L V. MAURIN Voce President Nuckar Operations Janusry 6, 1983 W3I83-0003 Q-3-A35.07.23 Mr. John T. Collins, Regional Administrator, Region IV
]
/
i U. S. Nuclear Regulatory Commission t
r
'"i j
611 Ryan Plaza Drive, Suite 1000
-l s
Arlington, Texas 76012 M101983 i
SUBJECT:
Waterford SES Unit No. 3 8
m Docket No. 50-382 Significant Construction Deficiency No. 23
" Defective Valve Actuators (Fisher Controls)"
Final Report
REFERENCE:
LP&L Letter W3I82-0074 dated October 15, 1982
Dear Mr. Collins:
In accordance with the requirements of 10CFR50.55(e), we are hereby providing two copies of the Final. Report of Significant Construction Deficiency No. 23, " Defective Valve Actuators (Fisher Controls)."
If you have any questions, please advise.
Very truly yours,
{ d.7 L. V. Maurin LVM/ MAL:keh Attachment cc:
- 1) Director 3)
E. Blake Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D. C.
20555 (with 15 copies of report) i l
- 2) Director 4)
W. Stevenson Office of Management Information and Program Control U. S. Nuclear Regulatory Commission l
Washington, D. C.
20555 i
(with I copy of report) l 8301140041 830106 PM ADOCK 05000382 g
y.
n
- 25 0 :5 g
ha a
y 7.
.FkNALREPORTOF-SIGNIFICANT' CONSTRUCTION DEFICIENCY NO.L23c
" DEFECTIVE VALVE ACTUATORS ((FISHER' CONTROLS)'?
- INTRODUCTION;
- This report :is; submitted, pursuant to 10CFR5'0.55(e).
It describes defects in 'the
- Spring Return Actuators.:resulting in replacement of the-spring' guide sleeves.
'c
-This problem is considered reportable:under the requirements of 10CFR50.55(e). :
This problem was identified to the USNRC by G.H. Bettis ' Corporation under 10CFR23..
DESCRIPTION In November 1980, during testing by thel.Hd Bettis Corporation _in'their R &-D G
Laboratory, a defect was discovered in the N521C-SR/N522C-SR (Spring Return)-
Actuators supplied by Jamesbury Corporation,LPO No. NY-403539, and Fisher Controls Company, PO No. NY-403483. Bettis'found that the sp' ring guide sleeve shifting internally could prevent the movement of.the actuator. The failure to actuate ~
l could only occur in the normal power ' stroke, and if the "0" degree position'of' the: valve is actually past the normal "0" of the actuator. These actuators are'
.used.on valves-in the component cooling water and HVAC systems.
~
i SAFETY IMPLICATIONS l
r Further evaluation since.the Interim Report has indicated that this deficiency I
on the component cooling water isolation valves to the Reactor Coolant Pumps (3CC-B188A1, 3CC-B189B1, 3CC-B190A2, and 3CC-B191B2) would not create a safety i
haza.d.
The deficiency is, however, still considered reportable due to its j
effect on HVAC control room isolation valves (3HV-B169A, 3HV-B170B, 3HV-B177A,
~
3HV-B178B, 3HV-B171A, 3HV-B172B). This deficiency could have caused these
~
valves.to fai11to isolate.
CORRECTIVE ACTION IMPLEMENTED
+
The corrective action for this significant construction deficiency involved the reworking of the above mentioned valve actuator assemblies.
i Nonconformance Report W3-3058, along with service forms #81-11-235, 81-11-236, 82-4-49, 82-12-122, and G.H. Bettis-Corporation Corrective Action Report No. 0011 were generated to instruct, track, and document corrective action.
l Corrective action was completed under the direction of the Bettis-representative, using'the above mentioned NCR, service forms, and corrective action report.
' The corrective action, service forms, and nonconformance report documentation have j
been reviewed.. accepted, and closed as of December 28, 1982.
l i
This report is submitted as the final report.