ML20024B116

From kanterella
Jump to navigation Jump to search
Startup Test Procedure 35,Recirculation Sys Flow Calibr
ML20024B116
Person / Time
Site: LaSalle 
Issue date: 06/24/1983
From:
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20024B100 List:
References
PROC-830624-08, NUDOCS 8307050235
Download: ML20024B116 (1)


Text

.

STARTUP TEST PROCEDURE 35 RECIRCULATION SYSTEM FLOW CALIBRATION 1.

PURPOSE A.

The purpose of this test is to perform a complete calibration of the installed recirculation system flow instrumentation.

2.

ACCEPTANCE CRITERIA A.

Level 2 1.

Jet pump instrumentation shall be adjusted such that the jet pump total flow recorder trill provide a correct core flow indi-cation at rated conditions.

2.

The APRM/RBM flow bias instrumentation shall be adjusted to function properly at rated conditions.

3.

RESULTS Test Condition 3 The core flow instrumentation was recalibrated to correctly indicate core flow as calculated from the individual jet pump dP's.

The APRM/RBM flow signals were verified to be conservatively adjusted.

Since the calculated loop flow variation based on the theoretical flow distribution factor was greater than 3%, additional data will be taken in this test cendition to determine the actual flow distribution factor.

5 8307050235 PDR R

ADOCK 830624 05000373 PDR