ML20029C293

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in Insp Rept 50-309/88-80.Corrective Actions:Plant Relay Data Base Will Be Developed & Certain Agastat Relays Evaluated by 901231
ML20029C293
Person / Time
Site: Maine Yankee
Issue date: 12/28/1990
From: Nichols S
Maine Yankee
To: Martin T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20029C285 List:
References
MN-90-129, SEN-90-344, NUDOCS 9103270129
Download: ML20029C293 (2)


Text

1

?-

MaineYankee 6fii4#U M MARifabuMM i!iWissig ED! SON DRIVE e AUGUSTA, MAINE 04336 * (207) 622 4868 s

l December 28, 1990 MN-90-129 SEN-90-344 i

UNITED STATES NUCLEAR REGULATORY COMMISSION Region 1 475 Allendale Road King of Prussia, PA 19406 Attention:- Mr. Thomas T. Martin, Degional Administrator a

References:

(a)

License No. DPR-36 (Docket No. 50-309)

(b) USNRC Letter to Maine Yankee dated January 20, 1989 - Inspection i

Reprt No.. 50-309/88 Special Maintenance Team Inspection (c) Maint Yankee Letter to USNRC dated April 13, 1989 - Response to

-Inspection Report 50-309/88 Maintenance (d) Maine Yankee Letter to USNRC dated March 30, 1990 (MN-90-35) -

Follow-up

Response

to Inspection Report 50-309/88-80 Maintenance

Subject:

Followup Retponse to Inspection Report 50-309/88 Maintenance f

Gentlemen-Reference (b) reported the results of a special maintenance team inspection of Maine Yankee. We provided our response to those areas of identified weaknesses with References (c) and (d).

The purpose of this letter is to provide an updated completion date for one of these issues.

In response to _ Weakness 11.4.7, we _ indicated that we planned to develop a plant relay data base and evaluate certain Agastat relays, to be completed by December 31, 1990. The completion of this effort has been rescheduled and we currently anticipate completion by December 31, 1991. The rescheduling of the expected completion date has been necessary as a result of a large increase in the scope and effort required to develop the ' relay data base 'and then perform the review required to determine whether commercial-grade Agastat relays have been used in safety-class applications.

i The data base will identify whether or not the relay should be a safety-class relay-or not. Since the data base will not contain actual individual relay serial numbers, all. Agastat E7000 series relays reflected in the data base will have to be walked down to ensure.a commercial-grade relay is not actually installed.

SEN90344.LTR 9103270129 9/03 2 0

~

l'

{DR ADocK c500o309 PDR J

-e:

~

+

1 ;.1 MaineYankee

~

UNITED STATES NUCLEAR REGULATORY COMMISSION MN-90-129 l Attention: Mr. Thomas T. Martin _

Page Two 1

The development of the relay data base has been in progress since December 1989.

We' anticipate ~ that it will be complete to the point of identifying all safety-class relay requirements by May 1991.. The effort to ensure there are not any commercial-grade relays ~ installed in safety-ciass applications will be de3endent on the number.

E of E7000 serie.s relays identified in the data base.

In addition, walkdown of some-safety-clast relays rray'only be possible during an outage.

We therefore expect to complete the effort of ensuring there are not any commercial-grade 70VO series relays

.in safety-class applications by the end of our next outage (December 31,1991).

A review of our procurement records indicates-that there have not been any-

. purchases of commercial-grade 7000 series ' relays in the. past -five years.

- All procurements.have been for safety-class relays.

In addition, a review of our stock records indicates that only commercial-grade 7000 series relays have been. issued from

= stock and these have been for non-nuclear system applications.

Thus,_ assurance

-exists that there have not been any commercial-grade 7000 series relays installed in-safety-class ' applications (if there ever were any) and a one year delay in the projected ' completion of this project does not adversely impact public health and 3

~ safety.

Should you have any questit # on these issues, please contact us.

t Very truly yours,

% d4 5

S. E. Nichols, Manager Nuclear Engineering and Licensing

. BD/sjj-W q

c:

cDocument Control Desk

Mr. Charles S. Marschall-o LMr. Eh H.LTrottier

~

a 21 'MI -4 L ). *

-SEN90344.LTR n

L D

_.g.

F