  1. pn ua UNITED STATES 8N NUCLEAR REGULATORY COMMISSION o

W ASHINGTON, D. C. 20555

%,TCUP:GHB

/

70-2940 SNM-1879, Amendment No. 1 Southern California Edison Company ATTN: Mr. R. Dietch, Vice President Nuclear Engineering and Operations P.O. Box 800 2244 Walnut Grove Avenue Rosemead, California 91770 Gentlemeni In accordance with your applicatio dated July 17, 1981, and pursuant to Title.

10, Code of Federal Regulationpart 70, haef Materials License No.

[

SNM-1879 is hereby amended to dd th; a c v' Jub 17,10S! te ;;...J t storage N'g of new fuel assemblies in the fuel handling building prior to the installation In addition Condition 15 is added to P

of fire detection and alarm systems [ q g g,g 4

.[., 0 read as follows:

4jffj 15.

" Fuel assemblies may be stored fn the fuel handling building cf A d'

prior to the installation of fire detection and alarm devices gg provided that a continuous fire watch is established. The fire watch shall be maintained until all fire detection and alarm devices, described in the July 25, 1978 application, have been placed in operation. The fire detection and alarm devices shall be operational prior to fuel loading."

All other conditions of this license shall remain the same.

This license condition was discussed with, and agreed to by Mr. Derrick Mercurio, representing Southern California Edison Company and San Diego Gas and Electric Company, and George Bidinger of my staff.

FOR THE NUCLEAR REGULATORY COMMISSION R. G. Page, Chief Uranium Fuel Licensing Branch Division of Fuel Cycle and Material Safety 8108280526 810811' PDR ADOCK 07002940 C

PDR

b s

o A

s o

4 AUG 5 1961 DOCKET NOS:

70-2901 70-2940 APPLICANT:

Southern California Edison Company San Diego Gas and Electric Company San Oncfre Generating Station, Units 2 and 3

SUBJECT:

REVIEW 0F AMENOMENT APPLICATION DATED JULY 17,1981 TO DELETE FIRE DETECTION EQUIPMENT IN THE FUEL HANDLING BUIDDING I.

Background

The SNM licenses currently authorize the receipt, possession and storage of fresh fuel elements.

The fuel will be stored in their shipping con-tainers, in new fuel storage racks, and in the spent. fuel storage, racks.

The purpose of the amendment is to delete the requirement for fire de-tection and alzm devices in the fuel handling building.

The fire detection and alam devices have not been installed, but fresh fuel is scheduled to be shipped by August 13, 1981 and to be received by August 17,' 1301.

II.

Discussion The NRR Standard Review Plan requires fire detection and alam devices.

The NRR reviewer for fire safety would accept a continuous fire watch until the fire detection and alam devices are installed and placed in operation.

The following condition would resolbe this issue:

15.

Fuel assemblies Itay be stored in the fuel haddling building prior to the.< installation of fire detection and alam devices provided that a continuous fire watch is established. The fire watch shall be main-tained until all fire detection and alam devices, described in the July 1978 application (docketed by NRC on July 31,1978), have been placed in operation.

The fire detection and alam devices shall be opera-tional prior to fuel loading, The NRR Project Manager, Mr. Harry Rood, and the Reginr. V inspector, Mr.

Tolbert Young, have stated that they have no objection to this amendment.

  • "'c c >

................. 8

N.

N s

~~

AUG 51981 III. Conclusion and Recocinendation Fresh fuel may be safely stored in the fuel handling building provid' d e

that a continuous fire watch is established and maintained until fire detection and alarm devices are installed and placed in operation. Apprw al of the application is recognended, provided that the above condition is added to the license.

Original Signed by G. H. Bidinger Uranium Process Licnnsing Section Uranium Fuel Licensing Branch Division of Fuel Cycle and Material Safety Driginal signed bn Approved by:

" I C"'

W. T. Crow, Section Leader Distribution:

' Docket File 70-2901 70-2940 PDR (2)

NMSS r/f FCUF r/f FCUP r/f GHBidinger (2)

LTyson (2 )

WTCrow IE HQ (2)

JBlaylock RErickson JRobertson

/

...r.c.ue.2rg....rcur..$i'

.....r. Cue.... pq

/-

...GHBj,di nger j,rdLTyson WTC ro,,,,,,,,

,/

ei.ua1.....

....ei h..t.8.1..

..... e t.d.. /.a1...

................\\...............

...................