ML20017A149

From kanterella
Jump to navigation Jump to search
T3401000-1UM, Rev B, NMP-1000, Multi-Range Linear Module User Manual - Redacted
ML20017A149
Person / Time
Site: University of Lowell
(R-125)
Issue date: 06/30/2015
From:
General Atomics, Xerox Corp
To:
Office of Nuclear Reactor Regulation
References
GA/EMS-4791 T3401000-1UM, Rev B
Download: ML20017A149 (92)


Text

arseam J,

xerox e arseam T3401000-1 UMB_REDACTED.pdf 01 /06/20 10:57 AM Xerox WorkCentre 7855

+ CENISRAL ATOMICS

.,I.ISCTROM.ACNEFICS

-NMP-1000*,.. MULTI-RANGE LINEAR MODULE USER MANUAL DOCUMENT T3401000-1UM Revision B:.June 2015 Document Level 1 Copyright@ GA 2014 - Ail Rights* Reserved

GENERAL ATOMICS 16969 MESAMINT STREET SAN DIEGO, CA 92127 Customer Service - (858) 522-8300

GA PROP RI ET ARY NMP-1000, MUL Tl-RANGE

. LINEA MODULE FUNCTION Technical Wrler 0Engineer Progrmn Manager Document Control Reiease USER MANUAL DOCUMENT T3401.00.0 -1UM Revision B: June 2015 Document Level 1 GENERAL ATOMICS 16989 MESAMINT STREET SAN DIEGO, CA 92127 Customer Service*-(858) 522-8300 APPROVING SIGNATURE CopyrightCGA 2014-AII RI12 DATE

This page intentionally left blank.

GA PROPRIETARY FRONT MATTER ABSTRACT This document contains lnfonnation that is proprietary to General Atomics. Possession of or access to this document, which may be granted by General Atomics to any person or organization, will in no way constitute public disclosure of nor act to transfer title to such lnfonnation. This document wlll be returned to General Atomics upon request or whenever it is no longer required for the purpose for which it was supplied. The infonnation contained herein may not be communicated to others nor used in any way other than as authorized by General Atomics nor copied in whole or in part without the express written consent of General Atomics Although General Atomics has attempted to compile the material contained in this Issuance with accuracy, neither it, Its employees, nor its agents can make any warranty or representation, expressed or Implied, with respect to the accuracy or completeness of such lnfonnatlon or assume any liability with regard to the use of or for damages resulting from the use of any Information apparatus, method, or procedure described in this Issuance.

© Copyright General Atomics, 2014 T3401000-1UM REVISION: B

GA PROPRIETARY FRONT MA TIER This document is based on infonnation available at the time of Its publication. While efforts have been made to render accuracy to Its content, the lnfonnation contained herein does not purport to cover all details or variations in hardware or software, or to provide for every possible contingency in connection with installation, operation, and maintenance. Features may be described herein, which are not present in all hardware and software systems. General Atomics assumes no obligation of notice to holders of this document with respect to changes subsequently made.

General Atomics makes no representation or warranty, expressed, Implied, or staMory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the infonnatlon contained herein.

TRIGA is a registered trademark of General Atomics.

All other trademarks and registered trademarks belong to their respective owners.

T3401000-1UM REVISION: B ii

FRONT MA TIER RECORD OF REVISIONS REVISION DA TE ENTERED

SUMMARY

OF CHANGES A

JANUARY 2014 Original issue by GA Incorporated customer feedback. Added Information and appendices related to FC0-673, FC0-67 4 for Test B

JUNE 2015, Currents. Added new appendix with site calibration notes. Added Information regarding compensating voltage options. Corrected typographlcal errors.

T3401000-1UM REVISION: B Ill

FRONT MATTER This page Intentionally left blank.

T3401000-1UM REVISION: B iv

FRONT MATTER TABLE OF CONTENTS 1.0 GENERAL INFORMATION....................................................................................................................... 1-1

1.1 INTRODUCTION

.................................................................................................................................... 1-1 1.2 SPECIFICATIONS.................................................................................................................................. 1-3 1.3 REFERENCE DOCUMENTS.................................................................................................................. 1-4 1.4 STANDARDS.............................................................................................................................................. 1-4

2.0 DESCRIPTION

........................................................................................................................................... 2-1 2.1 BLOCK DIAGRAM.................................................................................................................................. 2-1 2.2 MAJOR SUBASSEMBLIES.................................................................................................................... 2-2 22.1 Motherboard (T3400113-001).......................................................................................................... 2-3 2.2.2 Analog Amplifier Board (T3400133-001).......................................................................................... 2-5 2.2.3 Digital Interface Board (T313330~1)........................................................................................... 2-7 2.2.3.1 Component Location..................................................................................................................... 2 2.2.3.2 Dipswltches on the Microprocessor Daughterboard..................................................................... 2-9 2.2.4 Trip/Alarm Board (T3301133-001)................................................................................................. 2-12 2.2.5 Isolation Amplifier Board (T3133113-001)..................................................................................... 2-14 2.2.6 Display............................................................................................................................................ 2-15 2.2.7 Front Panel Board (T3400123-001)............................................................................................... 2-15 2.2.8 PS1 Power Supply......................................................................................................................... 2-15 2.2.9 Compensation Power Supply................'......................................................................................... 2-16 2.3 FRONT PANEL CONTROLS AND INDICATORS................................................................................ 2-17 2.4 REAJR PANEL CONNECTORS............................................................................................................. 2-18 3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)..................................................................... 3-1 3.1 INITIAL OPERATION.............................................................................................................................. 3-1 3.2 STARTUP OPERATION......................................................................................................................... 3-1 3.3 NORMAL OPERATION (LOCAL)........................................................................................................... 3-1 3.4 NORMAL OPERATION (REMOTE)........................................................................................................ 3-2 3.5 SHUTDOWN OPERATION................................................................................................................. :... 3-2 3.6 LCD DISPLAY SCREENS............................................................................................................................ 3-2 3.6.1 Description....................................................................................................................................... 3-2 3.6.2 Main Menu Display........................................................................................................................... 3-2 3.6.2.1 Display Parameters....................................................................................................................... 3-3 3.6.2.2 Bar Graph...................................................................................................................................... 3-3 3.6.2.3 Navigation Buttons........................................................................................................................ 3-3 3.6.2.4 Trip Reset...................................................................................................................................... 3-3 3.6.2.5 Heartbeat Indicator........................................................................................................................ 3-4 3.6.3 Gain Menu Display........................................................................................................................... 3-4 3.6.3.1 Display Parameters....................................................................................................................... 3-4 3.6.3.2 Navigation Buttons......................................................................................................................... 3-5 3.6.4 Test/Cal Menu Display..................................................................................................................... 3-5 3.6.4.1 Display Parameters....................................................................................................................... 3-5 3.6.4.2 Test Mode Buttons........................................................................................................................ 3-6 3.6.4.2.1 Operate Mode Button................................................................................................................ 3-6 3.6.4.2.2 Calibrate High Mode Button....................................................................................................... 3-6 3.6.4.2.3 Calibrate Low Mode Test........................................................................................................... 3-6 3.6.4.2.4 Manual Current Test Mode..... :.................................................................................................. 3-6 3.6.4.2.5 HVTest Mode............................................................................................................................ 3-7 3.6.4.3 Navigation Buttons........................................................................................................................ 3-7 3.6.5 About Menu Display......................................................................................................................... 3-8 3.6.5.1 Dlsplay Parameters....................................................................................................................... 3-8 T3401000-1UM REVISION: B V

FRONT MA TIER 3.6.5.2 Adjustments............................................................. ;.................................................................... 3-8 3.6.5.3 Buttons.......................................................................................................................................... 3-9 3.6.6 Calibrate Display.............................................................................................................................. 3-9 4.0 MAINTENANCE (CALIBRATION)............................................................................................................ 4-1 4.1 PRELIMINARIES.................................................................................................................................... 4-1 4.1.1 Reference Documents...................................................................................................................... 4-1 4.1.2 Test Equipment................................................................................................................................ 4-1 4.1.3 Setup................................................................................................................................................ 4-2 4.2 MOTHERBOARD (HVPS) CALIBRATION............................................................................................. 4-3 4.2.1 Component Location........................................................................................................................ 4-3 4.2.2 High Voltage Calibration................................................................................................................... 4-3 4.3 PVI/A, ANALOG AMPLIFIER-CALIBRATION....................................................................................... 4-4 4.3.1 Component Location........................................................................................................................ 4-4 4.3.2 Power/Current Calibration................................................................................................................ 4-4 4.3.2.1 Setup - Null................................................................................................................................... 4-5 4.3.2.2 E-11............................................................................................................................................... 4-5 4.3.2.3 E-10............................................................................................................................................... 4-6 4.3.2.4 E-9................................................................................................................................................. 4-6 4.3.2.5 E-8................................................................................................................................................. 4-6 4.3.2.6 E-7................................................................................................................................................. 4-6 4.3.2.7 E-6................................................................................................................................................. 4-6 4.3.2.8 E-5................................................................................................................................................. 4-7 4.3.2.9 E-4............................................................................................. ~................................................... 4-7 4.3.2.10 E-3................................................................................................................................................. 4-7 4.3.3 Gain.................................................................................................................................................. 4-7 4.3.4 Calibrate and Test Current............................................................................................................... 4-8 4.3.4.1 Calibrate High........................................................,...................................................................... 4-8 4.3.4.2.

Calibrate Low................................................................................................................................ 4-8 4.3.4.3 Test (Man) Current.... *************************************************************-r****************************************************4-8 4.3.5 Auto-Range Setpoints............................... :..................................................................................... 4-9 4.4 p,./1/ A, TRIP/ALARM - CALIBRATION AND FUNCTIONAL CHECK..................................................... 4-10 4.4.1 Component Location...................................................................................................................... 4-10 4.4.2 Calibration of Trips......................................................................................................................... 4-11 4.4.2.1 Setup, Normal Operation............................................................................................................ 4-11 4.4.2.2 Trip 2........................................................................................................................................... 4-12 4.4.2.3 Trip 1........................................................................................................................................... 4-12 4.4.2.4 High Voltage................................................................................................................................ 4-13 4.4.2.5 Restore System, Normal Operation............................................................................................ 4-13 4.5 PVI/A, ISOLATION AMPLIFIER-CALIBRATION AND FUNCTIONAL CHECK................................... 4-14 4.5.1 Component Location...................................................................................................................... 4-14 4.5.2 Calibration of Isolation Ampllfier.................................................................................. :.................. 4-14 4.5.2.1 Setup........................................................................................................................................... 4-15 4.5.2.2 Analog Output A.......................................................................................................................... 4-15 4.5.2.3 Analog Output B.......................................................................................................................... 4-15 4.6 Cm.APENSATION POWER SUPPLY -FUNCTIONAL CHECK...................................................................... 4-16 4.6.1 Minimum Value-Full CCVI/........................................................................................................... 4-16 4.6.2 Maximum Value - Full CW.............................................................................................................. 4-16 4.6.3 Normal Operation........................................................................................................................... 4-16 4.7 REMOTE DISPLAY VERIFICATION.................................................................................................... 4-16 4.7.1 Setup.............................................................................................................................................. 4-16 4.7.2 Trip Occurs..................................................................................................................................... 4-16 4.7.3 Return to Normal Operation........................................................................................................... 4-17 T3401000-1UM REVISION: B vi

4.8 4.8.1 4.8.2 4.8.3 4.9 4.10 FRONT MATTER REMOTE SIGNAL FUNCTIONS................................................................................................................... 4-17 Electrometer Pulse Disconnect.............................................................................,:....................... 4-17 Remote Select Test/Cal Modes..................................................................................................... 4-17 Remote Trip Reset......................................................................................................................... 4-17 REMOTE VOLTAGE.................................................................................................................................. 4-18 WATCH DOG TIMER................................................................................................................................. 4-18 5.0 ENGINEERING DRAWINGS...........................................................................,......................................... 5-1 5.1 LIST OF ENGINEERING DRAWINGS.................................................................................................... 5-1 6.0

SUMMARY

OF REAR PANEL CONNECTIONS...................................................................................... 6-1 APPENDIX I

  • GA TRIGA NUCLEAR MODULE SOFIWARE COMMUNICATIONS PROTOCOL........................ 1 APPENDIX 11-SITE CALIBRATION NOTES.......................................................................................................... 1 APPENDIX 111-FC0-673 AND FC0-674................................................................................................................. 1 LIST OF FIGURES Figure 1-1 NMP-1000............................................................................................................................................. 1-2 Figure 2-1 NMP-1000 Block Diagram................................................................................................................... 2-1 Figure 2-2 Multi-range Linear Module NMP-1000, Board Layout.......................................................................... 2-2 Figure 2-3 Multi-range Linear Module NMP-1000, Interior View.........*................................................................. 2-3 Figure 2-4 Digital Interface Board.......................................................................................................................... 2-9 Figure 2-5 Digital Interface Board DIP switch S1................................................................................................ 2-10 Figure 2-6 Multi-range Linear module NMP-1000, Front View............................................................................ 2-17 Figure 3-1 Main Menu............................................................................................................................................ 3-3 Flgure 3-2 Gain Menu.......................................................................................................................................*.... 3-4 Figure 3-3 Test/Cal Menu...................................................................................................................................... 3-5 Figure 3-4 About Menu.......................................................................................................................................... 3-8 Figure 3-5 Calibrate Display................................................................................................................................... 3-9 Figure 4-1 Motherboard Layout............................................................................................................................. 4-3 Figure 4-2 Analog Amplifier Board Layout............................................................................................................. 4-4 Figure 4-3 Trip/Alarm Board Layout...................................................... ;.............................................................. 4-10 Figure 4-4 Isolation Amplifier Board Layout.........................................................,............................................... 4-14 LIST OF TABLES Table 1-1 Reference Documents........................................................................................................................... 1-4 Table 2-1 Major Subassemblies........................................................................................................................... 2-2 Table 2-2 Jumpers (Motherboard - Highest Range)............................................................................................. 2-4 Table 2-3, Potentiometers (Motherboard - Startup Mode)..................................................................................... 2-4 Table 2-4 Potentiometers (Analog Amplifier-Range Calibration)........................................................................ 2-5 Table 2-5 Potentiometers (Analog Amplifier-Offset)........................................................................................... 2-6 Table 2-6 Potentiometers (Analog Amplifier-Cal HI)........................................................................................... 2-6 Table 2-7 Jumpers (Analog Amplifier-DMde/Multiply)........................................................................................ 2-7 Table 2-8 S1 Dip Switches (Mlcroprocessor)....................................................................................................... 2-11 Table 2-9 S1 Dip Switches LOGIC settings (Ethernet Addresses)...................................................................... 2-11 Table 2-10 S1 Dip Switches LOGIC settings (Com Ports).................................................................................. 2-12 Table 2-11 Detailed Trip Settings:...................................................................................... :................................ 2-13 Table 2-12 Analog Outputs Jumper Settings....................................................................................................... 2-14 Table 2-13 Potentiometers (Isolated Outputs)..................................................................................................... 2-14 Table 2-14 Pot~ntiometers (Front Panel)............................................................................................................. 2-15 T3401000-1UM REVISION: B vii

FRONT MATTER Table 2-15 Potentiometer (High Voltage)............................................................................................................ 2-16 Table 2-16 Controls and Indicators, Front Panel................................................................................................. 2-18 Table 2-17 Connectors, Rear Panel................................................................................................................... 2-19 Table 4-1 Dip Switch Logic Settings...................................................................................................................... 4-2 Table 4-2 Trip/Alarm Jumper Settings................................................................................................................. 4-11 Table 4-3 Analog Outputs Jumper Settings.......................................................................................................... 4-15 Table 5-1 Engineering Drawing List....................................................................................................................... 5-1 Table 6-1 Rear Panel Connectors......................................................................................................................... 6-1 Table 6-2 DB-25 (J4).............................................................................................................................................. 6-1 Table 6-3 DB-37 (J5)............................................................................................................................................. 6-2 Table 6-4 DB-37 (J6).............................................................................................................................................. 6-3 T3401000-1UM REVISION: B viii

ANS ANSI B/f ccs CD COTS csc DAC ERS l&C 1/0 IEEE LCD LINUX NRS NTE O&M PCA RPI RPS RWP TRIGA UPS LIST OF ABBREVIATIONS American Nuclear Society American National Standards Institute Bistable Trip Console Computer System Compact Disc Commercial-Off-The-Shelf Control System Console Data Acquisition and Control East Radiography Station Instrumentation and Control lnpuUOutput Institute of Electrical and Electronic Engineers Liquid Crystal Display Unix-like Computer Operating System North Radiography Station Not-To-Exceed Operator and Maintenance Printed Circuit Assembly Rod Position Indication Reactor Protection System Rod Withdrawal Prohibit Training, Research, Isotopes, General Atomic Uninterruptible Power Supply FRONT MA TIER T3401000-1UM REVISION: B ix

FRONT MATIER NOTICE Although GA has attempted to prepare the material contained in this manual with accuracy, no warranty or representation is expressed or implied with respect to the accuracy or completeness of such infonnation, and no liability is assumed for any loss or damages resulting from the use of the equipment or any infonnation contained in this manual.

The following are used throughout the manual to draw your attention to Items or procedures that require special notice or care.

X NOTE: Used to identify important infonnation.

CAUTION Used to Identify lnfonnation that may be useful in preventing damage to equipment.

WJ!\\RNIN-G Used to identify Information about situations that may present a danger tQ the technician,.

T3401000-1UM REVISION: B

1.0 GENERAL INFORMATION 1.0 GENERAL INFORMATION

1.1 INTRODUCTION

The NMP-1000 Is a microprocessor based wide-range linear power module which provides percent reactor power Indication and bi-stable trip circuits. The module Is packaged in a metal enclosure suitable for mounting In a reactor control console. The NMP-1000 module processes current of 1 E-11 to 1 E-3 Amperes from any detector producing current within input range, e.g. ion chamber or fission chamber. A compensating voltage power supply is provided for use with compensated ion chambers. The input current is converted into Oto 10V In 9 one-decade' ranges. The appropriate decade is selected either automatically by software (auto mode) or by the user (manual mode) via the touch screen display or a remote input The NMP-1000 has two modes of operation, local or remote. In local mode, the module accepts commands via the front panel touch screen or a remote display*. In remote mode, the module accepts commands via the Ethernet port or the analog remote Interface connectors on the rear panel. A detailed list of the remote interface pinouts Is given in section 6 of this manual.

Three (3) bi-stable trips are used to alarm on low high voltage to the detector and two Independently adjustable levels of reactor power. Three relays are provided with two sets of normally open and normally closed contacts for customer use. The relays are held energized in a fail-safe condition until an alarm de-energizes the coil.

The NMP-1000 has test modes to allow the user to test the proper performance of the electrometer and to ensure the functionality of all trip circuits. Test modes Include HV, calibrate high, calibrate low, and manual current. The HV and calibrate high test modes cause the bi-stable trips to alarm; current low gives fixed power indication in the highest range; and manual test lets the user vary the current over all ranges with a front panel potentiometer. Test modes can be enabled via the touch screen or a remote interface.

A photo of the NMP-1000 is provided in Figure 1-1.

  • The remote display is available as an option. It is Identical to the front panel display and connects to the RS-232 port on the rear panel.

T3401000-1UM REVISION: B 1-1

1.0 GENERAL INFORMATION Figure 1-1 NMP-1000 This manual includes an overview of the NMP-1000 along with the following sections: the major subassemblies, the specifications, and references. Also, control and operating instructions and maintenance details for the NMP-1000 are included. The manual includes the following sections:

Section 1.0 Section 2.0 Section 3.0 Section 4.0 Section 5.0 Section 6.0 GENERAL INFORMATION DESCRIPTION OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)

MAINTENANCE (CALIBRATION AND TEST PROCEDURES)

ENGINEERING DRAWINGS

SUMMARY

OF REAR PANEL CONNECTIONS T3401000-1UM REVISION: B 1-2

1.2 SPECFICATIONS Thefolowing specifications are for the NMP-1000.

Dimensions (Apptoxinate)

Weight (Apploximale)

TemperaUe (Range)

Presswe Power Response Tine Constants.

Outputs: '

Calibrafion/T est Isolated:

High voltage 1r1>

High power trip High power alarm 1.0 GENERAL INFORMATION MaxiTun 4.6 inches {W) by 8.3 mches {H)

X ~~.6 (16.7 with connectors and front panel poleldiolnetel) inches (D) 11 pounds

~ to 131°F (Design)

Atmosphedc ~)

117 Vac +/- 10%, 50160 Hz@1.0 Amp 0.:10 V or 4-20 mA, % Power, Two~oulplds

. O to 1000 Vdc at 3mA at max vollage T3401000-001: -30 to -200 Vdc T3401000-002: -8 to -50 Vdc T34010()()...()()3;,..23 to -150 Vdc Low end mup--out vollage may vay sightly.

All models provide 300pA at max vollage Relay contacts (9 outputs)

Adjustable, lYA> Form C COi dacts Aqustable, two Form ~ contacts Adjustable, two Form C contacts Two.fixed aarents for self-test One adjustable current for mulli-range fundlon test and trip testing1.

1 When T~ Mode is enlerecf.1he

  • are placed.i a falsafe condilion (mealing the rdays are*~*~

but the froot panel LB) and the Bhemet output do NOT lrdcate a trip sn:e they are based on the measwed parameter exceeding a selpoint In the comparator circtit (the Trip u:,gic *signal). As the front panel manual current potentiometer is timed and lhe trip setpon is crossed, the comparator flips state. the Trip LOQIC sl:gnal T3401000-1UM *REVISION: B 1-3

1.0 GENERAL INFORMATION Temperatue Coefficient*

1.3 REFERENCE DOCU11Bffl$

Table 1:..1 lists applicable reference documents for this manual.

HV~test Test modes selected individually by touch.

screen buttons

+/-0.15%fC maximt.rn st the range of10- to SSC 1 E-11 to 1 E-3 A in nne one decade ranges.

T9lJCti saeen buttons provided to switch ranges in manual mode.

Automatic

. switching range Remote range.SWitching capability.

Table 1-1 Reference Documents Document Name Doct.ment Namber

. TRIGA Reactor Control System Operation And Maintenance T959000100-10M Manual AcceptallC8 Test Procedl.l'e (ATP), Multi-Range Ulear Module T3401000-1AT NMP-1000 1A ST~ARDS The NMP-1000 was developed and 1e$d in accordance with MJ:SI~ NQA-1-2000, Quaity Assurance

~

.for Nuclear Faciity Appllcatlons. Performance of these adcilional quality assurance actfyities should~ use ot1he NMP-1000 as digital ~

equipment occurs, and the front panel LB> wll light and the Ethernet link wil send 1he ~

signal This is a latchi1g i1dication. so turning 1he knob down afterwards wit not~ the LB)_

T3401Q00-1UM REVISION: B

  • 1-4

2.0 DESCRIPTION

2.0 DESCRIPTION

2.1 BLOCK DIAGRAM Figure 2-1 is a block diagram for the NMP-1000 Module.

I I

Figure 2-1 NMP-1000 Block Diagram T3401000-1UM REVISION: B 2-1

2.0 DESCRIPTION

2.2 MAJOR SUBASSEMBLIES Table 2-1 identifies the monitor major subassemblies, which are further described in the following paragraphs.

Table 2-1 Major Subassemblies Description MUL Tl-RANGE LINEAR CHANNEL NMP-1000 A1 PWA, NMP-1000 MOTHERBOARD A2. PWA, ANALOG AMPLIFIER A3 PWA, DIGITAL INTERFACE A4 PWA, TRIP/ALARM A5 PWA, ISOLATION AMPLIFIER A6 DISPLAY, 3.8" LCD MODULE, TRANSFLECTIVE A7 PWA, FRONT PANEL PS1 POWER SUPPLY PS2 COMPENSATION POWER SUPPLY Part Number T3401000-001 T3400113-001 T3400133-001 T3133303-001 T3301133-001 T3133113-001 304922 T3400123-001 305855 T3401000-001: 306495 T3401000-002: 307127 T3401000-003: 307128 Figure 2-2 Multi-range Linear Module NMP-1000, Board Layout T3401000-1 UM REVISION: B 2-2

~lgure 2-3 Multi-range Linear Module NMP-1000, Interior View 2.2.1 : Motherboard (T3400113-001)

Refer to schematic T3400111 for circuit details. *

2.0 DESCRIPTION

The NMP. motherboard serves as the backplane for all)~MP PWA's (daughter cards). It provides the power for all d~ughter cards, HV power supply and compensation power supply. It contains somf!3 circuitry for monitoring voltage levels and range indicators. Connections between all daughter cards and peripheral devices such as the*

display or remote connectors are made via the motherboard.

The motherboa~ provides a number of connectors where all daughter cards plug in. Connectors are keyed and of different pin count, and in combination with card guides, only allow one type of daughter ca~ to be installed }n a partieular slot Additional connectors accept the cable connections to the rear panel remote connectors, as well as connections to the dlsplay and front panel Pt/I/A Incoming signal llnes for control slgnals originating* at the remote

2.0 DESCRIPTION

connector on the rear panel are protected by a resistor/diode network. Outgoing signals are generally Isolated via relays, opto-lsolators, or another method.

Additional circuitry ties in with the trip/alarm PWA If either the watch dog timer or operate signals are lost, the NMP will go out of operate and set all trips. While the NMP is in auto mode and also not in the highest range (e.g.

1 E-3), the percent power signal is pulled low, essentially preventing a power trip from occurring. If the NMP is taken out of auto mode, or the highest range has been reached, the percent power signal Is released and the trip circuits are enabled. Jumper settings let the user configure which current range is the highest range. The software receives indication that the highest range has been reached via a feedback circuit.

Table 2-2 Jumpers (Motherboard - Highest Range)

Highest Range JP1 I

JP2 Notes 1E-3 X

1-2 Factory Default 1E-4 1-2 2-3 Install FC~73 (see appendix) 1E-5 2-3 2-3 Install FC~7 4 (see appendix)

In the factory default condition, the Test Currents (see sectlon 4.3.4) are in the appropriate range; Hl Test Current can be adjusted from about 95% to 125% power, and Lo Test Current ls hard-wired to about 18% power. If JP1 and JP2 must be repositioned to accommodate a different high range, the Test Currents wlll not change unless the corresponding FCO, as listed in Table 2-2, is installed.

All relays that Indicate the active power range to the user are located on the motherboard. The relays are controlled by the microprocessor by the same signal that also sets the range on the analog amplifier.

There are two Jumpers on the motherboard that affect the start-up mode of the display. One jumper lets the user set the program mode. When the program mode ls enabled, the display will accept programming to the flash. This setting Is used only when it is necessary to reload the Display OS or when the code that was complled has locked up the display. The other jumper will start up the display in calibration mode. In normal use, the calibration mode can be accessed via the About menu of the NMP. Changing this jumper should only be necessary if the display brightness and contrast are very far out of calibration and calling the callbration routine from the screen is impossible.

Table 2-3 Potentiometers (Motherboard - Startup Mode)

T3401000-1UM REVISION: B 2-4

2.0 DESCRIPTION

Mode JP3 (prog)

JP4 (cal)

Normal Use 2-3 2-3 Program/Calibrate 1-2 1-2 All analog +/-15 Vdc power for the NMP is generated by two linear power supplies on the motherboard.

Transformers step down the 117 Vac nominal input voltage which then gets rectified by bridge rectifiers and filtered. Linear regulators convert the primary DC voltages into +/-15 Vdc. The transformers are sized to provide sufficient voltage to the linear regulators with 90% AC line input. +15 Vdc is also routed to the rear panel connector that is accessible to the customer for external auxiliary circuits. This external supply voltage is fused with a 1 OOmA, self-resetting fuse.

A 25W switching power supply on the motherboard generates +24 Vdc to provide power to the HV power supply and digital circuitry. The Input is fused with a 3A, slow acting glass fuse. +24 Vdc is also routed to the rear panel connector that is accessible to the customer for external auxiliary circuits. This external supply is fused with a 250mA, self-;esetting fuse.

2.2.2 Analog Amplifier Board (T3400133-001)

Refer to schematic T3400131 for circuit details.

The analog amplifier board measures the incoming current signal from the detector and converts it into a linear analog voltage In nine one-decade ranges. For every decade of current, the analog board returns a O to +10 Vdc signal. Because the NMP is designed to measure power up to 120% of nominal reactor power, an output voltage of +10 Vdc represents 1.2 x nominal current In every decade (e.g. 120nA or 1.2mA). In general, the NMP-1000 and detector should be setup such that 1mA equals 100% reactor power. This is accomplished by performing the bench calibration in section 4.3, reinstalling the instrument, operating the reactor to determine actual power levels (via other instrumentation), and then physically repositioning the detector so the NMP indicated power equals actual power.

At the heart of the analog amplifier board is a high input impedance operational amplifier. For every decade of current, a relay switches in the appropriate feedback resistor to generate the expected output signal. The 1 E-11 is the default range and always active. Other ranges are switched into the circuit in parallel as determined by the microprocessor. Every range has an adjustment potentiometer that allows for calibration of the circuit The high impedance ampllfier is followed by a buffer amplifier with an adjustable gain potentiometer.

Table 2-4 Potentiometers (Analog Amplifier - Range Calibration)

T3401000-1UM REVISION: B 2-5

2.0 DESCRPTION Potentiometer Func;tlon R84 1E-3range~

R83 1 E-4 range.calibration.

R82 1 E~ range call:>ratiori R64 1 E-6 range calibration R65 1E-7range~

R66 1E-8 range calibration R48 1E-9range~

R30 1 E-10 range calilratlon R4 1 E-11 range calibration.

R1 Amplffler offset calibration R18

~I

.gain call>ration

  • ---i Table 2-5 Polentiometers (Analog Amplifier-Ofraeij.

I

  • Function Offset Compensation Three self-test cil:uils are located on 1he analog l>Ocl'd: callxation low, calibration hg1 ~

manual current..The user.can n6ate these tests via the touch ~

or remote connectors.. The calibration low circuit \\WI ~te a current signal of approximately D.2mA:. It is not aajUStable. The callbration high anent can be aqusted *by the user via a potentiometer and is usually set around 12mA. The~.current is adjusted~ a~

on

. the front panel of the NMPs The circuit is designed to generate a current~ _O to >1.2mA over the rmge of 1he

Table 2-6. Polentiometers (Analog Amplifier-Cal Hi)

I R37 Polentlometer I

Function

. Cal Hi Ctneni ~

T3401000-1UM REVISION: B 2-6

2.0 DESCRIPTION

Whle any of the test modes are active, a relay disconnects the aurent Input frcm the detector to. the NMP. A signal from the mlaoprocessor activates tfjs relay. This relay can~ activated via the Bhemet Jnterface or via a remote connector.

2.2.3 Digital Interface Board (T3133303-001)

Refer to schematic T3133301 for acuit details.

The digital interface board houses the microprocessor cm circlEry that interfaces with fhe' al the other boards. It also contains power supplies for di{;tal power, AID converters, communications circuilry, and the watch dog tiller.

The microprocessor is part of the microprocessor assembly, a cornmeJCially available micfoprocessor With integrated merQOIY, Ethernet communication, and other peripherals. An 8-position DIP switch lets ~-user set the E~ address and other parameters as desai>ecf in the communications inlerface docum~

The +24 Vdc. generated on the motherboard, is converted by two switching power supplies to +3.3 Vdc and

+5 Vele digital power. The +3.3 Vdc supply ~ manly used 1o power the microprocessor assembly, 'Whereas the

+5 Vdc is used to poYlel" the GPIO (General Purpose UO) circt.ilry and the display.

Digital inputs originating at the remote comectors or other board assemblies. within the module are routed to the digital interface boartl The nominal input is +15 Vele and zero. Fl"St, the incoming signals get level shifted to

+5 Vdc, and then read by GPIO integrated ciraJits.. The GPIO ICs then communicate via an ~

SPJ bus with.

the microprocessor board. Outgoing signals are generated by fhe microprocessor, ~

to 1he GPIO I Cs via SPI bus, and fhes:l level shifted to +15 Vdc. There are a total of 24 inputs and 24 outputs available.


The incoming analog signals (+10 VdcfuR scale}

are divided In half by op-amp cmJitry and sent to the AID.converter. *The AID converter COll1fJlmicates_ wfth the microprocessor via isolated SPI bus. An additional stand-alone ND converter: conummicates with the microprocessor via paralel bus. ft is intended to be used for reading fast pulsed-signals. The input to this AID converter is designed to be +2.5 Vdc. Two op-amp ciraits perform the input signal conditiookJg. One*circtit can be used to <ivide an klcoming +10 Vdc signal by 4, the other to multiply a +1 Vdc signal by 2.5.

Table ~-7 Joolpers (Analog Amplifier-~}

I JP1 Jumper T3401000-1UM REVISION: B 2-7

2.0 DESCRIPTION

The microprocessor contains two Universal Asynchronous Receiver/Transmitter (UARTs} that are used for communication with the display and the remote display/maintenance port on the rear panel via RS-232. The remote display/maintenance port is isolated with Its own power supply and digital isolator. The nominal isolation voltage is >1,500 Vrms.

A watch dog timer (WOT} monitors the activity of the microprocessor. If the WOT receives no input from the microprocessor for more than 1.6 seconds, the WOT sends an alann and takes the module out of operate. When a WOT alarm occurs, the heartbeat LED will stop blinking, the loss of communications will cause all trips to set, and the console WOT Alarm will occur. A WOT alarm is latching in the Instrument and can only be reset by cycling power (or, if the Instrument cover Is off and the Instrument is in Test Mode, by pressing S2 on the Digital Interface Board). The heartbeat LED indicates the activity of the microprocessor and will blink about once per second as long as all software tasks are executing properly. A WOT alarm is expected to be an extremely rare event.

T3401000-1UM REVISION: B 2-8

2.0 DESCRIPTION

2.2.3.1 Component Location heartbeat S2 Figure 2-4 Digital Interface Board S1 NETBURNER (8 POS) DIP Switch S2 RESET Switch (used for development and testing only) 01 Heartbeat LED 2.2.3.2 Dipswitches on the Microprocessor Oaughterboard NOTE:

For the S1 DIP switch, logic 1 is an OFF setting of the switch and logic 0 is an ON setting of the switch. The signal logic is active low.

Therefore, the printed legend on the DIP switches is backwards.

T3401000-1UM REVISION: B 2-9 S1 not in view

2.0 DESCRIPTION

= switch in "on*

position=

towards edge of PCB Figure 2*5 Digital Interface Board DIP switch S1 T3401000.1UM REVISION: B 2-10

20 DESCRIPTION The microprocessor daughterboard contains 1 DIP (labelled S 1) with 8 switches, see Figure 2-5. These switches have the following uses:

Table 2-8 S1 Dip Switches (Microprocessor) t Dip Switch Purpos 1 --= 1 Static IP address selecti~ n 2

Static IP address selection e

(bit #0) --

(bit #1 )

3 Static IP address selection (bit #2)

Watchdog test 4

5 6

7 8

Ethernet multiple connectio COM port control bit #0 COM port control bit #1 Test mode enabled nsenabled. -

Default Setting 1

1 1 -1 1

1 1

1 The module can be programmed to one of four different static IP address. Dip switches #1, #2, and #3 select one of the seven possible IP addresses as follows:

Table 2-9 S1 Dip Switches LOGIC settings (Ethernet Addresses)

DipSw#3 Dip Sw #2 l Dip Sw #1 Static IP Address f ~

0 0

Ethernet access disabled fo -= 1_ -

base address+6 0

1 0

base address+S l~

1 1

base address+4 j

lo I Q base address+3

~ 1 0

1 base address+ 2 I

1 1

0 base address+1 1

1 I 1 base address The base address for the NMP-1000 is If dipswitch #5 is in the LOGIC 1 position (and dip switches #1, #2 and #3 are not all LOGIC 0), then the microprocessor will support multiple connections over the Ethernet (at least two, maximum is dependent upon the microprocessor). If dipswitch #5 is in the LOGIC O position (and dip switches #1, #2 and #3 are not all LOGIC 0),

then the microprocessor will support only a single connection on the TCP/IP socket.

NOTE:

If dipswitches #1, #2 and #3 are all in the LOGIC O position ("OOOn),

then no Ethernet communications is possible.

T3401000-1UM REVISION: 8 2-11

2.0 DESCRIPTION

Dip switches #6 and #7 control the communications ports as follows:

Table 2-10 S1 Dip Switches LOGIC settings (Com Ports}

Dip Sw #:a Dip Sw ##6 0

0

~

1 1

1 0

1 COM port status 1 COMO disabled, COM1 drives LCD display in/out I Reserved COMO LCD in/out, COM1 LCD in/out (independent operation}

COMO is status/maintenance port, COM1 drives display in/out.

If dipswitch #8 is in the LOGIC 1 position, then the system will accept test commands over the Ethernet. This dipswitch is only used during initial factory and site testing and is placed "OFF" at the conclusion of testing. When dipswitch #8 is enabled, the instrument responds to a remote 'Test' command. When dipswitch #8 is disabled, a remote 'Test' command will result in an error signal.

2.2.4 Trip/Alarm Board (13301133-001)

Refer to schematic T3301131 for circuit details.

The trip/alarm board contains six identical circuits to generate all trip and alarm indications. Every circuit is jumper configurable for a rising or falling trip. A comparator monitors an incoming signal voltage and compares it to a reference voltage. The reference voltage is user adjustable via a potentiometer. When the circuit is configured for a rising trip, the comparator will switch states when the amplitude of the incoming signal exceeds the reference signal. A falling trip works the opposite way; when the incoming signal amplitude falls below the reference voltage, the comparator will switch states. Once a trip has occurred, the circuit latches in the tripped state. The only way to unlatch the circuit is for the user to apply a reset signal, even if all signal levels return to nominal prior to the reset.

Every trip has a DPDT (Form C} relay that the user can connect to via the remote connectors. The relay is controlled by the output of the comparator and the operate signal. Taking the NMP out of operate mode (such as during a self-test} will immediately activate all trip relays. This is considered the failsafe condition - when all trips are set and latched, but not necessarily indicated by the front panel LEDs or remotely.

The trip logic signal (comparator output} is only activated when the comparator input exceeds its setpoint. Simply taking the NMP out of operate mode will not activate the trip logic signal. The front panel LEDs, opto-isolator T3401000-1UM REVISION: B 2-12

2.0 DESCRIPTION

outputs, and Ethernet indications are driven by the trip logic signal, and so will only indicate a trip when the comparator input exceeds the setpoint.

Because entering any self-test mode causes the loss of the operate signal and therefore activates the trip relay; the user may, in some cases, choose to bypass the operate signal on a trip circuit. To disable this feature, jumper settings have been provided to prevent a given trip when the instrument enters a test mode.

NOTE:

this feature does not change operation of the trip in normal operations

- the trip will still activate the relay if the setpoint is exceeded. It simply prevents an automatic trip when entering test mode.

Important: The Operate and WOT signals are logically tied together on the motherboard PWA. Bypassing the operate signal on a trip circuit also bypasses the WDT on the same trip. All trip circuits are independent of each other, so jumper settings and Operate Enable/Bypass for any one trip will not affect any others. The front panel LEDs and Ethernet output are not affected by this jumper.

Detailed Trip Settings:

Table 2-11 Detailed Trip Settings:

Trip#

Jumper#

Rising Falling Reference Operate Operate Adjustment Enable Bypass 1

JP18 2-3 1-2 JP17 2-3 1-2 R?S JP16 1-2 2-3 2

JP1S 2-3 1-2 JP1 4 1-2 2-3 R61 JP13 2-3 1-2 3

JP12 2-3 1-2 JP11 1-2 2-3 R47 JP1 0 2-3 1-2 4

JP9 2-3 1-2 JP8 2-3 1-2 R33 JP?

1-2 2-3 s

JP6 2-3 1-2 JPS 1-2 2-3 R19 JP4 2-3 1-2 6

JP3 2-3 1-2 JP2 2-3 1-2 RS JP1 1-2 2-3 T3401000-1UM REVISION: B 2-13

2.0 DESCRIPTION

As an example, consider the HV trip jumper set to Operate Bypass. If the operator enters any test mode, all trips except the HV trip will go to failsafe mode (meaning, the trips activate). If the operator then initiates the HV trip test; the HV trip will occur, the front panel LED will light, and the Ethernet trip signal will be sent. If the operator returns to normal operations (but does not change the jumper position), the HV trip is still active and will trip if a HV fault occurs. However, if only a WDT occurs, the HV trip will NOT indicate a fault (all other trips not in Operate Bypass will go to failsafe).

2.2.5 Isolation Amplifier Board (13133113-001)

Refer to schematic T3133111 for circuit details.

The isolation amplifier board houses two isolated outputs that can be jumper configured for either voltage or current output. The isolators are commercially available programmable voltage to current converters. The converters provide 1500Vrms galvanic isolation. Adjustment potentiometers allow the isolators to be calibrated for offset and span.

Table 2-12 Analog Outputs Jumper Settings Output Offset Span A

R12 R11 B

R14 R13 AO to +10 Vdc input will generate a 4 to 20mA or Oto +10 Vdc output that is available to the user via the remote connectors. The minimum compliance voltage for current loop operation is +8 Vdc. Voltage output is achieved by inserting a shunt resistor into the loop. The receiving device should have an input impedance >50k0, otherwise unacceptable measurement errors may occur.

Table 2-13 Potentiometers (Isolated Outputs)

Output Jumper 4-20mA 0-10V A

JP1 1-2 2-3 JP2 2-3 1-2 B

JP3 1-2 2-3 JP4 2-3 1-2 T3401000-1UM REVISION: B 2-14

2.0 DESCRIPTION

2.2.6 Display The display on the front of the module is a Monochrome LCD Display with white LED backlight. The display has a viewing area of 3.8 inches (diagonal) and a resolution of 320 X 240 (QVGA). The display includes an integrated touch panel and integrated digital backlight & contrast controls. A complete graphical operating system that executes GUI applications built in dynamic HTML is included with the display.

2.2.7 Front Panel Board (T3400123-001)

Refer to schematic T3400121 for circuit details.

The front panel board houses the red LED indicators for all trips, activated by the trip/alarm board. The remote/local switch lets the user control whether the module is in remote or local mode. A green LED indicator is wired in with the switch; it is lit when the module is in remote mode.

A potentiometer lets the user manually control the current in test mode. This potentiometer is accessible with a knob on the front panel. Two recessed potentiometers, accessible via the front panel with an adjustment tool, let the user adjust the compensation power supply voltage on the NMP.

Table 2-14 Potentiometers (Front Panel)

Potentiometer Function R20 Manual current adjust R6 Compensation Power Supply Coarse Adjust R21 Compensation Power Supply Fine Adjust 2.2.8 PS1 Power Supply The 4W high voltage power supply is powered from +24 Vdc and can supply up to +1,000 Vdc with a maximum of 2mVp-p ripple. An internal sense circuit returns Oto +1 Vdc for an output of Oto +1,000 Vdc. Circuitry on the motherboard amplifies this sense voltage to +1 0 Vdc at maximum output. Additional circuitry is connected to the sense line to enable the HV self-test. A potentiometer located on the motherboard lets the user manually adjust the HV output.

T3401000-1UM REVISION: B 2-15

2.0 DESCRIPTION

Table 2-15 Potentiometer (High Voltage}

Potentiometer Function R4 High Voltage Adjustment 2.2.9 Compensation Power Supply The compensation power supply produces an output voltage from -8 to -200 Vdc (depending on the part number, see below} with a ripple of less than 10 mVp-p. The +5 Vdc input power is derived from the +15 Vdc analog supply and a linear regulator. The output of the compensation power supply is controlled by a O to +3 Vdc programming voltage that can be adjusted by the user with potentiometers accessible on the front panel of the NMP. The compensation power supply is short circuit protected with two external resistors. As a result, depending on the load, the maximum voltage may not be available to the load, as the protection resistors will drop some voltage. A voltage sense circuit monitors the output and returns Oto +10 Vdc for Oto maximum output voltage. To accommodate a variety of detection systems and user situations, three different compensation power supplies are available:

Part number T3401000-001 provides a -30 to -200 Vdc compensation power supply.

Part number T3401000-002 provides a -8 to -50 Vdc compensation power supply.

Part number T3401000-001 provides a -23 to -150 Vdc compensation power supply.

NOTE:

All of the compensating power supplies drop out around 15-20% of their maximum output voltage. This is a result of fundamental design characteristics from the OEM and cannot be changed.

T3401000-1UM REVISION: B 2-16

2.0 DESCRIPTION

2.3 FRONT PANEL CONTROLS AND INDICATORS The front panel of the NMP-1000 is shown in Figure 2-6. Each control and indication is described in Table 2-16.

NMP 1000 NUCU.AI IIIULn-lANO[ UNEM CHANNEL

-..:_:ii COtffllOL-0 ONQ

---TEST--

ca o

---*TRPS---.

Q1RP1 Q TRIP 2 Q HIGH YOLTACE I*

I*

I*

D D

Figure 2-6 Multi-range Linear module NMP-1000, Front View T3401000-1UM REVISION: B 2-17

2.0 DESCRIPTION

Table 2-16 Controls and Indicators, Front Panel Label Description LCD Display Touchscreen Display User interface Compensation Power Supply Coarse Adjust CCW: Decreases current CW: Increases current Fine Adjust CCW: Decreases current CW: Increases current Remote Control Button Switch Depressed/engaged to enter local mode, out/disengaged for remote mode2 On (Green)

Illuminates when in remote mode Test Manual Current Adjust CW: Increases current CCW: Decreases current Trips Trip 1 (Red)

Illuminates when percent reactor power setpoint is exceeded, independent of Trip

2.

Trip 2 (Red)

Illuminates when percent reactor power setpoint is exceeded, independent of Trip

1.

High Voltage (Red)

Illuminates when HV goes below the HV setpoint 2.4 REAR PANEL CONNECTORS The rear panel connectors of the NMP-1000 are described in Table 2-17.

2 When the NMP-1000 is operated in remote mode, it is necessary to select a range (REM_ 1 E-11 to REM_ 1 E-3 or REM_AUTO) via the rear panel connector J6. If no range is selected, the instrument will default to the 1 E-3 range. This is true even if the instrument is otherwise controlled via the Ethernet port (trip reset and test modes). For details on the remote connectors, see section 6 of this manual.

T3401000-1UM REVISION: B 2-18

2.0 DESCRIPTION

Table 2-17 Connectors, Rear Panel Ref.

Type Label Signal Des J9 JS JI J1 BNC Signal From detector 0 §] * ~ rrl Coax (Current) Input J2 MHV HVOut High Voltage output (Coax) for detector Jt J3 TNC Compensation Compensation

-..ur 11 Coax Voltage voltage for detector (t_a_ ~

J4 DB25 Trip relay outputs

@)

r pin JI IDIOll --..,T (male)

~

?lo J5 DB37 Remote inputs, trip POWER pin outputs and analog

~

n (male) outputs

..,(;:]

J6 DB37 Range indication OM Bl socket contacts, remote J2 (female) selection inputs M

~

J7 DB9 PA-1000 Not used {for PA-1000) 115VAC IOHz JB DB9 Remote RS232 external

(

0 1W Ol!t (male)

Display communication to

i I~

0 tt>> I remote display or maintenance computer J9 RJ45 Commswith Ethernet console Power ON/OFF Power AC power switch and 115 Vac, 60Hz power connector T3401000-1UM REVISION: B 2-19

2.0 DESCRIPTION

T3401000-1UM REVISION: B 2-20 This page intentionally left blank.

3.0 OPERA TING INSTRUCTIONS (MENUS AND DISPLAYS) 3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)

This section contains detailed information on initial operation, monitor startup/shutdown and normal monitor operating procedures.

3.1 INITIAL OPERATION Before applying power to the NMP-1000 for the first time, perform the following:

a.

Verify that the power switch on the rear panel is in the OFF position.

b.

Verify connection of ac power to power connector on the back of the module and to an ac outlet.

c.

If a detector is to be connected, verify that the signal cable is connected to J1, SIGNAL INPUT, on the rear panel, and that the high voltage cable is connected to J2, HV OUT, on the rear panel. (Refer to Table 1-2 for connection information.) If the detector is a compensated ion chamber, connect the compensation volts cable to J3, COMPENSATION VOLT AGE, on the rear panel. Just prior to connecting any detector cable to the instrument, it is recommended to discharge any static electricity from the center pin by momentarily shorting the center pin to ground.

d.

If the outputs for the remote display, for the network or for trip outputs are to be connected, verify the cables are connected for those devices.

3.2 STARTUP OPERATION For local control follow these instructions:

a.

Set the power switch on the Power connector on the rear panel to the ON position.

b.

Set the module to Local Mode by depressing/engaging the Remote Control button switch.

c.

Verify the green LED is extinguished.

d.

Verify the NMP-1000 LCD displays the Main Menu Display.

e.

Ensure all trip and the High Voltage indicators are extinguished. Press Trip Reset on Main Menu if necessary.

3.3 NORMAL OPERATION (LOCAL)

a.

On the Front Panel, ensure the Remote Control button switch is depress/engaged.

b. Verify that the green LED is extinguished to indicate that the module is in Local Mode.
c.

On the Front Panel, tum the Manual Current Adjust potentiometer to full CCW.

d.

On the LCD press the Gain button. In the Gain menu Display, press the Auto button.

T3401000-1UM REVISION: B 3-1

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)

e.

On LCD press the Test/Cal button. In the Test/Cal menu Display, press the OPERATE button.

f.

Ensure all the trips on the front panel are extinguished.

3.4 NORMAL OPERATION (REMOTE)

a.

On the Front Panel, ensure the Remote Control button switch is not depressed/engaged.

b.

Ensure the green LED is illuminated to indicate that the module is in the Remote Mode.

3.5 SHUTDOWN OPERATION To shut down the module, set the power switch on the rear panel to the OFF position.

3.6 LCD DISPLAY SCREENS 3.6.1 Description There are four menu displays available on the NMP-1000. The first three displays have buttons to select any of the four displays and on their screen power in percent is displayed. From About Menu display only the Test/Cal Menu display is selectable.

Main Menu: general information Gain: current range selectable Test/Cal: operation and test modes are selectable.

About: software information and display control adjustable NOTE:

In the following descriptions of the menus, it is assumed the NMP-1000 is in Local Mode.

To enter the NMP-1000 Local Mode, depress the Remote button on the NMP-1000 front panel, and verify the green ON LED is extinguished.

3.6.2 Main Menu Display The Main Menu provides several different parameter readings, a bar graph, trip reset, watchdog indication and a menu.

T3401000-1UM REVISION: B 3-2

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)

P-1000

0 y
10B-3
0

~

MA Trip Reset Heartbeat: O Figure 3-1 Main Menu 3.6.2.1 Display Parameters The parameter readings are a single value except power which also displayed in a bar graph.

HV high voltage for the detector (0 to 1000 volts de)

Comp PS absolute value of voltage setting of compensation power supply output (0 to maximum Vdc range)

Range Power 3.6.2.2 Bar Graph selected range of electrometer (1 0E-11 to 10E-3 amps) percent reactor power measured by the detector (0 to 120 %)

The bar graph is used to display percent reactor power scaled from on a linear scale of O to 120%.

3.6.2.3 Navigation Buttons Four navigation buttons are provided.

Main Gain Test/Cal About 3.6.2.4 Trip Reset used to indicate Main is being displayed used to select the Gain display used to select the Test/Cal display used to select the About display The Trip Reset is used to extinguish the trip indicators if the trip is cleared.

T3401000-1 UM REVISION: B 3-3

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS) 3.6.2.5 Heartbeat Indicator The Heartbeat indicator flashes between black and blank to indicate that the microprocessor is functioning and the software has not hung. A momentary glitch that restores microprocessor functionality in less than about 1.6 seconds will not trip the WOT; and the Heartbeat indicator will simply pick up its flashing display. If a WOT does activate, it is a latching trip; and the only recovery is to cycle power on the instrument (or press S2 on the DIB with the instrument cover off). The WOT is only reset during system startup.

3.6.3 Gain Menu Display The gain menu display provides buttons to select the detector measurement range (decade) and automatic software range selection mode. In the automatic mode, the software selects range based on the current range by switching one range lower when the current is below 8% of range and switching up one range when the current exceeds 95% of range.

t'JMP-1000 GAIN MENU ba Range: 101:-3 EJ E-11 E-10 E-9 E-8 EJ E-7 E-6 E-5 E-4 (rest1ca1]

E-3 Auto

~ower: 0 lg

[ AbDUI )

Figure 3-2 Gain Menu 3.6.3.1 Display Parameters The display parameters are as follows:

Gain Range:

The current selected range is displayed.

T3401000-1UM REVISION: B 3-4

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)

Selectable Ranges:

In local mode, the buttons can be used to select a range or Auto.

Power:

The percent power is displayed.

3.6.3.2 Navigation Buttons Four navigation buttons are provided.

Main Gain Test/Cal About used to select Main used to indicate Gain is displayed used to select the Test/Cal display used to select the About display 3.6.4 Test/Cal Menu Display The Test/Cal menu display provides four self-tests buttons and an Operate button. The NMP-1000 returns to Operate after 50 seconds of inactivity. The self-tests are Calibrate High, Calibrate Low, Manual Current and HV Test.

~MP-1000 TEST /CAL MENU Operate 0

a 0

Calibrate High EJ Calibrate Low 0 Man Current 0

[Test~]

HV Test 0

[ About )

~ain Range: lOE-3

~ower: 0 ts Figure 3-3 Test/Cal Menu 3.6.4.1 Display Parameters The display parameters are as follows:

Test Mode Buttons:

In local mode, the buttons can be used to select a self-test or Operate Power:

percent power T3401000-1UM REVISION: B 3-5

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS) 3.6.4.2 Test Mode Buttons The display includes five Test Mode buttons: Operate, Calibrate High, Calibrate Low, Man Current and HV Test.

3.6.4.2.1 Operate Mode Button This button is used to select the Operate mode and to indicate the module is in Operate.

3.6.4.2.2 Calibrate High Mode Button This button is used to test Trips 1 and 2. A setting of 120% power or 1.2 mA is used as factory setting.

a.

Press Calibrate High.

b.

Verify Trip 1 LED illuminates.

c.

Verify Trip 2 LED illuminates.

d.

In the Test/Calibration Menu press the Operate button.

e. To reset the trips, select Main Menu and press Trip Reset.

3.6.4.2.3 Calibrate Low Mode Test This button is used to test the performance of the module at a low current. A setting of approximately 0.19 mA is used. No trips should occur.

a.

Press Calibrate Low.

b.

Verify that no trips occur and that approximately 19% power is indicated.

3.6.4.2.4 Manual Current Test Mode This button is used to test the automatic range selection. The Current Adjust knob can be used to adjust from 1 E-1 E-11 to 1 E-3 amps.

a.

Verify that the Gain is set to Auto on the Gain Menu Display.

b.

Ensure that the Current Adjust knob is set to minimum (full CCW)

c.

Press Man Current.

d.

Tum the Manual Current Adjust knob clockwise on the Front Panel to obtain an increasing value% power.

Verify that software autoranges by selecting the next decade.

e.

Repeat the previous step for each decade being used.

T3401000-1UM REVISION: B 3-6

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)

f.

In the Test/Calibration Menu press the Operate button.

g.

To reset the trips, select Main Menu and press Trip Reset.

3.6.4.2.5 HV Test Mode This button is used to test the HV trip. A high voltage of about 9% of the high voltage nominal value is used for the test. During this test, the HV to the detector is disconnected so there is no power output on the J2 connector on the rear panel.

a.

Press HVTest.

b.

Verify High Voltage Trip LED illuminates.

c.

In the Test/Cal Menu Display, press the Operate button.

d.

To reset the trips, select Main Menu and press Trip Reset.

3.6.4.3 Navigation Buttons Four navigation buttons are provided.

Main Gain Test/Cal About used to select Main used to select Gain used to indicate Test/Cal is displayed used to select the About display T3401000-1UM REVISION: B 3-7

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS) 3.6.5 About Menu Display The About Menu Display provides software version information, IP address, and adjustments for contrast and backlight.

NMP-1000 ABOUT MENU 5/W Ver: o.o.o Dlsploy Ver: 00.00.14 IP Address: 192.168.2.30

ontrost ~

I I

I I

I I

I 0

I I...

I D

BackUght 0

I a

I I

8 g

,t Saw

)

[

Ceftll )

[ eo*,ahl )

Figure 3-4 About Menu 3.6.5.1 Display Parameters The display parameters are as follows:

NOTE: The software and display version will always be identical.

software (microprocessor) version display (Display) software version IP address 3.6.5.2 Adjustments The display includes two slide controls for the display.

contrast backlight T3401000-1UM REVISION: B 3-8

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS) 3.6.5.3 Buttons Calibrate opens the Calibrate Display Save saves the LCD settings made on this Display Cancel does not retain any setting changes and returns to Main Menu display 3.6.6 Calibrate Display The Calibrate Display provides a method to adjust the screen edges for selectable area. A Touch Center is provided in the upper left, lower right and center.

~<Touch Center Figure 3-5 Calibrate Display T3401000-1UM REVISION: B 3-9

3.0 OPERATING INSTRUCTIONS (MENUS AND DISPLAYS)

This page intentionally left blank.

T3401000-1UM REVISION: B 3-10

4.0 MAINTENANCE (CALIBRATION) 4.0 MAINTENANCE (CALIBRATION) 4.1 PRELIMINARIES All instructions in Section 4 use these preliminaries unless otherwise specified.

The NMP-1000, Multi-Range Linear Channel, P/N T3401000-001, -002, -003.

NOTE:

It is assumed the microprocessor and Display code is properly installed.

NOTE:

Cycling the AC power at any time, whether in normal operation or during maintenance, does not invalidate the calibration in any way.

4.1.1 Reference Documents See Section 5, Engineering Drawings.

4.1.2 Test Equipment

a.

AC power cord

b.

Current source with range of 1 pA to >1.2mA and BNC output cable

c.

Extender card for A2 Analog Amplifier, GA-ESI P/N T3400183-001 or equivalent

d.

Remote display with power source, if applicable

e.

RS232 cable, DB9M to DB9F, straight through for the remote display, if applicable

f.

DMM, Fluke 787 or equivalent CAUTION AC and DC voltages are present during this test on the NMP-1000. Observe proper safety precautions.

T3401000-1UM REVISION: B 4-1

4.0 MAINTENANCE (CALIBRATION) 4.1.3 Setup

a.

Remove the cover from the NMP-1000.

b.

Connect the AC power cord to the NMP-1000 and plug it in, but do not turn on the power.

c. Connect the current source to J1 on the NMP-1000.
d.

Set the following dip switch settings on S1 on the Digital Interface Board. Reference Figure 2-5.

Table 4-1 Dip Switch Logic Settings Switch Purpose Setting 1

Static IP address Selection (bit #0)

NOTE 1 2

Static IP address Selection (bit #1)

NOTE 1 3

Static IP address Selection (bit #2)

NOTE 1 4

Reserved for module-specific purposes 1

5 Ethernet multiple connection enabled 0

6 COM port control bit # 0 1

7 COM port control bit # 1 0

8 Test mode enabled 1

NOTE 1: See Section 2.2.3.2 for important information regarding switch labels.

Dip Switch settings are customer specific.

T3401000-1UM REVISION: B 4-2

4.0 MAINTENANCE {CALIBRATION}

4.2 MOTHERBOARD (HVPS) CALIBRATION 4.2.1 Component Location Use the following graphics to locate calibration components.

Figure 4-1 Motherboard Layout 4.2.2 High Voltage Calibration NOTE:

This is a functional checkout. The actual high voltage will have to be set based on detector requirements.

a. Monitor the output voltage of the HV power supply on rear panel connector J2 with a DMM capable of reading up to 1000 Vdc.
b. Vary R4 on the motherboard and verify that the power supply produces between 300 and 1000 Vdc.
c. Set the power supply output for 800 Vdc with R4.
d. Verify the HV value on the MAIN MENU Display is 800V +/- 12V.

T3401000-1UM REVISION: B 4-3

4.0 MAINTENANCE (CALIBRATION) 4.3 PWA, ANALOG AMPLIFIER - CALIBRATION 4.3.1 Component Location Use the following graphics to locate calibration components.

0 DMM +for Current Cal

(% Power)

Figure 4-2 Analog Amplifier Board Layout 4.3.2 Power/Current Calibration DMM-In general, the NMP-1000 and detector shouJd be setup such that 1mA equals 100% reactor power. This is accomplished by first performing the bench calibration described below, then reinstalling the instrument, operating the reactor to determine actual power levels (via other instrumentation), and physically repositioning the detector so the NMP indicated power equals actual power.

T3401000-1UM REVISION: B 4-4

4.0 MAINTENANCE (CALIBRATION) 4.3.2.1 Setup - Null NOTE:

Anytime any circuit boards are removed or installed, instrument power must be OFF to prevent damage to the circuits. Use caution and discharge static electricity to the extent practicable before handling or working with circuits.

a.

Install the extender card for the analog amplifier and install the EMI shield.

b.

Connect a DMM to TP1 (+) and TP6 (-) on the Analog Amplifier PWA.

c.

Set the current source for an output of zero current (O.OOOnA), and wait at least 5 minutes. Adjust potentiometer R1 until the DMM reads 0.00 +/- 0.05 Vdc on TP1. After every adjustment, wait at least 5 minutes for the voltage to settle. Readjust _until the desired accuracy is reached.

NOTE:

When adjusting the offset voltage, pay attention to the compliance voltage of the current source. If necessary, readjust R1 until the compliance voltage displayed by the current source is a positive value.

Any positive value is fine. A negative value will cause the manual current test to fail (range will not be adjustable down to 10E-11 range with the front panel potentiometer), as it will produce a small current that is additive to the expected current from the manual current source.

When setting R1 for a positive compliance voltage rather than OV offset, a small measurement error will be introduced in the lowest current range. That error is dependent on the amplitude of the compliance voltage and is typically less than 10% at 5pA.

d. On the MAIN MENU Display, select the Gain button to enter the GAIN MENU Display.

4.3.2.2 E-11

a.

Select the E-11 button on the GAIN MENU Display.

b.

Set the current source for an output of 10pA.

c.

Adjust potentiometer R4 until the DMM reads -10.00 +/- 0.05 Vdc.

NOTE:

It may take several minutes for the reading to stabilize in the lowest ranges. Wait for the reading to stabilize before making final adjustments.

d.

Set the current source for an output of 5pA.

T3401000-1UM REVISION: B 4-5

4.0 MAINTENANCE (CALIBRATION)

e.

Verify that the DMM reads -5.00 +/- 2 Vdc after the reading has stabilized.

4.3.2.3 E-10

a.

Select the E-10 button on the GAIN MENU Display.

b.

Set the current source for an output of 1 OOpA.

c.

Adjust potentiometer R30 until the DMM reads -10.00 +/- 0.05 Vdc.

4.3.2.4 E-9

a.

Select the E-9 button on the GAIN MENU Display.

b.

Set the current source for an output of zero current.

c.

Adjust potentiometer R49 until the DMM reads 0.00 +/- 0.05 Vdc, or until R49 is adjusted fully CCW.

d. Set the current source for an output of 1 nA.
e.

Adjust potentiometer R48 until the DMM reads -10.00 +/- 0.05 Vdc.

4.3.2.5 E-8

a.

Select the E-8 button on the GAIN MENU Display.

b.

Set the current source for an output of 1 OnA.

c.

Adjust potentiometer R66 until the DMM reads -10.00 +/- 0.05 Vdc.

4.3.2.6 E-7

a.

Select the E-7 button on the GAIN MENU Display.

b.

Set the current source for an output of 1 OOnA.

c.

Adjust potentiometer R65 until the DMM reads -10.00 +/- 0.05 Vdc.

4.3.2.7 E-6

a.

Select the E-6 button on the GAIN MENU Display.

b.

Set the current source for an output of 1 µA.

c.

Adjust potentiometer R64 until the DMM reads -10.00 +/- 0.05 Vdc.

T3401000-1UM REVISION: B 4-6

4.0 MAINTENANCE (CALIBRATION) 4.3.2.8 E-5

a.

Select the E-5 button on the GAIN MENU Display.

b.

Set the current source for an output of 1 OµA.

c.

Adjust potentiometer R82 until the DMM reads -10.00 +/- 0.05 Vdc.

4.3.2.9 E-4

a.

Select the E-4 button on the GAIN MENU Display.

b.

Set the current source for an output of 100µA.

c.

Adjust potentiometer R83 until the DMM reads -10.00 +/- 0.05 Vdc.

4.3.2.10 E-3

a.

Select the E-3 button on the GAIN MENU Display.

b.

Set the current source for an output of 1 mA.

c.

Adjust potentiometer R84 until the DMM reads -10.00 +/- 0.05 Vdc.

4.3.3 Gain NOTE:

This adjustment should not be used to make indicated power equal actual power during reactor operation, as repeated adjustments could cause the instrument to operate above 1.2 mA (or outside the calibrated range). The preferred method is to perform the bench calibration first, then physically reposition the detector to make indicated power equal actual power.

a.

Connect a DMM to TP4 (+) and TP6 (-) on the NMP-1 000 and set it to measure Vdc. Alternately, connect a DMM to the corresponding signal on the extender card (instead of TP4) for easier access.

b.

GAIN 100%: Set the current source for an output of 1 mA. Adjust potentiometer R18 until the DMM reads 8.33

+/- 0.05 Vdc on TP4.

c.

GAIN 120%: Set the current source for an output of 1.2 mA. Verify the DMM reads 10.00 +/- 0.05 Vdc on TP4.

T3401000-1UM REVISION: B 4-7

4.0 MAINTENANCE (CALIBRATION) 4.3.4 Calibrate and Test Current 4.3.4.1 Calibrate High NOTE:

Tests time out and the NMP returns to normal operation after 50 seconds. Re-enable the test mode if the adjustment is not completed within that time.

a.

Select the AUTO button on the GAIN MENU Display.

b.

Select the Test/Cal button on the GAIN MENU Display to enter the TEST/CAL MENU Display.

c.

Select the Calibrate High button on the TEST/CAL MENU Display.

d. Adjust potentiometer R37 until the DMM reads >10.0 Vdc on TP4.

NOTE:

Adjusting R37 until the DMM reads >10.0V ensures the test circuit produces more than 1.2mA (or 120% power), which is the nominal high power trip setpoint. To set the test current to a different value, adjust R37 accordingly.

Example:

If a high power trip test current of 1.1 mA ( or 110% power) is desired, adjust R37 for a DMM reading of -9.167Vdc.

4.3.4.2 Calibrate Low

a.

Select the Calibrate Low button on the TEST/CAL MENU Display.

b.

Observe the voltage on TP4 should read about 1.50 +/- 0.1 Vdc.

4.3.4.3 Test (Man) Current

a.

Tum the MANUAL CURRENT ADJUST potentiometer on the front panel fully counter clockwise (CCW).

b.

Select the Man Current button on the TEST/CAL MENU Display.

c. Observe the Gain Range on the TEST/CAL Menu Display.
d.

Slowly start turning the MANUAL CURRENT ADJUST potentiometer on the front panel clockwise (CW).

e.

As the potentiometer is turned CW, observe the Gain Range change from 10E-11 to 10E-3 over the range of the potentiometer.

NOTE:

Refer to step 4.3.2.1. If the amplifier offset was set to OV rather than a positive compliance voltage, it may not be possible to manually adjust the potentiometer into the lowest gain ranges.

T3401000-1UM REVISION: B 4-8

4.0 MAINTENANCE (CALIBRATION)

f.

Turn the MANUAL CURRENT ADJUST potentiometer on the front panel fully counter clockwise (CCW).

4.3.5 Auto-Range Setpoints

a.

Select GAIN on the Display, select Auto, then select Main.

b.

Set the current on the current source to 0.1 µA. Using steps of 0.1 µA, increase current to 0.9 µA. Observe that the range is switched to the next higher range at -90% Power.

c.

Using steps of 0.1 µA, decrease the current of 0.9 µA to 0.1 µA. Observe that the range is switched to the next lower range at -8% Power.

NOTE: The auto-range setpoints are encoded in the NMP firmware and not user adjustable. The above steps merely replicate the factory acceptance test to verify correct functionality of the software and hardware.

T3401000-1 UM REVISION: B 4-9

4.0 MAINTENANCE (CALIBRATION) 4.4 PWA, TRIP/ALARM - CALIBRATION AND FUNCTIONAL CHECK 4.4.1 Component Location Use the following graphics to locate calibration components.

RS TRIP6 (Spare)

R19 TRIPS (Spare)

R33 TRIP4 (Spare)

R47 HVTrip (Trip 3)

R61 Power Trip (Trip 2)

Figure 4-3 Trip/Alarm Board Layout T3401000-1UM REVISION: B 4-10 R7S Power Trip (Trip 1)

~@

0 II II

+

4.0 MAINTENANCE (CALIBRATION) 4.4.2 Calibration of Trips 4.4.2.1 Setup, Normal Operation NOTE:

The trip relay connections on the remote connectors may be checked as part of this calibration. Refer to the remote connector description tables In Section 6.0

SUMMARY

OF REAR PANEL CONNECTIONS.

NOTE:

Power trips 1 and 2 are user configurable. One trip circuit Is usually chosen to be the reactor power high alarm, the other trip circuit Is the reactor power high trip. Functionality is based on the overall system configuration, For the purpose of this calibration procedure, trip 1 has been assigned the high power trip functionality, and trip 2 the high power alert. It 1s the user's responsibility to venfy these assignments and adjust the trip settings accordingly.

a.

Verify the Trip/Alann board jumpers are configured per the following table.

NOTE:

If the site jumper configuration is different, record the site configuration so that it can be restored after testing.

Table 4-2 Trip/Alarm Jumper Settings Jumper PINS Name JP18 2-3 JP17 2-3 Trip 1 JP16 1-2 JP15 2-3 JP14 1-2 Trip 2 JP13 2-3 JP12 2-3 JP11 2-3 HVTrip JP10 1-2 JP9 2-3 JP8 2-3 N/A JP?

1-2 JP6 2-3 JPS 1-2 N/A JP4 2-3 JP3 2-3 N/A T3401000-1UM REVISION: B 4-11

4.0 MAINTENANCE (CALIBRATION)

Jumoer PINS Name JP2 2-3 JP1 1-2

b.

Select the Main button on the TEST/CAL MENU Display to enter the MAIN MENU Display.

NOTE:

The HV trip should be set to the setpoint that is determined to be correct for the site. 300 Vdc Is used as a setpolnt for test purposes.

c.

Adjust R4 on the Motherboard until the display displays HV: 300V, or as selected by the customer.

d.

Tum R75 on the Trip/Alarm board fully CW.

e.

Tum R61 on the Trip/Alarm board fully CW.

f.

Tum R47 on the Trip/Alarm board fully CCW.

g., Set the current source for an output of 1.1 mA.

NOTE:

This is the current level expected for a high power alert and corresponds to 110% reactor power. If a different value is desired, adjust the current accordingly.

Example: For 105% reactor power high alert, set the current source to 1.05mA

h.

Select the Trip Reset button on the GAIN MENU Display.

i.

Observe that all front panel trip indicator LEDs are off.

4.4.2.2 Trip 2

a.

Tum R61 CCW slowly until the Trip 1 LED on the front panel lights up.

4.4.2.3 Trip 1

a.

Set the current source for an output of 1.2mA NOTE:

This is the current level expected for a high power trip and corresponds to 120% reactor power. If a different value is desired, adjust the current accordingly.

Example: For 110% reactor high power trip, set the current source to 1.1 mA.

T3401000-1UM REVISION: B 4-12

4.0 MAINTENANCE (CALIBRATION)

b.

Tum R75 CCW slowly until the Trip 2 LED on the front panel lights up.

4.4.2.4 High Voltage

a.

Tum R47 CW slowly until the High Voltage LED on the front panel lights up at just below the setpoint of 300V.

4.4.2.5 Restore System, Normal Operation

a.

Adjust R4 on the Motherboard until the Main Menu displays HV: 800 +/-12 Vdc.

b.

Set the current source for an output of 1.0mA

c.

Select the Trip Reset button on the GAIN MENU Display.

d.

Observe that all front panel trip indicator LEDs are off.

T3401000-1UM REVISION: B 4-13

4.0 MAINTENANCE {CALIBRATION) 4.5 PWA, ISOLATION AMPLIFIER - CALIBRATION AND FUNCTIONAL CHECK 4.5.1 Component Location Use the following graphics to locate calibration components.

R12 R13 Offset A Span B R14 Offset B Figure 4-4 Isolation Amplifier Board Layout 4.5.2 Calibration of Isolation Amplifier There are 2 isolation amplifier outputs, A and B, which indicate the percent power value. They can be jumper configured to either 4-20mA or 0-10V. This calibration section is written for the 4-20 mA output If 0-10 Vdc is desired, change the switch setting and convert the mA values to Vdc.

T3401000-1UM REVISION: B 4-14

4.0 MAINTENANCE (CALIBRATION)

Table 4-3 Analog Outputs Jumper Settings Cutout 4-20mA 0-10V A JP1 1-2 2-3 JP2 2-3 1-2 B JP3 1-2 2-3 JP4 2-3 1-2 4.5.2.1 Setup

a. Verify that the jumpers are set for the 4-20 mA configuration on the Isolation Amplifier board per Table 4-3.

4.5.2.2 Analog Output A

a.

Set the current source for an output of zero current.

b.

Set the DMM to measure mA and connect it to Pins 22 (+) and 23 (-) of J5 (DB-37 Connector) on the rear of the NMP-1000.

c.

On the front panel screen select Gain and E-3.

d. Adjust R12 on the Isolation Amplifier board until the DMM reads 4.0 +/-0.2 mA.
e.

Set the current source for an output of 1.2 mA.

f.

Adjust R11 on the Isolation Amplifier board until the DMM reads 20.0 +/-0.2 mA 4.5.2.3 Analog Output B

a.

Connect the DMM set to measure mA to Pins 24 (+) and 25 (-) of J5 (DB-37 Connector) on the rear of the NMP-1000.

b.

Set the current source for an output of zero current

c.

Adjust R14 on the Isolation Amplifier board until the DMM reads 4.0 +/-0.2 mA.

d.

Set the current source for an output of 1.2 mA.

e. Adjust R13 on the Isolation Amplifier board until the DMM reads 20.0 +/-0.2 mA T3401000-1UM REVISION: B 4-15

4.0 MAINTENANCE (CALIBRATION) 4.6 COMPENSATION POWER SUPPLY -FUNCTIONAL CHECK 4.6.1 Minimum Value - Full CCW

a.

Tum both the Coarse Adjust and Fine Adjust potentiometers on the front panel fully CCW.

b.

On the MAIN MENU Display, verify COMP PS: VALUE Is less than 2V.

4.6.2 Maximum Value - Full CW

a.

Tum both the Coarse Adjust and Fine Adjust potentiometers on the front panel fully CW.

b.

On the MAIN MENU Display, verify COMP PS: VALUE is larger than 99% of the rated maximum compensating voltage for the unit under test 4.6.3 Normal Operation

a.

Adjust the Coarse Adjust and Fine Adjust potentiometers for a COMP PS value of about 50 Vdc or as determined by the customer.

4.7 REMOTE DISPLAY VERIFICATION NOTE:

This section is not applicable to sites that do not have remote displays.

4.7.1 Setup

a.

Connect the remote display via the RS-232 cable.

b.

Verify the remote screen software version number displayed on the ABOUT MENU matches the software version installed in the NLW-1000 Local Display.

c.

Verify that the backlight and contrast can be adjusted

d.

On the remote display, select Trip Reset, select Gain, and then select E-3.

4.7.2 Trip Occurs

a.

Using the current source and starting at 0.9mA, increase the current using steps of 0.1 mA until a current of 1.2 mA Is achieved.

b.

Verify that both TRIP 1 and TRIP 2 LEDs on the front panel are illuminated.

T3401000-1UM REVISION: B 4-16

4.0 MAINTENANCE (CALIBRATION) 4.7.3 Return to Normal Operation

a.

Decrease current source output to 1.0mA

b.

Select Trip Reset on the Remote Screen. Trip 1 and Trip 2 LED on the front panel should be extinguished.

4.8 REMOTE SIGNAL FUNCTIONS 4.8.1 Electrometer Pulse Disconnect

a.

Set the NMP-1000 to Remote Mode.

b.

Jumper JS Pin 20 (GND) to J6 Pin 26 (sets to Auto Range Select) on the D-Sub connectors in the rear of the NMP.

c.

Set the current source to 1 nA

d.

Verify the front panel screen shows power to be within 7% and 13% and the range to be 1 OE-8.

e. Jumper JS Pin 29 (+15 Vdc) to JS Pin 9 to open the pulse disconnect relay.
f.

Verify the electrometer Is disconnected as indicated by the percentage of poWer to be within 7% - 13% and the range set to 10E-11.

g.

Remove the jumper from JS Pin 28 to JS Pm 9.

h. Verify the power range has returned to 1 OE-8.

4.8.2 Remote Select Tost/Cal Modes

a.

On the front panel of the NMP-1000, press Trip Reset

b.

Press the Test/Cal button located on the Main Menu.

c.

Verify that the NMP-1000 is In Operate mode.

d.

Momentarily connect JS Pin 28 (+15 vdc) to JS Pin 16. This may best be accomplished with a push button switch. Verify the NMP has advanced to the first test mode.

e.

Continue to momentarily connect JS Pin 28 (+15 vdc) to JS Pin 16 and cycle through all 5 modes i.e. Operate, Calibrate High, Calibrate Low, Man Current, and HV test.

4.8.3 Remote Trip Reset

a.

On the front panel of the NMP-1000, select Test/Cal Menu.

b.

On the front panel, verrfy that Tnp 1, Tnp 2, and High Voltage LED's are ht.

c.

Select Operat~ mode.

d.

Momentarily Jumper JS Pin 20 (GND) to JS Pin 19 to activate the trip reset

e.

Verify that all trips are cleared by verifying Trip 1, Trip 2, and High Voltage LEDs are off.

T3401000-1UM REVISION: B 4-17

4.0 MAINTENANCE (CALIBRATION) 4.9 REMOTE VOLTAGE

a.

Verify the voltage reading between J5 Pln 28 (+15V) and J5 Pin 27 (Ground) Is +15.0 Vdc +/- 0.5 Vdc.

b.

Verify the voltage reading between J5 Pin 30 (+24V) and J5 Pin 27 (Ground) Is +24.0 Vdc +/- 0.5 Vdc.

4.10 WATCH DOG TIMER

a.

Select trip reset on the front panel screen.

b.

Vertfy no trip LEDs on the front panel are Illuminated.

c.

On the digital interface board, set dip switch 4 on S1 to the OFF position. Verify the heartbeat has stopped pulsing on the NLW.

d.

Verify the contact between Connector J4 Pin 20 (Trip_ 1_A-NO) and Pin 24 (Trip_ 1_A-C) is open (TRIP 1 ).

e.

Verify the contact between Connector J4 Pin 14 (Trip_2_A-NO) and Pin 18 (Trip_2_A-C) is open (TRIP 2).

, f.

Verify the contact between Connector J4 Pin 13 (HV_Trip_A-NO) and Pin 9 (HV_Trlp_A-C) Is open (HV TRIP).

g.

On Digital Interface board reset dip switch 4 to ON position and cycle power on the NLW. Verify heartbeat is pulsing.

T3401000-1UM REVISION: B 4-18

5.0 ENGINEERING DRAWINGS 5.0 ENGINEERING DRAWING$

5.1 LIST OF ENGINEERING DRAWINGS Table 5-1 llsts the engineering drawings by assembly for the NMP-1000. The drawings marked with an asterisk(*)

are not included with this manual.

Table 5-1 Engineering Drawing List Description MULTI-RANGE LINEAR CHANNEL NMP-1000 PARTS LIST, MULTI-RANGE LINEAR CHANNEL NMP-1000 A1 PWA, t\\lMP-1000 MOTHERBOARD SCHEMATIC, A1 PWA, NLP-1000 MOTHERBOARD A2. PWA, ANALOG AMPLIFIER SCHEMATIC, A2. PWA, ANALOG AMPLIFIER A3 PWA, DIGITAL INTERFACE SCHEMATIC, A3 PWA, DIGITAL INTERFACE A4 PWA, TRIP/ALARM SCHEMATIC, M PWA, TRIP/ALARM A5 PWA, ISOLATION AMPLIFIER SCHEMATIC, A5 PWA, ISOLATION AMPLIFIER A6 DISPLAY, 3.8" LCD MODULE, TRANSFLECTIVE A7 PW A, FRONT PANEL SCHEMATIC, A7 PWA, FRONT PANEL PS 1 POWER SUPPLY PS2 COMPENSATION POWER SUPPLY (200 Vdc maximum)

PS2 COMPENSATION POWER SUPPLY (50 Vdc maximum)

PS2 COMPENSATION POWER SUPPLY (150 Vdc maximum)

Drawing Number T3401000 T3401000-001 T3401000-002 T3401000-003 Depending on compensating PS T3400113 T3400111 T3400133 T3400131 T3133303 T3133301 T3301133 T3301131 T3133113 T3133111 304922*

T3400123 T3400121 305855*

306495*

307127*

307128*

T3401000-1UM REVISION: B 5-1

5.0 ENGINEERING DRAWINGS 02/24/2015 Dynamic Li st Di splay l

GA M-BOM -- --

I I I I I

  • I
  • ~

1 *

  • I
  • I
  • ~
  • II 1=

1.5 T3401000-1UM REVISION: B 5-2

5.0 ENGINEERING DRAWINGS

[iii l

~

T3401000-1UM REVISION: B 5-3

5.0 ENGINEERING DRAWINGS Ir I

I I

I *

~

I

  • 1.5 T3401000-1UM REVISION: B 5-4

5.0 ENGINEERING DRAWINGS

~

~

~

T3401000-1UM REVISION: B 5-5

5.0 ENGINEERING DRAWINGS

~

~

I I

I

~-

~

  • I

~

T3401000-1UM REVISION: B 5-6

5.0 ENGINEERING DRAWINGS T3401000-1UM REVISION: B 5-7

5.0 ENGINEERING DRAWINGS T3401000-1UM REVISION: B 5-8 This page intentionally left blank.

GA PROPRIETARY 6.0

SUMMARY

OF REAR PANEL CONNECTIONS 6.0

SUMMARY

OF REAR PANEL CONNECTIONS This is the detailed list of all inputs and outputs from the remote/rear panel.

Table 6-1 Rear Panel Connectors Connector Type Function J1 BNC Current input from detector, isolated from chassis J2 MHV High voltage output to detector, isolated from chassis J3 TNC Compensation voltage output to Ion chamber, Isolated from chassis POWER AC AC input power, line filter, with fuses and on/off switch Fuses (2): 3A, time delay JB DB-9 RS-232 communication port for maintenance and remote display (male)

Pin 2: RX (to pin 2 TX on Display)

Pin 3: TX (to pin 3 RX on Display)

Pin 5: GND (to pin 5 GND on Display)

NOTE: For connection to a PC In maintenance mode, use a null-modem cable.

Jg Ethernet Ethernet port for communication with console.

Table 6-2 DB-25 (J4)

Remote DB-25 connector J4, pin (male)

Pin Name Function Rating 1,2,3,4, 5,6, 7 NC Not Connected 8

HV_TRIP _B-NO HV trip relay, con'tact B, NO lmax = 1A; Vmax = 30 Vdc 9

HV_TRIP _A-C HV trip relay, contact A, common lmax = 1A; Vmax = 30 Vdc 10 HV_TRIP _B-NC HV trip relay, contact B, NC lmax = 1A; Vmax = 30 Vdc 11 HY_ TRIP _A-NC HV trip relay, contact A, NC lmax = 1A; Vmax = 30 Vdc 12 HV_TRIP _B-C HV trip relay, contact B, common lmax = 1A; Vmax = 30 Vdc 13 HV _ TRIP _A-NO HV trlp relay, contact A, NO lmax = 1A; Vmax = 30 Vdc 14 TRIP _2_A-NO Trip relay 2, contact A, NO lmax = 1A; Vmax = 30 Vdc 15 TRIP_2_B-C Trip relay 2, contact B, common lmax = 1A; Vmax = 30 Vdc 16 TRIP _2_A-NC Trip relay 2, contact A, NC lmax = 1A; Vmax = 30 Vdc 17 TRIP _2_B-NC Trip relay 2, contact B, NC lmax = 1A; Vmax = 30 Vdc 18 TRIP_2_A-C Trip relay 2, contact A, common lmax = 1A; Vmax = 30 Vdc 19 TRIP _2_B-NO Trip relay 2, contact B, NO lmax = 1A; Vmax = 30 Vdc 20 TRIP_ 1_A-NO Trip relay 1, contact A, NO lmax = 1A; Vmax = 30 Vdc 21 TRIP_1_B-C Trip relay 1, contact B, common lmax = 1A; Vmax = 30 Vdc 22 TRIP_ 1_A-NC Trip relay 1, contact A, NC lmax = 1A; Vmax = 30 Vdc 23 TRIP_ 1_B-NC Trip relay 1, contact B, NC lmax = 1A; Vmax = 30 Vdc 24 TRIP_1_A-C Trip relay 1, contact A, common lmax = 1A; Vmax = 30 Vdc 25 TRIP _1_B-NO Trip relay 1, contact B, NO lmax = 1A; Vmax = 30 Vdc T3401000-1UM REVISION: B GA PROPRIETARY 6-1

GA PROPRIETARY 6.0

SUMMARY

OF REAR PANEL CONNECTIONS Table 6-3 DB-37 (J5)

Remote DB-37 connector JS, pin (male)

Pin Name Function 1, 2 GND Ground 3, 4, 5, 6, 7, NC Not connected 8

g REM_PULSE_DIS Disconnects electrometer when reactor is pulsed Active high (+15V); Zin= 100k0 10 HV_TRIP _LOGIC-HV trip emitter Opto-isolated transistor 11 TRIP1_LOGIC-Logic trip 1 emitter Opto-lsolated transistor 12 TRIP1_LOGIC+

Logic trip 1 collector Opto-isolated transistor, use with pull-up resistor VCEmax = 80V; ICmax = 50mA 13 HV_TRIP _LOGIC+

HV trip collector Opto-isolated transistor, use with pull-up resistor VCEmax = 80V; ICmax = 50mA 14 TRIP2_LOGIC+

Logic trip 2 collector Opto-isolated transistor, use with pull-up resistor VCEmax = 80V; ICmax = 50mA 15 TRIP2_LOGIC-Logic trip 2 emitter Opto-isolated transistor 16 REM_SEL Remotely enables test/cal modes Expect momentary logic high to cycle through test modes Active high (+15V); Zin= 100k0 17 NC Not Connected 18 NC Not Connected 19 REM_ TRIP _RESET Resets all trips from the remote Expect momentary logic low (GND) to activate Open circuit voltage = 15V; Zout = 5000 20 GND Ground 21 NC Not Connected 22 PERCENT _PWR_IS01 Isolated analog output 1, 0-1 OV, 4-20mA Current mode: av compliance voltage minimum Voltage mode: Connected device must have input impedance >

50k0, otherwise read error will be >1 %

23 PERCENT PWR IS01 RET Isolated analog output 1 return 24 PERCENT _PWR_IS02 Isolated analog output 2, 0-10V, 4-20mA Current mode: av compllance voltage minimum Voltage mode: Connected device must have input impedance >

50k0, otherwise read error will be > 1 %

25 PERCENT PWR IS02 RET Isolated analog output 2 return 26 NC Not Connected 27 GND Ground T3401000-1UM REVISION: B GA PROPRIETARY 6-2

GA PROPRIETARY 6.0

SUMMARY

OF REAR PANEL CONNECTIONS Remote DB-37 connector JS, pin (male)

Pin Name Function 28,29

+15V

+15 Vdc Source 100mA maximum 30,31

+24V

+24 Vdc Source 250mA maximum 32, 33, 34, NC Not connected 35, 36,37 Table 6-4 DB-37 (J6)

Remote DB-37 connector J6, socket (female)

Pin Name Function 1

1E-4_1ND_1 Switch contact 1 for 1 E-4 range i~dication lmax = 1 OOmA, Vmax = 30 Vdc 2

1E-4 IND 2 Switch contact 2 for 1 E-4 range indication 3

1E-3_1ND_1 Switch contact 1 for 1 E-3 range indication I max = 1 OOmA, Vmax = 30 Vdc 4

1E-3 IND 2 Switch contact 2 for 1 E-3 range indication 5

AUTO_IND_1 Switch contact 1 for autorange indication lmax = 100mA, Vmax = 30 Vdc 6

AUTO IND 2 Switch contact 2 for autorange indication 7

1E-11_1ND_1 Switch contact 1 for 1 E-11 range Indication lmax = 100mA, Vmax = 30 Vdc 8

1E-11 IND_2 Switch contact 2 for 1 E-11 range indication 9

1E-10_1ND_1 Switch contact 1 for 1E-10 range indication I max = 1 OOmA, Vmax = 30 Vdc 10 1E-10 IND 2 Switch contact 2 for 1E-10 range indication 11 1E-5_1ND_1 Switch contact 1 for 1 E-5 range indication I max = 1 OOmA, Vmax = 30 Vdc 12 1E-5 IND 2 Switch contact 2 for 1 E-5 range indication 13 1E-6_1ND_1 Switch contact 1 for 1 E-6 range indication I max = 1 OOmA, Vmax = 30 Vdc 14 1E-6 IND 2 Switch contact 2 for 1 E-6 range indication 15 1E-7_1ND_1 Switch contact 1 for 1 E-7 range indication lmax = 100mA, Vmax = 30 Vdc 16 1E-9_1ND_1 Switch contact 1 for 1 E-9 range indication lmax = 1 OOmA, Vmax = 30 Vdc 17 1E-9 IND 2 Switch contact 2 for 1 E-9 range indication 18 1E-8_1ND_1 Switch contact 1 for 1 E-8 range indication lmax = 100mA, Vmax = 30 Vdc 19 1E-8 IND 2 Switch contact 2 for 1 E-8 range indication 20 REM_1E-4 Remote select for 1 E-4 range Active low (0 to 1V), Zout = 1 OOkO, Vhigh = 15V T3401000-1UM REVISION: B GA PROPRIETARY 6-3

GA PROPRIETARY 6.0

SUMMARY

OF REAR PANEL CONNECTIONS Remote DB-37 connector J6, socket (female)

Pin Name Function 21 REM_1E-3 Remote select for 1 E-3 range Active low (0 to 1V); Zout = 100k0; Vhigh = 15V 22 REM_1E-6 Remote select for 1 E-6 range Active low (0 to 1V); Zout = 100k0; Vhigh = 15V 23 REM_1E-7 Remote select for 1 E-7 range Active low (0 to 1V); Zout = 1 OOkO; Vhigh = 15V 24 REM_1E-8 Remote select for 1 E-8 range Active low (0 to 1V); Zout = 100k0; Vhigh = 15V 25 REM_1E-9 Remote select for 1 E-9 range Active low (0 to 1V); Zout = 100k0; Vhigh = 15V 26 REM_AUTO Remote select for autorange Active low (0 to 1V); Zout = 1 OOkO; Vhigh = 15V 27 REM_1E-10 Remote select for 1 E-10 range Active low (0 to 1V); Zout = 100k0; Vh1gh = 15V 28 REM_1E-11 Remote select for 1 E-11 range Active low (0 to 1V); Zout = 1 OOkO; Vhigh = 15V 29 REM_1E-5 Remote select for 1 E-5 range Acbve low (0 to 1V); Zout = 100k0; Vhigh = 15V 30,31,32 NC Not connected 33,34,35, 36 GND Ground 37 1E-7 IND 2 Switch contact 2 for 1E-7 range Indication T3401000-1 UM REVISION: B GA PROPRIETARY 6-4

APPENDIX I I

I I

I I

T3401000-1UM REVISION: B 1-1

APPENDIX I T3401000-1UM REVISION: B 1-2

APPENDIX I T3401000-1UM REVISION: B 1-3

APPENDIX I IL I

I

= = =-

=

=

T3401000-1UM REVISION: B

--~

1-4

APPENDIX I

~--

- ~

~

Ii

~ -

- - - -~

'~

~

~

~

=

T3401000-1UM REVISION: B 1-5

APPENDIX I T3401000-1UM REVISION: B 1-6

APPENDIX I I

I I

'~

-=

T3401000-1UM REVISION: B 1-7

APPENDIX I T3401000-1UM REVISION: B 1-8

I APPENDIX II T3401000-1UM REVISION: B 11-1

APPENDIX II T3401000-1UM REVISION: B 11-2

APPENDIX II T3401000-1UM REVISION: B 11-3

APPENDIX Ill

Document Number T3401000-10M z

~

~ -p

~o~

)> 0 0 0

ZCo r-rri m ~

zoc

)> -u r z m :::!

(') ::0 I

m>~

~:::!z

)> 0 G')

zzm c>r

)>z-

  • o~
0 BY

+

t:ENERAL ATOMICS lli.Cf'ROautC#lfflCS 16969 MESAMINT STREET SAN DIEGO, CA 92127 Customer Service (858) 522-8300 Document Number T3401000-0TM z

~

'"O

~~*

)> 0 0

-Oo zco

-Ir -

mm~

z 0 c

)> "'tJ r Zm --i

(") ~ I

~::!~

l>QG)

Zzm C )> r

)> z z rom BY

)>

o

+c:s~IIS 16969 Mesamlnt Street San Diego, CA 92127 Customer Service (858) 522-8300