ML20024A476

From kanterella
Jump to navigation Jump to search
Submits Evaluation of Plant Design & Initial Description of Planned Actions in Response to IE Bulletin 83-03 Re Diesel Generator Svc Water Sys.Check Valve Design & Matls Superior. Final Evaluation Forthcoming
ML20024A476
Person / Time
Site: Farley  Southern Nuclear icon.png
Issue date: 06/10/1983
From: Clayton F
ALABAMA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-SSINS-6820 IEB-83-03, IEB-83-3, NUDOCS 8306170357
Download: ML20024A476 (3)


Text

Mallhg Address Alabama Power Company 600 North 18th Street rost Offic] Box 2641 Birmingh:m, Alabama 35291 Telephone 205 783-6081 F. L Clayton, Jr.

b R n" % % g y "'

AlabamaPower Docket No. 50-348 N S * " * "C8 * '"

50-364 June 10, 1983 Mr. J. P. O'Reilly, Regional Administrator U. S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street, N.W.

Atlanta, Georgia 30303 Joseph M. Farley Nuclear Plant - Units 1 & 2 IE Bulletin 83-03 Gentlemen:

Alabama Power Company has reviewed IE Bulletin 83-03 and herewith provides an evaluation of plant design and an initial description of planned actions.

Joseph M. Farley Nuclear Plant - Units 1 and 2 are designed such that cooling water to the diesel generators is supplied by the normally operating Service Water System.

Therefore, only those portions of the Service Water System supplying cooling water directly to and from the diesel generators were considered for the purpose of this evaluation. Each unit design consists of three inlet check valves and two outlet check valves in a dual train arrangement.

The ten check valves (five in each unit) contained in the described systems are listed in.

The next Unit 2 refueling outage is currently scheduled to begin in September 1983.

During the outage, the Service Water System Train A will be drained and the three accessible check valves (6 inch and 8 inch inlets and 12 inch outlet) will be disassembled and inspected.

If any evidence of abnormal degradation as described in IEB 83-03 is found where repair or replacement of components or parts is required, the Train B system will be drained and the remaining two valves (6 inch inlet and 12 inch outlet) will be disassembled and inspected.

If these conditions are found in Unit 2, an inspection of the Unit 1 valves will be performed, as described above, at the fifth refueling outage scheduled to begin in March 1984 Alabama Power Company has reviewed the plant maintenance records which would describe a history of any known previous failures of these valves.

As a result of this review, no failures of the nature described in IEB 83-03 have occurred in either unit.

In addition, no other service, repair or replacement of these valves including parts or svil f

F306170357 830610 fI l PDR ADOCK 05000348 C

PDR

2j c Joseph M. Farley Nuclear Plant - Units 1 & 2 IE Bul1etin 83-03 June 10, 1983

.Page 2 components has been, required during the operation of either unit.

Furthermore' as-listed ~ in Attachment 1, the inlet valves are currently included in the Inservice Testing (IST) Program for each unit.

In conducting the positive flow. inservice test of the inlet valves, the respective outlet valves are also required to perform as designed to produce acceptable' inservice test results.

All inservice tests conducted to date, in accordance with the NRC approved IST Programs, have produced acceptable results and have not indicated any condition which would limit service water flow to the diesel generators.

Alabama Power Company has reviewed the similarity of the design of the subject Farley Nuclear Plant. valves compared to the valves identified in IEB 83-03.

The preliminary conclusion is that the Farley valves are superior in design and materials of construction such that the probability of finding problems at the Farley Nuclear Plant is low.

Final evaluation will be completed based on the Unit 2 refueling outage inspection results.

Following completion of inspections and evaluation of val ve condition, Alabama ~ Power Company will report the inspection results and future ' actions, if any, to the NRC as required by IEB 83-03 within 90 days. An evaluation of inspection results will be conducted to determine what changes, if any, will be made to the IST Programs.

Yours truly F. L. Clayton, Jr.

SWORN TO AND SUBSCRIBED BEFORE ME d

THIS fo DAY OF

/gM,1983 l

A W h.

I

~

Yotarj PuT) Tic

/o,/z7./gr My Commission Expires:

STB:bs Attachment cc: Mr. R. A. Thomas Mr. G. F. Trowbridge Mr. E. A. Reeves Mr. W. H. Bradford l

I

r s-

.4 r

l ATTACHMENT 1 IE Bulletin 83-03 FNP Diesel Generator Service Water Check Valves Unit No.

TPNS No.

Diesel Gen. No.

Train Function Size In IST Progran 1

Q1P16V659 2C B

SW Inlet 6"

Yes 1

Q1P16V660 IC A

SW' Inlet 6"

Yes 1

Q1P16V661 1-2A A

SW Inlet 8"

Yes 1

Q1P16V564 IB, 2B & 2C B

SW Outlet 12" No 1

Q1P16V565 1-2A & 1C A

SW Outlet 12" No 2

Q2P16V659 2C B

SW Inlet 6"

Yes 2

Q2P16'!560 1C A

SW Inlet 6"

Yes 2

Q2P16V661 1-2A A'

SW Inlet 8"

Yes 2

Q2P16V564 1B, 2B & 2C B

SW Outlet 12" No 2

Q2P16V565 1-2A & IC A

SW Outlet 12" No