Responds to IE Bulletin 83-03, Check Valve Failures in Raw Water Cooling Sys of Diesel Generators. Bulletin Not Applicable to Plant Since Check Valve Not Used at Facility
ML20024A473
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 06/09/1983
From: Johnson B
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-SSINS-6820 IEB-83-03, IEB-83-3, NUDOCS 8306170355
Download: ML20024A473 (4)


Text

a i

..g-o e.

~

Consumers Power Company General offices: 1946 West Parnall Road, Jackson, MI 49201 e (517) 788-0550 June 9, 1983 James G Keppler, Administrator Region III US Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 DOCKET 50-155 - LICENSE DPR BIG ROCK POINT PLANT -

RESPONSE TO IE BULLETIN 83-03 The NRC, in IE Bulletin 83-03, " Check Valve Failures in Raw Water Cooling Systems of Diesel Generators," dated March 10, 1983, requested operating license holders to:

1.

Review and modify the In-Service Testing program to include check valves in the flow path of cooling water for the diesel generator from the intake to the discharge, 2.

Modify the In-Service Testing program to include verification procedures that confirm the integrity of the valve internals, 3.

Perform an initial valve integrity verification on check valves identified as in the cooling water flow path for the diesel generator.

4.

Report:

a) valves identified as in the cooling water flow path for the diesel generator, b) schedule of In-Service Testing program for identified valves, and c) history of any known previous failures of identified valves, and 5.

Report the results of completed initial valve integrity verification with a description of any failure modes.

Actions taken by Consumers Power Company to respond to these requests are as follows:

1.

The In-Service Inspection (ISI) program at Big Rock Point Plant was reviewed. One check valve was identified in the cooling water flow path for the diesel generator (VEP-301) which was not included in the ISI oc0683-0209a142 h j 3g

/

I

/

lt(

8306170355 830607 PDR ADOCK 05000155

\\

G PDR

-+

r-

'0 James G Keppler, Administrator 2

Big Rock Point Plant Response to IE Bulletin 83-03 June 9, 1983 program.

Based on the following discussion, the ISI program will not be modified to include VEP-301.

2.

As stated above, the ISI program will not.be modified.

Consumers Power Company believes IE Bulletin 83-03 is not applicable.

3.

Initial valve integrity test was done on VEP-301 on June 8, 1983. The valve was disassembled and inspected.

4.

One check valve (VEP-301) was identified in the cooling water flow path of the diesel generator. This two-inch diameter check valve acts to hold the prime for the self priming diesel generator pump. The check valve is a brass, vertical lift check valve, and it is not fabricated by the manufacturer identified in IE Bulletin 83-03.

The check valve has a history of no required maintenance.

5.

Upon disassembly, the vertical disc was found seated and holding water.

There were no failures or indications of failure. The valve stem, disc, spring, and disc nuts were in place and showed no signs of excessive wear or degradation.

Scheduling of an inservice inspection program is not applicable for VEP-301.

Conclusion Consumers Power Company has determined that IE Bulletin 83-03 is not applica-ble at Big Rock Point Plant for the following reasons:

a.

The check valve which is in the cooling water flow path for the diesel generator does not meet the description of check valves identified in-IE Bulletin 83-03.

The valve is smaller, is fabricated by a different manufacturer, and operates differently (VEP-301 is a lift check valve not a swing check valve.)

b.

The check valve has no histcry of failure.

oc0683-0209a142

f,

. James G Keppler, Administrator 3

Big Rock Point Plant Response to IE Bulletin ~83-03 June'9, 1983

~

Based on the above information, Consumers Power Company requests exemption from surveillance testing of the check valve in the diesel generator cooling water path at their Big Rock Point Plant.

A "r,

Brian D Johnson Staff Licensing Engineer CC Director, Office of Nuclear Reactor Regulation Director, Office of Inspection and Enforcement

-NRC Resident Inspector-Big Rock Point NRC Document Control Desk, Washington, DC i

f i

oc0683-0209a142-i I

r,.

s CONSUMERS POWER COMPANY Big Rock Point Plant IE Bulletin 83-03 Docket 50-155 License DPR-6 At the request of the Commission and pursuant to the Atomic Energy Act of 1954 and the Energy Reorganization Act of 1974, as amended, and the Commission's Rules and Regulations thereunder, Consumers Power Company submits our response to IE Bulletin 83-03 dated March 10, 1983, entitled, " Check Valve Failures in Raw Water Cooling Systems of Diesel Generators". Consumers Power Company's response is dated June 9, 1983.

CONSUMERS POWER COMPANY g ye B

_ 2(4) W If B DeWitt, Vice President Nuclear Operations Sworn and subscribed to before me this 9th day of June, 1983.

L.

SherryLDugey, Notary @

c Jackson County, Michig My commission expires November 5,1986 SHERRY LYNN DURFEY Notary Public, Jackson Co'nt li:tt; w f

IVv rerrri+n Exp4es b5.1986 nu0683-0209c142

__. _