:............:.........
NAME :Piloona g....:............:....h/90 pATE ':04////90
- 04/
- 04/11/90
- 04/itj90 0FFItlXI.~RECDRD COPY
~
Dochnint Narie:~~ E ETR/76159 02
~
a l
1
s hr. Jerrold G. Dewease Waterford 3_
Louisiana Power & Light Company cc:
4 W. Halcolm Stevenson, Esq.
Regional Administrator, Region IV-Monroe & Leman U.S. Nuclear Regulatory Commission 201 St. Charles Avenue, Suite 3300 Office of Executive Director for New Orlear,s, Louisiana 70170-3300_
Operations 611 Ryan Plaza Drive, Suite 1000 Mr. E.'Blake Arlington, Texas 76011 Shaw, Pittman, Potts & Trowbridge 2300 N Street, NW Mr. William H. Spell, Administratcr 4
Washington, D.C.
20037 Nuclear Energy Division Department of Environmental Quality Resident Inspector /Waterford NPS Post Office Box 14690 Post Office Box B22 Baton Rouge, Louisiana 70ES8 Killona, Louisiana 70066 Mr. Ralph T. Lally President, Police Jury Manager of Quality Assurance St. Charles Parish Middle South Serefces, Inc.
Hahnville, Louisiana 700S7 Post Office Box 61000 New Orleans, Louisiana 70161 Chairmar.
William A. Cross Louisiana.Fublic 5ervice Commission Bethesda Licensing Office One American Place, Suite 1630 3 Metro Center Daton Rouge, Louisiana 70825-1697 Suite 610 Cethesda, Maryland 20814 Mr. R. F. Burski Nuclear Safety and Regulatory Affairs Manager Louisiana Power & Light Ccmpany 317 Baronne Street New Orleans, Louisiana 70112 i
-