Ro:On 801104,as a Result of Performing Flush on Unit II Fire Header Fire Protection Tanks,A & B Vols Fell Below Tech Spec Limits.Details to Be Provided in Followup Rept
ML20030C188
Person / Time
Site: Farley  Southern Nuclear icon.png
Issue date: 11/05/1980
From: Hairston W
ALABAMA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
FNP-80-1434, NUDOCS 8108250487
Download: ML20030C188 (1)


Text

.

  • i ICIAL co,,,

') TD i!!

NU 10 AlabamaPower the Southem eWtrC syStern P. O. Drawer 470 Ashford, AL 36312 November 5,1980 gg-otP '

Mr. J. P. O'Reilly, Director U. S. Nuclear Regulatory Commission 101 Marietta Street, N. W.

Atlanta, Georgia, 30303

Dear Mr. O'Reilly:

This is to confirm the telephone all to Mr. Bob Martin (NRC) at 1445 on November 5, 1980 by Mr. W. G. Hairston, III (APCo) in accordance with Tech.

Spec. 3.7.11.1.b.

As a result of performing a flush on the Unit II fire header, the Fire Protection Tanks A and B volumes fell to approximately 231, 297 gallons each at 2020 on 11/4/80. Tech. Spec. 3.7.11.1.b requires a minimum volume of 250,000 gallons in each tank.

The tank volumes were returned to 250,000 gallons at 2235 on 11/4/80.

Further details will be provided in the followup report.

Sincerely Yours, T

g.M W. G. Hairston, III A t Manager t

p I th@gp,... Farley Nuclear Plant 8'

9/

'/

i WGH/HMM:jpd

.?

/

1 cc:

H. O. Thrash S-T 5

I R. D. Hill Qk

/

il n

.a Nya 3

/'o,i.@

~I'1 CIA L r PDR ADOCK 05000348 TfAw 8108250487 801105 J

1 0

PDR

/I