AD18 955y Donald A. Wells Ml nag p Assurance Edison EEEsm-July 29, \\p/ /,

s EF2-54 c

dlV[on s

Mr. James G. Keppler, Director i /,( 'g NIA _,

lM 'a'7S!jgron Region III u

fl U.S. Nuclear Regulatory Cmmission 799 Roosevelt Road Q

Glen Ellyn, Illinois 60137 q,f

, 4'

//*

m \\ \\/

/

Subject:

Final Report of 10CFR50.55(e) Item on Cut Reinforcing Bar YM25k I

Dear Mr. Keppler:

This is subnitted as Detroit Edison's final report on the Cut Reinforcing Bar problem which was reported per 50.55(e) requirenents.

The item was originally reported to Mr. F.J. Jablonski of NRC-Region III by Mssrs. R.W. Barr and W.M. Street of Detroit Edison on Decerrber 27, 1979. At that tine, it had been determined that cut rebar may have resulted in a re-duced floor load capacity in the Reactor Auxiliary Building at the Fermi 2 site.

Sargent and Lundy has reviewed the Reactor Auxiliary Building, and has found l

all floor slabs capable of supporting the original design loads except for l

the roof slab area in the end panel along Column Line 9 between Columns G and H.

An "as-built" analysis will be perforned by Sargent and Lundy on this 4" riab for new loading criteria. All overstressed sicbs will be re-inforr-3 at that tine.

If you have questions concerning this matter, please contact Mr. H.A. Walker, Supervisor-Construction Quality Assurance.

Very truly yours, f

V l

l DAW / HAW /cp

(

cc:

Mr. Victor Stello, Jr., Director Office of Inspection and Enforcement hey]

Division of Reactor Inspection Programs U.S. Nuclear Reculatory Cmmission A

Washington, D.C. 20555 Mr Bruce Little, Resident Inspector U.S. Nuclear Regulatory Cmmission Resident Inspectors Office 6450 North Dixie Highway Newport, Michigan 48166 8108210270 810729 DR ADOCK 05000 f[jg y 4_

l J