Insp Rept 99901132/88-01 on 880914.No Violations or Deviations Noted.Major Areas Inspected:Vendors Supply of Molded Case Circuit Breakers to Westinghouse Nsd for Subsequent Dedication
ML20029A092
Person / Time
Issue date: 12/15/1988
From: Jeffrey Jacobson, Potapovs U
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20029A085 List:
References
REF-QA-99901132 99901132-88-01, 99901132-88-1, NUDOCS 9102040047
Download: ML20029A092 (3)


Text

_._ _

ORGANIZATION: WESTINGHOUSE ELECTRIC SUPPLY COMPANY 4

MURRAYSVILLE, PENNSYLVANIA REPORT INSPECTION INSPECTION NO.:

99901132/88-01 DATE:

9/14/88 ON-SITE HOURS: 8 CORRESPONDENCE ADDRESS: Westinghouse Electric supply Company Mr. C. Antonikas, Branch Manager Post Office Box 607 Murraysville, Pennsylvania 15668 ORGANIZATIONAL CONTACT: Cris Antonikas TELEPHONE NUMBER:

(412) 733-6800 NUCLEAR INDUSTRY ACTIVITY: Westinghouse Electric Supply Company (WESCO)

Murraysville supplies safety-related relays and other commercial grade com-ponents to Westinghouse Nuclear Service Division (NSD) for sale to the nuclear industry.

ASSIGNED INSPECTOR:

6

'L

/7////i A J, B.'JfCobson, Special Projects Inspection Uate 7

Section (SPIS)

~

OTHERINSPECTOR(S):

J. Knox, SPIS APPROVED BY: /

/.< I -

/

/

. PotapeM, Section Chief, SPIS ate INSPECTION BASES AND SCOPE:

A.

BASES:

10 CFR Part 21 and Appendix B to 10 CFR Part 50.

B.

SCOPE:

This limited inspection was conducted to review activities related to WESCO's supply of molded case circuit breakers.to Westinghouse NSD for subsequent dedication.

PLANT SITE APPLICABILITY:

All nuclear facilities using Westinghouse molded case circuit breakers.

9102040047 910129 PDR OA999 EMVWEST 99901132 PDR

ORGANIZATION: WESTINGHOUSE ELECTRIC SUPPLY COMPMAY MURRAYSVILLE, PENNSYLVANNIA REPORT INSPECTION NO.: 99901132/88-01 RESULTS:

pAGE ? of 3 A.

VIOLATION:

None B.

NONCONFORMANCE:

None C.

STATUS OF PREVIOUS INSPECTION FINDINGS:

None D.

OTHER FINDINGS AND COMMENTS:

During the inspection, a review was conducted of the WESCO, Murraysville activities relative to their supply of comercial grade molded case circuit breakers to Westinghouse NSD. Over the last three years, WESCO Murraysville has supplied approximately 200 molded case circuit breakers to the Westinghouse NSD dedication program. Of particular concern was where WESCO obtained the breakers sold to Westinghouse NSD. Recent Information has alerted the NRC to a large supply of refurbished molded case circuit breakers that have infiltrated the commercial marketplace (detailed in NRC Information Notice 88-46).

At the time of the inspection, WESCO was already in the process of determining their supply sources for the 200 breakers and had completed their record review for the 65 most rer'at orders. All of the orders reviewed had been supplied by the Westinghouse business unit that

.3 manufactures the type of breakers in question.

In addition, the NRC inspectors reviewed a sample of the orders and confinned they had indeed been supplied by the Westinghouse business unit.

When WESCO was questioned as to where else they procure breakers, the inspectors were told that if the breakers were unavailable from the business unit. WESCO might go to another WESCO office or outside the Westinghouse Corporation to obtain the breakers. However, WESCO stated that they could not remember ever having to do this for any of the breakers supplied to Westinghouse NSD.

In addition, to the above review, the NRC inspectors reviewed the WESCO financial records for payments to suppliers for 1986, 1987, and 1988.

Several of the suspected circuit breaker refurbishers appeared on the list and in fact had supplied circuit breakers to WESCO Murraysville over this time period.

Each of the orders originating from the suspect companies were tracked and found to have been supplied to non-nuclear customers.

ORGANIZATION: WESilNGHOUSE ELECTRIC SUPPLY COMPMAY MURRAYSVILLE, PEhNSYLVANNIA REPORT INSPECTION NO.:

99901132/88-01 RESULTS:

PAGE 3 of 3 A review of the material currently in stock at the WESCO warehouse revealed that the five samples for which records were requested, all had originated from the Westinghouse business unit.

In suninary the NRC review determined that currently no procedures are in place that would prevent WESCO Murraysville from supplying Westinghouse NSD with breakers from other WESCOs or from sources outside the Westinghouse Corporation.

However, the review conducted determined that for the breakers previously sold to Westinghouse NSD, reasonable assurance exists that the breakers originated from the Westinghouse business unit as new and were not refurbished material.

Should Westinghouse NSD continue to procure commercial grade molded case circuit breakers from WESCO Murraysville, procedures would need to be implemented to ensure that only new Westinghouse breakers are supplied.

E.

PERSONS CONTACTE0:

C. Antonikas, Branch Manager K. Gordan, Branch Administrative Manager.

S. Cunningham, Westinghouse Electric, Monroeville l

_ _ ~

s JAN 2 9 f991 t

Docket No. 9991132/88 01 Mr. C. Antonikas, Branch Manager Westinghouse Electric Supply Company Post Office Box 607 Murraysville, Pennsylvania 15688

Dear Mr. Antonikas:

This letter addresses the inspection of your facility at Murraysville, Pennsylvania, conducted by Messrs. J. Jacobson and J. Knox of this office on September 14, 1988, and the discussions of their findings with you and other members of your staff at the conclusion of the inspection.

Release of this report was delayed due to the NRC's ongoing review of nonconforming and substandard vendor products.

The inspection was conducted to review activities relative to your supply of molded case circuit breakers-to Westinghouse Nuclear Services Division for subsequent dedication and sale to the nuclear industry.

This inspection consisted of an examination of procedures and representative records, interviews with personnel, and observations by the inspectors, in accordance with 10 CFR 2.790 of the Commission's regulations, a copy of this letter and the enclosed inspection report will be placed in the NRC's Public tiocument Roor,.

Should you have questions concerning this inspection, we will be pleased to discuss them with you.

Sincerely,

/Sl Edward T. Baker, Acting Chief Vendor Inspection Branch Division of Reactor Inspection and Safeguards Office of Nuclear Reactor Regulation

Enclosure:

Inspection Report 99901132/88 01 DISTRIBUTION VIB/DRIS R/F RIDS Code IE:09 BGrimes BHayes, 01 UPotapovs EBaker KNaidu YanDenburgh JJacobson JKnox WMcNulty 01, RV

  • see p i

/ concurrence DFC

VIB:DR15
SC:VIB:DRlS
D:
VIB:DRIS
SC:VIB:DRIS
BC:V DRIS j_

.f.

l NAME

JJACOBSON*
UPOTAPOVS*

I

  • x :KNAIDU*
CVAN

' GH. BAKER l

DATE

11/28/88
11//01/88
12/15/881/N}/91:1/25/91
1/ W 91
1Aff/91 l

DTFICIAL RECORD COPY Document Name: ANTONIKAS LET"ER l

'