ML20033B005
| ML20033B005 | |
| Person / Time | |
|---|---|
| Site: | Duane Arnold |
| Issue date: | 11/18/1981 |
| From: | Mineck D IES UTILITIES INC., (FORMERLY IOWA ELECTRIC LIGHT |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| DAEC-81-558, NUDOCS 8111300271 | |
| Download: ML20033B005 (1) | |
Text
.
s n.$
,k Iowa Electric Light and Ibwer Company
,i November 18, 1981 DAEC-81-558 c
l' r
Sr! James G. Keppler, Director Of fice of Inspection and Enforcement - Region III o
N U. S. Nuclear Regulatory Commissior, g
799 Roosevelt Road 8
r f
Glen Ellyn, IL 60137 g
t Nov I IS8/d'
/
Subject:
Prompt Notification of a
- u,5 gg E g
Reportable Occurrence e
//-
File: A-118a g
G
Dear Mr. Keppler:
This letter, telecopied to your office, is intended to satisfy the requirement for prompt notification of a Reportable Occurrence in accordance with-Specification 6.11.2.a of the Duane Arnold Energy Center Technical
,SpLcifications.
('
Technical Specification paragraph (s) violated:
1
/., v Description Occurrence:
i On 11/18/81 during normal operation, operations personnel attempted to -
cycle reactor water cleanup system return isolation valve MOV-2740. An investigation was initiated after it was found that no flow changes occurred in response to tne valve being cycled. The investigation revealed that the valve stem clamp setscrew had become loose which allowed the clamp key to drop out. This allowed the stem to rotate whenever the motor operator was cycled and resulted in no valve disk movement. The isolation function of the valve was thus compromised. The key has been reinstalled and the stem ' clamp restored to its original configuration. M0V 2740 is a 4 inch anchor globe valve.
Very truly yours, Daniel L. Mineck h
U Chief Engineer i ' ;,
Duane Arnold Energy Center 2
b DLM/JVS[pl
~
cc:
U. S. NRC Resident Inspector
+
i tj
.8111300271 811118 TEP Si e (PDR ADOCK 05000331
..S PDR 3 3 6g (
thiane Anusid Energv Center
- In Ikm 351
- Cedar llapids, lomn 52406
- 319/851-5611 %
u. '"
i