s

.-=.=-----m THE CINCINNATI GAS & ELECTRIC COMPANY ag' -

N WM. H. ZIMMER NUCLEAR POWER STATION CINCINN ATI. OHIO 45201 P. O. BOX 201 January 4, 1983 MOSCOW, OH 45153 QA-2193 L A. BoRGM ANN stN80R v6CE PRESIDENT U. S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 Attention:

Mr. J. G. Keppler Regional Administrator RE:

WM. H. ZUIMER NUCLEAR POWER STATION UNIT 1 I. E. INSPECTION REPORT 82-01 DOCKET NO. 50-358, CONSTRUCTION PERMIT NO.

CPPR-88, WO #57300, JOB E-5590, FILE NRC-1 Gentlemen:

This letter constitutes a supplement to our previous response, QA-1917, dated August 4,1982, concerning the subject Report.

Item 3a(5) of the Report stated, in part, that cable pulling procedure QACMI E-7, addressed cable grip support requirements, but that the Construction Inspection Plans (CIP) did not document these requirements. CG&E committed to verify cable grip installation on vertical runs of cable over 35 feet when installed in conduit, by December 31, 1982.

In preparation for this inspection, it was noted that design specification requirements for grip basket length were unclear. Therefore, Design Document Change (DDC) E-8112 has been issued to establish a minimum installed basket length dimension. It is now expected that this inspection will be completed by January 31, 1983.

We trust the above will be found acceptable as a supplementary response to the subject Report.

Very truly yours, THE CINCINNATI CAS & ELECTRIC COMPANY

= - - -

E. A. BORGMANN SENIOR VICE PRESIDENT cc: NRC Office of Inspection & Enforcement Washington, D.C. 20555 NRC Senior Resident Inspector Attn:

W. F. Christianson Zimmer Project Inspector Region III 8301210037 830118 PDR ADOCK 05000358 0