Environ Assessment & Finding of No Significant Impact Re Util 870112 & 890731 Requests for Nine Exemptions from App R to 10CFR50 for Fixed Fire Suppression Sys,Alternate Shutdown Capability & Emergency Lighting
ML20033F418
Person / Time
Site: Davis Besse 
Issue date: 03/15/1990
From: Hannon J
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20033F417 List:
References
NUDOCS 9003200379
Download: ML20033F418 (6)


Text

b 7590-01

.vm UNITED STATES NUCLEAR REGULATORY COMMISSION TOLEDO EDISON COMPANY A!!E THE CLEVELAND ELECTRIC ILLUMINATING COMPANY DAVIS-BESSE NUCLEAR POWER STATION, UNIT NO. 1 DOCKET NO. 50-346 ENVIRONMENTAL ASSE!3 MENT-AND FINDING OF NO SIGNIFICANT IMPACT The U. S. Nuclear Regulatory Commission (the Commission) is considering issuance of a number of exemptions from the requirements of Appendix R to 10 CFR Part 50 in response to a request filed by the Toledo Edison Company ar.d The Cleveland Electric Illuminating Company (the licensees), for the Davis-Besse Nuclear Power Station, Unit No. 1, located in Ottawa County, Ohio.

E!!VIRONMEllTAl. ASSESSMENT Identification of Preposed Action The Toledo Edison Company (the licensee) submitted in its letter dated January 12, 1987, a request for nine specific exemptions from the requirements of Appendix R to 10 CFR Part 50. The licensee later submitted in its letter dated July 31, 1989, a request for three additional exemptions from Appendix.R.

In its subsequent letters dated January 18, March 15, and October 26, 1989, the licensee withdrew its requests for three of these exemptions.

Additionally, the staff found that one of the others was not required.

Each of the remeining eight exemption requests is discussed below with a description of the pertinent Appendix R requirement and a brief description of the nature of the deviation from the applicable Appendix R requirement.

9003200379 900315 3

-PDR.ADOCK 05000346 F

PDC

4

' For Fire Areas R, EE and AB, the last paragraph of Section III.G.3 of Appendix R requires that a fixed fire suppression system be installed in these three fire areas in that an alternate shutdown capability and its l

associated circuits is provided for these areas.

Fire Area R has an alternate shutdown capability in Fire Area BD for the service water system and has an alternate shutdown capability in Fire Area 11 for the control valves of the turbine driven auxiliary pumps, Fire Area EE has an alternate shutdown capability in Fire Area II which l

is physically and electrically independent in the event of fire damage to the circuits or electrical components of the M5106 main steam inlet isolation valve for auxiliary feedwater pump turbine No. 1 Fire Area AB has an alternate shutdown capability in Room No. 115 for potential fire damage to circuits associated with the emergency core cooling rystem (ECCS) room cooler fans C31-1 and C31-2.

For Fire Area A and for embedded conduits,Section III.G.2.a of Appendix R requires _in part that cables and equipment and associated nonsafety circuits of redundant trains be separated by a fire barrier having a 3-hour rating.

While there are, in general, 3-hour fire barriers in Fire Area A between redundant circuits used to achieve and maintain hot shutdown conditions.

-there'is a nonrated door as well as a number of nonrated heating ventilating andair-conditioning (HVAC) penetrations. These nonrated features compromise the fire barrier between redundant electrical circuits in Room Nos. 124 and 123 and those in Room No. 115 within Fire Area A.

fI

' )

e i

i Certain cables of electrical circuits required to achieve a safe shutdown in the event of a fire and which are enclosed in conduit and embedded in concrete were not evaluated by the licensee in its safe shutdown analysis for a fire. As discussed above, the placement of these cables does not meet the Appendix R requirements specifying that they be separated by a 3-hour fire barrier. The specific cables involved are listed in Appendix B-2 of the Davis-Besse Appendix R Compliance Assessment Report (CAR),

Section III.J of Appendix R requires that emergency lighting units with at least an 8-hour battery power supply be provided in all areas needed for operation of safe shutdown equipment and in access and egress routes thereto.

The licensee has requested approval to utilize existing "hard-wired" AC/DC essential lighting systems in portions of the auxiliary and turbine buildings and to utilize hand-held portable lighting units in outside plant areas, in lieu of meeting the specific requirements of Section III.J cited above.

For Fire Area D,Section III.G.2.d of Appendix R requires for non-inerted containments that cables and equipmant and associated nonsafety circuits of l

redundant trcins be separated by a horizontal distance of more than 20 feet l

l with no intervening combustibles er fire hazards. However, in Fire Area D

(

(i.e., the primary reactor containment), redundant containment air cooler l

l fans Cl-1, Cl-2 and Cl-3 are about 10 feet apart.

In manhole MH 3001,Section III.G.2.b of Appendix R requires in part that cables and equipment and associated nonsafety circuits located within the l

same fire area outside of primary containment and required to achieve and maintain hot shutdown conditions of the reactor be separated by a horizontal distance of more than 20 feet with no intervening combustibles or fire l

I

f I

I hazards.

However, there are redundant circuits in manhole MH 3001 associated withtheservicewatersystem,includingpumps(P3-1,P3-2andP3-3),the backuppump(P-180), valves (SW1395andSW1399)andmotorcontrolcenters (MCCs,E12CandF12C)whicharelessthan6feetfromoneanother.

The Need for the Proposed Action The proposed exemptions are needed because the features described in the licensee's requests regarding the existing level of fire protection and proposed modifications at the plant are a practical method of meeting the intent of Appendix R and literal compliance would not significantly enhance the fire protection capability.

Environmental Impects of the Proposed Action The proposed eight exemptions cited above are from the specific renuirements of certain provisions of Appendix R to 10 CFR Part 50.

For each of the requested exeirptions, the licensee has provided.iustification for the requests demenstrating that it is providinq equal protection for the safe shutdown capability of the Davis-Besse facility in the event of a fire within any of the fire areas affected by the proposed exemptions. On this basis, there are no changes in the manner of the plant operation in the event of a fire.

Accordingly, there will be no increase in either the probability or the amount of radiological release from the Davis-Besse plant in the event of a fire. Therefore, the Commission concludes that there are no significant radiological environmental impacts associated with the proposed exemptions.

f; c.

With regard to potential nonradiological impacts, the proposed exemptions cause no chance in the manner of the plant operation. They do not affect-nonradiological plant effluents and have no other environmental impact..There-fore, the Comission concludes that there are no significant nonradiological environmental impacts associated with the proposed exemptions.

Alternative to the Proposed Action Since the Comission concluded that there are no significant environmental impacts associated with the proposed actions, any alternatives would have either no or greater environmental impact.

The principal alternative would be to deny the requested exemptions.

This vould not reduce the environmental impacts attributed to the facility but v:ould result in the expenditure of resources without any compensatinc benefit.

Alternative Use of Resources This action does not involve the use of any resources not previously considered in the Final Environmental Statement for the Davis-Besse t>uclear Power Station, Unit 1, dated March 1973 end its supplement dated October 1975.

Agg etes and Persons Consulted The NRC staff reviewed the licensee's request and did not consult other acencies or persons.

FINDING 0F H0 S!GNIFICANT IMPACT The Comission has determined not to prepare an environmental impact statement for the proposed exemptions.

4

.j 6-1 Based upon the foregoing environmental assessment, we conclude that the proposed action will not have a significant effect on the quality of the human environment.

For further details with respect to these actions, see the requests for exemptions dated January 12, 1987 and July 31, 1989 which are available for public inspection at the Commission's Public Document Room 2120 L Street, N.W., Washington, D.C. and at the University of Toledo Library, Docunents Department, 2801 Bancroft Avenue, Toledo, Ohio 43606.

Dated at Rockville, Maryland, this 15th day of March 1990.

FOR THE NUCLEAR REGULATORY COMMISSION

/

Jo n N. Hannon, Director Project Directorate III-3 Division of Reactor Projects - III, IV, Y and Special Projects Office of Nuclear Reactor Regulation I