ML20024E866
| ML20024E866 | |
| Person / Time | |
|---|---|
| Site: | Midland, 05000000 |
| Issue date: | 12/30/1982 |
| From: | Jackie Cook CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| Shared Package | |
| ML20024E849 | List: |
| References | |
| 10CFR-050.55E, 10CFR-50.55(E), 10CFR-50.55E, 19130, 82-16-#1, NUDOCS 8309070147 | |
| Download: ML20024E866 (4) | |
Text
_ _. - - _
g Qt PM dhtNhat
~
g~
E.ss(e) }
6%sm v
s
.. C011SumCIS
" Power 4
James W Cook i
qqy wElErEn3 Vice President - Ivojects, Engineering and Construe ion General Offices: 1945 West Parnell Road, Jackson, MI 49201 * (517) 78& O453 December 30, 1982 82-16 #1 Mr J G Keppler, Regional Administrator US Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND NUCLEAR COGENERATION PLANT -
DOCKET NOS 50-329 AND 50-330 POTENTIAL 50.55(e) REPORT CONCERNING PROCURED ELECTRICAL EQUIPMENT FILE 0.4.9.72 SERIAL 19130 On December 3, 1982, W R Bird reported a potential 50.55(e) condition concerning delivered, safety-related electrical equipment not meeting project requirements to R Gardner of your Staff. The attachment provides a description of the problem and the overall corrective actions to resolve this issue. This letter is the first interim report on this subject.
The condition remains as a potential reportable condition in that it is indeterminate whether the specific nonconforming conditions found would have prevented the equipment / components from properly functioning during all design basis events. The types of electrical equipment in question are those panels and cabinets having extensive vendor wiring and which provide instrument, control, and power functions. Actions being initiated to support the overall corrective actions include:
1.
Establishing a comprehensive review of the subject equipment purchases to support determining root causes as to how equipment was manufactured with deficiencies and delivered to the Midland site without detection of the deficiencies.
2.
Development of a matrix of past corrective actions implemented to provide improvements in this area versus the timing of manufacture and delivery of nonconforming equipment.
3.
Development of specific inspection planning to be utilized at the supplier facilities for source or receipt inspection of future orders.
4.
Review the status of the overinspections performed on delivered subject (s
equipment to assure that no items were missed.
oc1282-1489a131 8309070147 830831 r 1933 PDR ADOCK 05000329 dg a
S PDR
2 a
t 5.
Dispositioning and necessary rework or replacement of items identified.
Either another interim or final report will be submitted on or before February 28, 1983.
o WRB/MJS/jm
Attachment:
Management Corrective Action Report MCAR-1, Report No 66, Rev 2, dated 12/30/82 CC: Document Control Desk, NRC Washington, DC R J Cook, NRC Resident Inspector Midland Nuclear Plant CBechhoefer, ASLB Panel RSDecker, ASLB Panel FPCowan, ASLB Panel
(.
JHarbour, ASLB Panel AS&L Appeal Panel MMCherry, Esq MSinclair BStamiris CRStephens, USNRC WDPaton, Esq, USNRC FJKelley, Esq, Attorney General SHFreeman, Esq, Asst Attorney General WHMarshall CJMerritt, Esq, TNK&J Great Lakes QA Managers
(
oc1282-1489a131
AIf A5014 s/ut PGM000 Pricrityt 02 QUAUTY ASSURANCE PROGRAM MANAEEMENT CSRRECTIVE ACTl N REP 3RT MCAR-1 REPORT NO.:
66-Revision 2
[
JOB NO.:
7220 O NO.:
DATE:
12/30/82 i DESCRIPTION * (including References):
Unacceptable workmanship conditions, such as insufficient solder, broken wire strands, damaged wire insulation, leads pulling from lugs, loose identification tags and markers, use of improper wire lugs, and improper crimping have been identified on electrical control panels and cabinets supplied by various suppliers. Approximately 30 discrepancy reports (continued on page 2)
RECOMMENDED ACTION * (Optional):
The following recommended corrective actions are for vendor supplied electrical panels and cabinets.
A.
Safety Evaluation of Identified Conditions 1.
Based on cases of workmanship identified as not in compliance with MPQAD overinspection (plan 01-E-7B) predict the potential effects on component performance.
(continued on page 2)
REFERRED TO:
$ Engineering O Construction XX OA Management X2 Ouality
@ Procurement (Supplier Quality)
II MPQAD NOTE: This condition was reported to the ISSUED BY:
N NRC by CPCo as potentially reportable
%,oaEa,a,
o on 12/3/82.
[
11 REPORTA8LE DEFICIENCY:
NOTIFIED CLIENT:
I D NO D YES 0
^
l2b30l82 l
M~
/
6 I
Ill CAUSE:
CORRECTIVE ACTION TAKEN:
l l
l l
AUTHORIZED BY:
l I
anno o smounow emoa oesmemo=
ornER oismemoa uGR or consTRucnou enu cousm oc EwGR uaR or on. Two FORMAL REPORT TO CLIENT ucR or to.EERe G cutui oro. om uGR (if Sectionll Applies) o==
uGR or Paoewutui proce uso. om uGR MGR or PRa# OPERATIONS PRoJFCT CoNSTR MGR 8FPo. QA WGR uGR or cuauTV assuRascE PRoJEcr ENQmEER CORRECTIVE ACTION IMPLEMENTED CONSTRUCTION MGR PROJECT MOR
(
ENGINEERING MGR PRoJ PROCUREMENT MGR l
SUPPUER ouAUTV WGR SITE MGR oE SUPERytSom l
VERIFIED BY l
- Desenbe in space provided and attach reference document.
Pme.ct om Enease omie m oco.
Section Number Page of
n 4.
,,s-
.o MCAR 66, Revision 2 Page 2 l
Description (continued)
(e.g., nonconformance reports and quality action requests) have been written in the last two years on electrical equipment for similar conditions discovered during MPQAD overinspections using Consumers Power Company Project Inspection Plan 01-E-7B.
Recent examples of these conditions have also been noted on items supplied by Terry Corp. (auxiliary feedwater pump turbine control panel), Vitro Laboratories (ESIS cabinet internal circuit board) and Transamerica Delaval (diesel engine control panel).
The above is evidence of a weakness in the electrical panel and cabinet suppliers for Midland to fully meet specified requirements in the areas identified.
The source and receipt inspection activities have not been structured to be completely effective in identifying the vendor's discrepancies.
Recommended Actions 2.
Evaluate the effects on plant safety due to the predicted effects from Item A.1 above.
B.
Evaluation of Requirements and Vendor Programs 1.
Review the material requisitions for definition of workmanship requirements or criteria using the discrepancy reports i
(nonconformance reports and quality action requests) from MPQAD overinspection plan 01-E-7B.
This will be input to Item B.2.
2.
Evaluate the vendors' programs (i.e., workmanship standards, inspection planning, etc.).
Modify the programs as appropriate.
3.
Evaluate the vendors' implementation of their program (i.e., methods used and results obtained) in the area of workmanship. Initiate corrective action as appropriate.
C.
Evaluation of Bechtel Programs 1.
Evaluate the source and receipt inspection programs with regard to vendor workmanship and modify the programs as appropriate.
2.
Determine process corrective actions necessary for Bechtel to improve control of vendors' performance in the area of workmanship.
D.
Interim Report 1.
Provide interim report by February 15, 1983 to meet client commitment date of February 28, 1983.
/
\\
.