ML20024F321

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 830523-27
ML20024F321
Person / Time
Site: Grand Gulf 
Issue date: 06/27/1983
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20024F309 List:
References
50-416-83-22, NUDOCS 8309090272
Download: ML20024F321 (1)


Text

,

e, APPENDIX A NOTICE OF VIOLATION Mississippi Power and Light Company Docket No. 50-416 Grand Gulf License No. NPF-13 As _a result of the inspection conducted on May 23 - 27, 1983, and in accordance

-with the NRC Enforcement Policy, 47 FR 9987 (March 9, 1982), the following violation was identified.

l 10 CFR 50.59(b) requires that the licensee maintain records of changes in the facility and these records shall include a written safety evaluation which provides the bases for the determination that the change does not involve an unreviewed safety question.

Contrary to the above, design change packages (DCP) 82/3596(Replace 28VDC coil relays with 20VDC coil relays in APRM, SRM, and IRM trip circuits) and 82/3588 (Replace handswitches for standby diesel generator on panel 1H13-P864) failed to provide bases for the determination that these DCPs did not involve an unreviewed safety question.

This is a Severity Level IV Violation (Supplement I ).

Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to this office within thirty days of the date of this Notice, a written statement or explanation in reply, including:

(1) admission or denial of the alleged viola-tion; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will

be taken to avoid further violations; and (5) the date when full compliance will be achieved. Consideration may be given to extending your response time for good cause shown.

- JUN 2 71983 Date:

8309090272 830816 PDR ADOCK 05000416 O