ML20028C273

From kanterella
Jump to navigation Jump to search
Discusses Status of Commitment to Diversify Power Source to Three Auxiliary Feedwater Flow Control Valves & Steam Admission Valve to turbine-driven Pump,Per 820903 Request & TMI Action Item II.E.1.2
ML20028C273
Person / Time
Site: Maine Yankee
Issue date: 01/04/1983
From: Garrity J, Gorrity J
Maine Yankee
To: Clark R
Office of Nuclear Reactor Regulation
References
TASK-2.E.1.2, TASK-TM JHG-83-01, JHG-83-1, MN-83-02, MN-83-2, NUDOCS 8301070286
Download: ML20028C273 (2)


Text

,

e h

im E IS N RIVE MAlllE M~GHAllHEE AmmlCPol'KRComPARS*

AUGUSTA, MAINE 04336 r<

k,

~ "

(207) 623-3521 O

January 4, 1983 MN-83-02 JHG-83-01 United States Nuclear Regulatory Commission Washington, D. C.

20555 Attention: Office of Nuclear Reactor Regulation Division of Licensing Operating Reactors Branch No. 3 Mr. Robert A. Clark, Chief

References:

(a)

License No. DPR-36 (Docket No. 50-309)

(b) MYAPCo Letter to USNRC, dated May 4, 1982 (c) USNRC Letter to MYAPCo, dated September 3, 1982

Subject:

Auxiliary Feedwater System Automatic Initiation and Flow Indication (TMI Action Plan Item II.E.1.2)

Dear Sir:

This letter responds to your request, Reference (c), for the status of our commitment to diversify the power source to the three AFW flow control valves and the steam admission valve to the turbine-driven pump.

Maine Yankee has installed two safety-grade solenoids for each AFW flow control valve. One solenoid receives its power from vital bus 1; the other solenoid receives its power from vital bus 3.

These control valves are designed to fail open.

The steam admission valve to the turbine-driven pump has two power sources available. The circuit for this valve is normally powered from vital bus 4.

Capability also exists to transfer this circuit by means of a local selector switch to MCC 7A which is powered from emergency bus 7.

.o y b i

8301070286 830104 PDR ADOCK 05000309 p

PDR 0364L - AJC

MAINE YANKEE ATOMIC POWER COMPANY 4

r United States Nuclear Regulatory Commission January 4, 1983 Attention: Mr. Robert A. Clark, Chief Page two MN-83-02 The technical specifications requested by Reference (c) will be forwarded under separate cover by January 24, 1983.

We trust you will find this information satisfactory. However, should you have any questions, please feel free to call.

Very truly yours, MAINE YAWEE ATOMIC POWER COMPANY r

John H. Garrity, Senior Director Nuclear Engineering & Licensing JHG:pjp cc: Mr. Ronald C. Haynes Mr. Paul A. Swetland 0364L - AJC

___