Text
^
t 30 tto
'o 8
g UNITED STATES -
NUCLEAR REGULATORY COMMISSION-o
- i E
WASHINGTON, D. C. 20665 9
.J.
DUQUESNE LIGHT COMPANY
.i OHIO EDISON COMPANY-PENNSYLVANIA POWER-COMPANY 7
DOCKET NO. 50-334 BEAVER VALLEY POWER STATION ~ UNIT NO. I AMENDMENT TO FACILITY OPERATIN0' LICENSE Amendment No,'153 -
l License No. DPR-66=
1._
The Nuclear Reculatory Commission ~(the Commission) has found that:-
A.
The application for amendrent by Duquesne Light Company, et-a1.
(the licensee) dated February 7, 1990, complies with the standards and requirements of the Atomic-Energy Act of 1954, as ' amended (the Act) and the Commission's_ rules and regulations set forth in 10 CFR Chapter I; B._
The facility will operate in_ cerformity with the' application, i
I the provisions of the'Act, and the rules and regulations of-1 the tcmmission; 3
C.
There is reasonable assurance (1)'.that the activities authorized by this amendment can be conducted without endangering the' health and safety of the public, and (ii)-that such. activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will net be inimical to-the common-defense and security or to the health and safety-of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all' applicable-requirements
[
have been satisfied.
h i
9004230430 900412 DR ADOCK 03000334 PDC
,,-c..
~
L 1
-4 a
2.
Accordingly, the license is amended by changes to the Technical i
Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-66 is hereby amended to read as follows 1
(2) Technical Specifications t
.The Technical Specifications contained-in Appendix A, as revised-through Amendment No. 153, are-hereby. incorporated in the license, e
.The licensee shall operate the facility in accordance with the Technical Specifications, j
3.
This license amendment is effective as of the date of its' issuance, to be implemented within 45 days of issuance..
FOR THE-NUCLEAR REGULATORY C0tiMISSION Jo Tr-F. Stolz, Direc3or.
1 PrfjectDirectorate4-4 i
ivision of Reactor Projects'- I/II
~
Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of issuance:
April 12,1990 t
y a-e
1
- i ATTACHMENT TO LICENSE AMENDMENT NO.'153.
FACILITY OPERATING LICENSE NO.=DPR-66 DOCKET NO. 50-334 4
Replace the following pages of the Appendix A (Technical Specifications) with the enclosed pages as indicated.- The revised pages are identified by-amendment number and contain vertical lines-indicating the areas of change..
Remove Insert 3/4 8 3/4 8-6.
t 3/4 8-6a
~
s e
P
~
.n
.,e--
l l *,.
ELECTRICAL POWER SYSTEMS 3/4.8.2 ONSITE POWER DISTRIBUTION SYSTEMS
\\
l A.C.
DISTRIBUTION - OPERATING l
LIMITING CONDITION FOR OPERATION R3.8.2.1 The following electrical busses shall be energized in the specified manner with tie breakers open between redundant busses within the unit.
a.
Train A
-A.C. Emergency Busses consisting of:
l l
1) 4160-Volt Emergency Bus #1AE, and l
2) 480-Volt Emergency Bus #8N.
b.
Train B A.C. Emergency Busses consisting of:
1) 4160-Volt Emergency Bus #1DF, and 2) 480-Volt Emergency Bus #9P c.
120-Volt A.C.
Vital Bus #I energized from its associated inverter connected to D.C. Bus # 1-1 d.
120-Volt A.C.
Vital Bus #II energized-from its associated inverter connected to D.C.
Bus # 1-2 e.
120-Volt A.C. Vital Bus #III energized from its associated inverter connected to D.C. Bus # 1-3 f.
120-Volt A.C.
Vital Bus #1V energized from its associated inverter connected to D.C. Bus # 1-4 APPLICABILITY:
MODES 1, 2,
3, and 4.
ACTION:
a.
With one of the required trains of A.C. emergency busses not fully energized, re-energize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.
With one A.C.
Vital Bus not energized, re-energize the A.C. Vital Bus within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be-in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
c.
With one A.C.
Vital Bus either not energized.from its associated
- inverter, or with the inverter not connected to its associated D.C.
- Bus, re-energize the A.C.
Vita) Bus from its associated inverter connected to its associated D.C. Bus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
BEAVER VALLEY - UNIT 1 3/4 8-6 kaendment No. is,153
ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS 4.8.2.1
.The specified busses-shall be determined energized in the required manner at least once per 7 days.by verifying correct breaker alignment and indicated voltage on the busses..
t 7
l l
l l
l l
l l
l l
BEAVER VALLEY - UNIT 1 3/4 8-6a Am ndment No.
153 l
l
s uo y s
v q7f ng UNITED STATES' o
_.g NUCLE AR REGULATORY COMMISSION:
5
-0
, _'E WASHINGTON, D. C. 20555
- ...+
i DUQUESNE-LIGHT COMPANY OHIO EDISON COMPANY-THE CLEVELAND' ELECTRIC-ILLIMINATING COMPANY.
-THE TOLEDO EDISON COMPANY y
l-DOCKET NO. 50-412-o BEAVER VALLEY POWER STATION,'UFIT NO. 2 FENDMENTTO' FACILITY 0PERATING~ LICENSE i
Amendaent No. 30 L
License No. IIPF-73:
1.
The Nuclear-Regulatory Commission (the Connission)- has.found thati-A.-
The application for amendment by Duquesne-Light Company, et al.
(the licensee) dated February 7,:1990 complies ~with the standards and requirements of the Atcmic Energy Act of 1950, as amended (the Act)~
and the Commission's rules and reguletions set forth;in 10 CFR-t l
Chapter I;-
1 B.
The facility will o>erate in conformity with the application, the provisions of tie Act, and the rules and regulations of the Consnission; C.
There is retscrable essurance (i) that the. activities authorized by this amendment can be conducted without endar.gering-the heelth and safety of the public, and (ii) that such activities will be conducted in complience with the Commission's regulations;.
D.
The issuance of this amendment will not-be inimical to the common defense and security or to the health and safety of'the public; and E.
The issuance of this amendment is in accordance.with 10 CFR'Part 51 of the Commission's regulations and all-applicable requirements have been satisfied.
n
.{', ' \\ j t
. -.. ~
E
= r
\\ ?. '
1
\\'
2.
Accordingly, the license is amended byLchanges to'the. Technical Specifications as indicated inLthe attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating' License-No. NPF-73 is hereby amended to read as follows:
(2) Technical Specifications
~
The Technical Specifications contained in Appendix A, as revised through Amendment No. 30, and the Envirnnmental Protection Plan contained in Appendix-B, both of which are attached hereto are hereby incorporated in the. license. DLC0 shall operate the-facility in accordance with the Technical Specifications'and the Environmental Protection Plan ~.
3.
This license amendment is effective on issuance, to be_ implemented within 45 days of. issuance.
FOR THE NUCLEAR REGULATORY COMMISSION
($d[dd Joh 'f. Stolz, Direc r Project Directorate
-4
\\ Division of Reactor Projects -- 1/II Office of Nuclear Reactor Regulation
Attachment:
' hanger to the Technical C
Specifications Date of Issuance: April 12,1990 4
4
--e e-
f i
ATTACHMENT TO LICENSE AMENDMENT !!O. 30
[
FACILITY OPERATING LICENSE NO..NPF-73 DOCKET NO. 50-412.
t' Replace.the following pages of the Appendix A (Technical Specifications)-
with the enclosed pages as indicated.. The: revised pages are identified by amendment number and contain vertical lines indicating the areas of change.
Remove Insert 3/4 8-7 3/4 8-71 l
(
F i
x-ELECTRICAL POWER SYSTEMS 3/4.8.2 ONSITE POWER ~ DISTRIBUTION' SYSTEM.
'A.C.
DISTRIBUTION - OPERATING 4
iLIMITING CONDITION FOR OPERATION 3.8.2.1.The following electrical' busses shall be' energized in the specified manner with tie breakers open between redundant busses within the unit.
a.
Train A A.C. Emergency Busses consisting of:
1.
4160-Volt Emergency Bus #2AE, and>
1 2.
480-Volt Emergency Bus #2N.
b.
Train B A.C. Emergency Busses consisting of:
1.
4160-Volt Emergency Bus #2DF and-2.
480-Volt Emergency Bus #2P c.
120-Volt A. C.
Vital Bus #I energized from its associated inverter connected to D.C. Bus # 2 d.
120-Volt A. C.
Vital Bus #II energized from its associated inverter connected to D.C. Bus # 2-2 e.
120-Volt A.C.
Vital Bus #III energized from its associated inverter connected to D.C. Bus # 2-3 i
f.
120-Volt A.C.
Vital Bus #IV. energized from its ' associated inverter connected to D.C. Bus # 2-4 APPLICABILITY:
MODES 1, 2, 3, and 4 ACTION:
With one of the required trains of A.C. emergency busses not fully i
a.
energized, re-energize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
I b.
With one A.C.
Vital Bus not energized, re-energize the A.C. Vital Bus within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next-6 hours and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
c.
With one A.C.
Vital Bus either not energized from its associated inverter, or with the inverter not connected to its associated D.C.
Bus, re-energize the A.C.
Vital Bus from its associated inverter connected to its associated D.C. Bus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS 4.8.2.1 The specified busses shall be determined energized in the required manner at least once per 7 days by verifying correct breaker alignment and indicated voltage on the busses.
BEAVER VALLEY - UNIT 2 3/4 8-7 Amendment No. 30'
-..