YANKEE ATOMIC ELECTRIC COMPANY Time.
1345 !!rs.
,(
- Date:
L v. 5, 1981
, Yay k Rowe,Mos:achusetts 01367 uxne.
~
IN{*j f
s N
/8 I
u November 6, 1981 NOV1 G Iggy $
\\N U.s. w-7.
mm United States Nuclear Regulatory Comission d
hmc=, 43 Off:ce Of Inspection and Enforcement Q,
p Rer, ion I 4.*'
- 63) Park Avenue m
King of Prussia, Pa.
19406 Attention: Mr. R. C. ficjes
Dear Mr. flaynes:
Pursuant to the requirements of Technical Specifications, Section 6.9.4.a, the following is reported as Licensee Event Report 50-29/
81-29, Failure Of Relays In The MC Flow (MCP Current) Trip System.
hhile 1,erforming OP-4606, Main Coolant Flow Trip (Main Coolant Pump Current) Functional Test, the System A loop 4 Phase B Undercurrent Relay and the System B loop 2 Phase A and Loop 4 Phase C Undercurrent Relays failed to trip. The relays were manually tripped, then exercisod several times with the relays functioning properly each time.
Inspection and cleaning of the relays will be performed.
A 14 day report will follow.
Very truly yours, NJ7s l'
R flerbert A. Autio Plant Superintendent NNS/ meg Direc'toriiOffide.ofi anagement Information M
cc:
[2]
6 Program. Control (USNRC)
Ui. x. 1
[1] Managerg p;0pgrations, (YAEC)
[1] NSARC Cnaiman (YAEC)
[1] Manager of Operational Quality ?ssurance, (YAEC) 8111170491 011106 e;T" PDR ADOCK 05000029 S