Interim Deficiency Rept Re Accident Temp Effects on Containment Level Measurement.Design Revised to Include One Transmitter Per Steam Generator & to Insulate Transmitter Ref Leg.Next Rept Will Be Provided by 831031
ML20024F285
Person / Time
Site: Midland
Issue date: 08/31/1983
From: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50.55E, 23783, 82-05-#5, 82-5-#5, NUDOCS 8309090202
Download: ML20024F285 (2)


Text

e 0

g0, ;{ Consumers Power m o c,,

Vice President - Projects, Engineering and Construction General offices: 1945 West Parnall Road, Jackson, MI 49201 * (517) 78& O453 August 31, 1983 82-05 #5 Mr J G Keppler, Regional Administrator US Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND ENERGY CENTER PROJECT -

DOCKET NOS 50-329 AND 50-330 ACCIDENT TEMPERATURE EFFECTS ON CONTAINMENT LEVEL MEASUREMENT FILE:

0.4.9.61 SERIAL:

23783

Reference:

J W Cook letters to J G Keppler, same subject:

1) Serial 16192, dated May 14, 1982
2) Serial 19053, dated September 28, 1982
3) Serial 20689, dated February 1, 1983
4) Serial 22188, dated May 6, 1983 This letter, as were the referenced letters, is an interim 50,55(e) report on accident temperature effects on containment level measurement.

Investigation has limited the need for corrective action to steam generator level transmitters.

It has been determined that instrument string error for this equipment under accident conditions exceeds that allowed to establish the steam generator ECCS control setpoints.

The design has been revised to include one transmitter per steam generator and insulate the transmitter reference leg.

In addition, Bechtel and B&W are refining existing calculations to determine optimum installation details.

Another letter, either interim or final, will be provided on or before October 31, 1983.

N JWC/WRB/AHB/cd CC:

RJCook, NRC Resident Inspector i

Midland Nuclear Plant Document Control Desk, NRC b

Washington, DC OC0883-0026A-MP01 8309090202 830831 l 0 PDR ADOCK 05000329

[bh S

PDR

o 2

Serial 23783 82-05 #5 CC:

CBechhoefer, ASLB Panel LBernabei, GAP FPCowan, ASLB Panel JHarbour, ASLB Panel AS&L Appeal Panel MMCherry, Esq MSinclair BStamiris CRStephens, USNRC WDraton, Esq USNRC FJKelley, Esq. Attorney General SHFreeman, Esq. Asst Attorney General

'WHMarshall GJMerritt, Esq TNK&J INPO Records Center OC0883-0026A-MP01