Text
__
Commonwealth Edison
'1 One First National Plaza. Chicago. filinois Address Reply to: Post Office Box 767 Chicago, minois 60690 November 6, 1981 gi 4'
7 4 (:T ' '/
Mr. James G. Keppler, Director s
's Directorate of Inspection and
,7 +, O Enforcement - Region III p/
7 L
U.S. Nuclear Regulatory Commission
-]
E
- kpk [8 799 Roosevelt Road
'c Glen Ellyn, IL 60137
?
g q
"M
Subject:
LaSalle County Station Units 1 an, 3t ASCO Solenoid Valve Qualification b 10 CFR 50.55(e), Final Re, ort No. 81-09 NRC Docket Nos. 50-373/374
Dear Mr. Keppler:
Commonwealth Edison Company notified your office on October 7,
1981, of a deficiency in accordance with 10 CFR 50.55(e).
Based on information received from ACF Industries, W-K-M Valve Division, thirty-six (36) unqualified solenoid valves were delivered to and installed at LaSalle County Station, Units 1 and 2 (see attached).
Tnis letter fulfills the 30 day reporting requirement of 10 CFR 50.55(e).
This deficiency occurred through unclear information on the Valve Data Sheets supplied to W-K-M which resulted in a significant deviation from performance specifications.
We have found it to be an isolated occurrence and we will replace all of the unqualified l
valves with aualified ones.
The qualified valves for Unit I are on site and will be installed prior to fuel load.
The qualified valves for Unit 2 will be installed upon delivery.
If there are any questions in this regard, please contact this office.
Ve ry t ruly yours, Cb c
C.
E. Sargent Nuclear Licensing Administrator cc:
A. Bournia (NRR-DL)
NRC Resident Inspector - LCSC 1m 8111130476 811106 1
PDR ADOCK 05000373
/$
S PDR i
2834h NO
- k 1981
c.
ATTACHMENT Identification of Unqualified. Solenoid Valves-Unit 1 Unit 2 1E12-F327A 2E12-F327A 1E12-F3278 2E12-F3278 lE12-F327C 2E12-F327C-1E51-F355 2E51 c355 1E51-F354 2E51-F354 lE21-F333 2E21-F333 lE22-F354 2E22-F354 lIN-001A 2IN-001A IIN-001B 2IN-001B IIN-017 2IN-017 IIN-074 21N-074 IIN-075 2IN-075 1RF-012 2RF-012 1RF-013 2RF-013 1RE-024 2RE-024 1RE-025 2RE-025 1RE-026 2RE-026 1RE-029 2RE-029 i
i l
2834N
[.