ML20028D683

From kanterella
Jump to navigation Jump to search
Forwards LER 82-154/03L-0.Detailed Event Analysis Encl
Date released: 02/11/2020 Download: ML20028D683


LER 82-154/03L-0:on 821213,during Routine Channel Function Test,Steam Generator Steam Pressure Channel III Bistable Setpoint Observed Less than 480 Psig.Caused by Failure of Capacitor Incomparator 2PC 526 C/D.Capacitors Replaced
ML20028D693
Person / Time
Site: Salem PSEG icon.png
Issue date: 01/05/1983
From: Frahm R
Public Service Enterprise Group
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML20028D693 (1)
Forwards LER 82-154/03L-0.Detailed Event Analysis Encl
ML20028D682
Person / Time
Site: Salem PSEG icon.png
Issue date: 01/05/1983
From: Midura H
Public Service Enterprise Group
To: HAYNES R C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML20028D682 (3)