ML20010F937

From kanterella
Jump to navigation Jump to search
Forwards LER 81-025/03L-0
Date released: 01/24/2020 Download: ML20010F937


LER 81-025/03L-0:on 810630,fire Developed on Exhaust Header of Diesel Generator 2.Caused by Oil Soaked Insulation Igniting When Exhaust Temp Reached Approx 1000 F Due to Oil Leak Through Gasket.Manifold Cleaned & Gaskets Changed
ML20010F940
Person / Time
Site: Arkansas Nuclear 
Issue date: 08/03/1981
From: Bramlett L
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML20010F940 (1)
Forwards LER 81-025/03L-0
ML20010F936
Person / Time
Site: Arkansas Nuclear 
Issue date: 08/03/1981
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: MADSEN G L
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML20010F936 (1)