LER 83-015/03L-0:on 830402,PT-27A Revealed That Amp Readings for Heat Tracing Panel 10 Circuit 1B & Panel 11 Circuits 2A, 4A & 6B Below Acceptance Criteria.Caused by Excessive Heat. Defective Heat Tracing Replaced & Design Change Initiated
ML20023B501
Person / Time
Site: Surry 
Issue date: 04/27/1983
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20023B501 (2)
LER 83-016/03L-0:on 830329,signal from B Steam Line Pressure Transmitter PT-2-485 Increased Approx 300 Mv,Rendering Transmitter Inoperable.Cause Not Determined.Basis Adjusted & Transmitter Calibr & Returned to Svc