ML20012D521

From kanterella
Jump to navigation Jump to search
Notice of Deviation from Insp on 900205-09.Deviation Noted: on 900209,control Room Panels Did Not Have Specific Identification of post-accident Monitoring Instrumentation as Required by Reg Guide 1.97
ML20012D521
Person / Time
Site: Yankee Rowe
Issue date: 03/13/1990
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20012D517 List:
References
RTR-REGGD-01.097, RTR-REGGD-1.097 50-029-90-02, 50-29-90-2, NUDOCS 9003280007
Download: ML20012D521 (1)


Text

,,

v t SG L

ar-APPENDIX A-NOTICE OF DEVIATION Yankee Atomic Electric Company-Docket No.50-029 Rowe, Massachusetts -

License No. DPR-3 As a. result of the. inspection conducted on February:5-9,1990, and in accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (Enforcement Policy) the

.following deviation'was identified:

Table 1, Section 8 of Regulatory Guide 1.97, Revision 3 states that r

types A, B and C instruments designated as Categories 1 and 2 should be specifically identified with a common designation on the control panels so that the operator can easily discern that they are intended for use under accident conditions.

Contrary to the above, on Feb' uary 9,1990, the control room panels did r

not have specific identification of post accident monitoring-instrumentation as required by Regulatory Guide'1.97.

This is a deviation.

Yankee Atomic Electric Company is hereby requested to submit to-this office within thirty days of the date of the letter which transmitted this Notice, a written statement or explanation in reply,-including:

(1) the reason for the deviation, if admitted; (2) the corrective steps which have been'taken.and the results achieved; (3) corrective steps which will be taken to avoid further deviations; and (4) the date when full compliance will be achieved.

Where

good cause is shown, consideration will'be given to extending this response time.

m 9003280007 900313 b

gDR ADOCK 05000029 h ac.

A H

.