-,c,-

~

@ Consumers power James W Cook C0mpany vic, e,, sis,,, - e,.i,,,,, n.,i.,,,i.,

and Construction General offices: 1945 West Pernall Road, Jackson, MI 49201 * (517) 788-0433 May 6, 1983 82-05 #4 Mr J G Keppler, Regional Administrator US Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND ENERGY CENTER PROJECT -

DOCKET NOS 50-329 AND 50-330 ACCIDENT TEMPERATURE EFFECTS ON CONTAINMENT LEVEL MEASUREMENT FILE; 0.4.9.61 SERIAL:

22188

Reference:

J W Cook letters to J G Keppler, same subject:

1) Serial 16192, dated May 14, 1982
2) Serial 19053, dated September 28, 1982
3) Serial 20689, dated February 1, 1983 This letter, as were the referenced letters, is an interim 50.55(e) report on accident temperature effects on containment level measurement, Investigation has limited the need for corrective action to steam generator t

level transmitters. It has been determined that instrument string error for this equipment under accident conditions exceeds that allowed to establish the steam generator ECCS control setpoints.

It is now known that one transmitter must be added to each instrument channel.

In addition, Bechtel and B&W are refining existing calculations to determine optimum installation details.

Final information is expected by July 15, 1983.

Another letter, either interim or final, will be provided on or before August 31, 1983.

JWC/WRB/AHB/cd CC:

RJCook, NRC Resident Inspector Midland Nuclear Plant Document Control Desk, NRC Washington, DC 8305170409 8305 DR ADOCK 05000 0C0583-0002A-MP01 S

9 PDR "Qg }

r g

s 2

Serial 22188 82-05 #4 CC:

CBechhoefer, ASLB Panel FPCowan, ASLB Panel JHarbour, ASLB Panel AS&L Appeal Panel MMCherry, Esq MSinclair BStamiris CRStephens, USNRC WDPaton, Esq, USNRC FJKelley, Esq, Attorney General SHFreeman, Esq. Asst Attorney General WHMarshall GJMerritt, Esq, TNK&J INPO Records Center OC0583-0002A-MP01