Forwards LERs 82-097/03L-0,82-098/03L-0,82-099/03L-0, 82-100/03L-0 & 82-101/03L-0
Date released: 02/11/2020 Download: ML20028C263


LER 82-101/03L-0:on 821124,discovered Time Delay of Two Automatic Load Sequence Relay Timers Not Repeatable & Timers Exceeded Allowed Tolerance.Caused by Toggle Switch Assemblies Being Out of Alignment.Assemblies Replaced
ML20028C286
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 12/22/1982
From: Palmer R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20028C286 (1)
LER 82-100/03L-0:on 821130,during Surveillance Test on Diesel Generator Load Shedding Relays,Six 4 Kv Loss of Voltage Relays Exceeded Allowed Tolerance.Caused by Instrument Drift.Undervoltage Relay Under Study
ML20028C282
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 12/22/1982
From: Palmer R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20028C282 (1)
LER 82-099/03L-0:on 821123,during Surveillance Test on Automatic Load Sequence Timing Relays,Four ESF Timers Found to Exceed Allowed Tolerance.Caused by Instrument Drift. Timers Readjusted & Solid State Relays Under Review
ML20028C278
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 12/22/1982
From: Palmer R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20028C278 (1)
LER 82-098/03L-0:on 821127,fire Detection Sys Alarm for 4 Kv Switchgear Room Received Due to Pyralarm Detector Alarming. Caused by Low Alarm Setpoint.Pyralarm Replaced
ML20028C270
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 12/22/1982
From: Palmer R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20028C270 (1)
LER 82-097/03L-0:on 821204,fire Detection Sys Alarm for 4 Kv Switchgear Room Received Due to Pyralarm Detector Alarming for No Apparent Reason.Caused by Low Setpoint.New Detector Installed
ML20028C266
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 12/04/1982
From: Palmer R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20028C266 (1)
Forwards LERs 82-097/03L-0,82-098/03L-0,82-099/03L-0, 82-100/03L-0 & 82-101/03L-0
ML20028C262
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 12/22/1982
From: Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML20028C262 (1)