1 or E80N EDISON PLAZA March 15, 1990 330 MADISON AVENUE Tottoo. osio nacw.oam Docket No. 50-346 NP33-90-003 License No. Npr-3 BB90-00319 United States Nuclear Regulatory Commission Document Conttol Desk Vashington, D.C.
20555 Gentlement
Subject:
Voluntary Report of a Missed Daily Test of the Portable Fire Detection System On July 28, 1989, Toledo Edison submitted a letter to the NRC (Serial reduce No. 1689) describing a portable fire detection system intended to certain continuous fire watches to hourly fire vatch patrols. The letter included the planned compensatory actions for the deviations from the NFPA 72D code. The actions included a test at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of the auto-dialer, message unit, and phone lines.
Contrary to the above, on February 4, 1990, the daily functional test was not done. The hourly fire vatch check of the local panel for alarms and to assure the phone line was connected was still being performed. On February 5, 1990, it was recognized that the daily functional test was missed. The functional test was performed, which verified that the circuit between the local panel and the control room was still functioning.
The test was missed due to a personnel error on the part of the Shift The Supervisor who inadvertently failed to ensure the test had been done.
The test had test activity vas on the Shitt Supervisor's turnover sheet.
usually been performed by the Shift Manager, but upon entry into Mode 5 and the commencement of the Sixth Refueling Outage, the Shift Manager was no longer a required member of the shift compliment. The veekend that the test was missed, no Shitt Manager vas scheduled to work.
To ensure this daily functional test of the portable detection system is performed, the requirement vill be added to the Oparations Department Monthly This document identifies tasks usually of a Activity Log, DB-0P-00003 repetitive nature and includes regulatory requirements, commitments, and good It operating practices to be accomplished by Shilt Operations personnel.
identifies the frequency for the activities and provides space for a checkoff when the activity is complete. This activity was added to the log as of March 9, 1990.
9003230058 900315 P
1 PDR ADOCK 05000346
{W%j l
5 PDC pM' 9
g,yc-.
or
$ti-F;#f0k '
[
J.
k7
- Decket'Nok $0-346'
-v?:
License No. NPF-3 Ifi,
' NP33-90-003-
~Page ?
.), '"
i The daily functional checks involve the non-supervised part of the portable m
detection' system.
For permanently' installed fire detection systems, the-Technical Specifications require surveillance ~of non-supervised circuits between the local panels and the control room once per 31 days.
Very truly yours, c.
[