ML20028B232

From kanterella
Jump to navigation Jump to search
Forwards Corrected LER 82-117/03L-0.Detailed Event Analysis Encl
Date released: 02/11/2020 Download: ML20028B232


Corrected LER 82-117/03L-0:on 820929,svc Water Flow to Containment Fan Coil Unit 23 Observed to Be Less than 2,500 Gpm Required by Tech Specs.Caused by American Oysters Plugging Valve 23SW57.Oysters Removed & Valve Reassembled
ML20028B238
Person / Time
Site: Salem PSEG icon.png
Issue date: 10/20/1982
From: Frahm R
Public Service Enterprise Group
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML20028B238 (1)
Forwards Corrected LER 82-117/03L-0.Detailed Event Analysis Encl
ML20028B231
Person / Time
Site: Salem PSEG icon.png
Issue date: 11/19/1982
From: Midura H
Public Service Enterprise Group
To: HAYNES R C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML20028B231 (3)