NPDES Permit AR 0009920,issued to AR Power & Light Co
ML20010B560
Person / Time
Site: Arkansas Nuclear  
Issue date: 06/05/1981
From: Dutton D
ENVIRONMENTAL PROTECTION AGENCY
To:
Shared Package
ML20010B558 List:
References
AR-0009920, AR-9920, NUDOCS 8108170236
Download: ML20010B560 (19)


Text

"

/

o renn.: w.

AR0001392 Apriwa,. N...

AR0001392 t

AUTIIORIZATION TO DISCIIARGE UNDER Tile NATIONAL POLLUTANT DISCIIARGE ELIMINATION SYSTEM In compliance with the provisions of the Federal Water Pollution Control Act, as amended, (33 U.S.C.1251 et. seq; the "Act"),

ArkansasPowerNdLightCompany PT 0. Box 551 ~~~ ~

- - ~ ~

- ~ -

~

Little Rock, Arkansas 72203 is authorized to du, charge from a facility located at Arkansas Nuclear One Pope County, Arkansas to receiving waters named Dardanelle Reservoir in e.ccordance with effluent limitations, monitoring requirements and other conditions set forth in Parts I, II, and III hereof.

This permit shall become effective on July 6, 1981 This permit and the authorization to discharge shall expire at midnight, July 5,1986 Signed this 5th day of June 1981 s

/

/W_

Diana Dutton Director Enforcement Division (6AE)

EPAPoem 3540 -2 87 74) as*L a c ts es a comu asac.a i.o-ts' wic= wa v et usto un tit suppi.v es re wausiso f1108170236 810804 ',

PDR ADOCK 05000313 P

pop,

t-i-D, i

l

=

+.

l.

A-1 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENT 5 h

During the period beginning the effective date and lasting through June 30, 1984 l !

lthe permittee is authorized to discharge from outfcil(s) serial number (s) 001, once through cool 1ng water and l

previously monitored effluents.

such discharges shall be limited and monitored by the permittee as specified below:

Monitoring Requirements Effluent Garacteristic Discharge Limitations kg/ day (Ibs/ day)

Other Units (Specify)

Measurement Svnple Daily Avg Daily Max Daily Avg Daily Max

Frequency Type Flow-m / Day (MGD)

N/A N/A (1123)

(1145)

I Continuous Record 3

Temperature N/A N/A 40.6 C(105 F)* 43.3 C(110 F)**

Continuous Record Free Available Chlorine ***

71(156) 181(398) 0.2 mg/l 0.5 mg/l

" 1/ week Grab

  • See Part III, Paragraph C.

[-

    • Instantaneous maximum.
      • See Part III, Paragraph D.

J t-

+1 The pII shall not be less than N/A standard units nor greater than N/A standard units and shall be monitored N/A l

ag g

There shall be no discharge of floating solids or visible foam in other than trace amounts.

y Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location (s):

"y~

In the discharge canal prior to return to' g '5 8

Lake Dardanelle.

S ts

~

i n


x

=+

%%yn

~

\\

\\

'N -N A-2 EFFLUENT LIMITATIONS AND MONITORING REQUIRIM' ENTS During the period beginning July 1, 1984 andlasting through the expiration of this permit 001, once through cooling water and lthe permittee is authorized to discharge from outfall(s) serial number (s) previously monitored effluents.

Such discharges shall be limited and monitored by the permittee as specified below:

Monitoring Requirements Effluent aaracteristic Discharge 1. imitations kg/ day (!bs/ day)

Other Units (Specify)

Measurement Sample Daily Avg Daily Max Daily Avg Drily Max Frequency Type Flow-m / Day (MGD)

N/A N/A (1123)

(1145)

Continuous Record 43.3 C(110*F)**

Continuous Record 3

Temperature N/A N/A 40.6*C(105 F)*

Total Residual Chlorine ***

N/A 181(398)

N/A 0.5 mg/l 1/ week Grab

  • See Part III, Paragraph C.
    • Instantaneous maximum.
      • See Part III, Paragraph E.

The pil shall not beless than N/A standard units nor greater than N/A standard units and shall be monitored '

N/A There shall be no discharge of floating solids or visible foam in other than trace amounts.

lu Samples taken in compliance with the monitoring requirements specified above shall ha taken at the following location (s):

2 In the discharge canal prior to return to Lake Dardanelle.

g-85'.

9 "o

~

A-3 EFFLUENT UMITATIONS AND MONITORING REQUIRC'MENTS~

30, 1984

,During the period beginning the effective date and lasting through June 002, cooling tower blowdown.

lthe permittee is authorized to discharge from outfall(s) serial number (s)

Such discharges shall be limited and monitored by the permittee as specified below:

Effluent Garacteristic Discharge Limi'.ations Monitoring Requirements kg/ day (Ibs/ day)

Other Units (Specify) l Measurement Sample Daily Avg Daily Max Daily Avg Daily Max Frequency Type Flow-m / Day (leMGD)

N/A N/A (20)

(35)

Daily Estimate 3

Free Availab Chlorine 15(33) 38(83) 0.2 mg/l 0.5 mg/l 1/ week Grab l

The pil shall not be less thm 6.0 standard units nor grt.ater than 9.0 standard units and shall be monitored '

1/ ween by grib sample.

?$

There shall be no discharge of floating solids or visible foam in other than trace amounts.

l E

?",

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location (s):

Pricr to mixing with once through cooling water (Outfall 001).

g-8M S

~

\\

1 A-4 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS Durmg the period beginning July 1,1984 andlasting through the expiration of this pennit lthe permittee is authorized to discharge from outfall(s) serial number (s) 002, cooling tower blowdown Such discharges shall be limited and monitored by the permittee as specified below:

1 Effluent Otaracteristic Discharge Limitations Monitoring Requirements kg/ day (lbs/ day)

Other Units (Specify)

' Measurement Sample Daily Avg Daily Max Daily Avg

. Daily Max Frequency Type Flow-m / Day (MGD)

N/A N/A (20)

(35)

Daily Totalized 3

Total Residual Chlorine N/A 10.5(23)

N/A 0.14 mg/l 1/ week Grab See Part III, Paragraph I.

l.

b 2

i The pH shrli not be less than 6.0 standard units nor greater than 9.0 standard uniss and shall be monitored 1/ week by grab sample.

There shall be no discharge of r.oating solids or visible foam in other than 1, ace amouts.

-1(

? a, -

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location (s):

Prior to mixing with once through cooling water (0utfall 001).

g-o-

0 0*

0

8

A-5 EFFLUENT LIMITATIONS AND MONITORING REQtPRFJdENTS During the period beginning the effective date and lasting through the expiration of this permit "the permittee is authorized to discharge from outfall(s) serial number (s) 003, oily water separator discharge Such discharges shall be limited and monitored by the permittee as specified below:

Effluent Characteristic Discharge Limitations Monitoring Requirements.

kg/ day (lbs/ day)

Other Units (Specify)

. Measurement Sample Daily Avg Daily Max Daily Avg Daily Max Frequency Type Flowm / Day (MGD)

N/A N/A (0.2)

(0.5)

Daily Totalized 3

Total Suspended Solids 23(50) 76(167) 30 mg/l 100 mg/l 1/ week Grab 011 and Grease 11(25) 15( 33) 15 mg/l 20 mg/l 1/ week Grab 1

l-8 I

) '

1 The pli shall not be less than 6.0 standard units nor smater than 9.0 standard units and shall be monitored 1/ week by grab sample.

There shall be no discharge of floating solids or visible loam in other than trace amounts.

!(

g o, Samples taken in compliance with the monitoring requir ements specified above shall be taken at the following location (s):

Prior to discharge to Lake Dardanelle.

g' 8M S

M i

_ _ -. + _ - -.

N

.-+,4-.m b*W

=hvNm.-

~

i i

i.

c l

A-6 EFFLUENT LIMITATIONS AND MONITORING REQUIRE'MENTS' j

~

During the period beginning the effective datandlastingthrough the expiration of this permit lthe permittee is authorized to discharge from outfall(s) serial number (s) 004, 1ow volume wastewater Such discharget shall be limited and monitored by the permittee as specified below:

Effluent aaracteristic Discharge Limitaticas Mc.iitoring Requirements kg/ day (lbs/ day)

OtEer Units (Specify) i Measurement Sample l

Daily Avg Daily Max Daily Avg Daily Max Frequency Type Flow-m / Day (MGD)

N/A N/A

(.15)

(.3)

, Each release Totalized 3

Total Suspended Solids 17.l(37.5)

(*)

30 mg/l 100 mg/l 1/ week Grab Oil and Grease 8.5(18.8)

(*)

15 mg/l 20 mg/l 1/ week Grab Report The pil shall not be less than 6.0 standard units nor greater than 9.0 standard urits and shall be monitored '

1/ week by grab sarr.ple, nr There shall be no discharge of floating solids or visible foam in other than trace amounts.

.y ~

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location (s):

Prior to release to Lake Dardanelle o1 gcn t;

n

i 1'

I 9

A-7 EFFLUENT LIMITATIONS AND MONITORING REQLIIREMENTS l

.During the period beginn!ng the effective date and lasting through the expiration date of this pennit

'the permittee is authorized to discharge from outfall(s) serial number (s) 005, sanitary sewage discharge Such discharges shall be limiud and monitored by the permittee as specified below:

Effluent Garacteristic Discharge Limitations Monitoring Requirements.

kg/ day (Ibs/ day)

Other Units (Specify) ;

i Measurement Sample Daily Avg Daily Max Daily Avg Daily Max -

Frequency Type Flow-m / Day (MGD)

N/A N/A

(.025)

(.1005)

Daily Estimate 3

Total Suspended Solids N/A N/A 30 mg/l 45 mg/l 1/ week Grab Biochemical Oxygen Demand (5-day)

N/A N/A 30 mg/l 45 mg/l 1/ week Grab 4

I i

i i

The pH shall not be less than 6.0 standard units nor greater than 9.0 standard units and shall be monitored 1/ week by grab sample.

l-

,y I

There shall be no discharge of floating solids or visible foam in other than trace amounts.

! (,

z Samples taken in compliance with the monitoring requirements specified e'aove shall be taken at the following location (s):

Prior to discharge to Lake Dardanelle 3 %.

i

$6.

j 8

i i

5 n

,-v 4

7 PART l

~~'

Page g of }6 Permit No.

A.R0001392 B. SCIIEDULE OF COMPLIANCE Outfalls 001 and 002

1. The pe#rmittee shall achieve compliance with the effldent limitations specified for discharges in accordance with the following schedule:

Progress Report 06/30/82 Progress Report 12/31/82 Progress Report 06/30/83 Progress Report 12/31/83 Progress Report 03/31/84 Achieve' Compliance

- ~~07/01/84

~

)

2. No later than 14 calendar days following a date identified in the above schedule of compliance, the permittee shd submit either a report of progress or, in the case of I

specific actions being required by identified dates, a written notice of compliance or noncompliance. In the latter case, the

'i e shall include the cause of noncomplianca, I

any remedial actions taken, and ths y bility cf meeting the next scheduied requirement.

I I

1 l

l

(

~~ PART1

^

Pnc 10,,,

16 Permit m.

ARnon1392 C. MONITORING AND REPORTING

1. F.epresentativeSampling Saqies and measurements taken as required herein shall be reprewntative of the volume and nature of the monitored discharge.
2. Reporting

' Mondor.ag results obtained during the previous '3 ~ months shall be summarized for each month and reported on a Discharge Monitoring Report Form (EPA No.-3320-1),

postmarked no later than the 28th day of the month following the completed reporting

~~

~

~~~

~ period. 'lhe first report is dtie on October 28, hall 1981

.~ Duplicate' signed copies of these, and all other reports required herem, s be submitted to the Regional Administrator and the State at the following addresses:

Diana Dutton, Director Jarrell E. Southall, Director Enforcement Division (6AE)

Arkansas Department of Pollution U.S. Environmental Protection Agency Control and Ecology First International Building 8001 National Drive 1201 Elm Street Little Rock, Arkansas 72209 Dallas, Texas 75270

3. Definitions a.

De " daily average" discharge means the total discharge by weight during a calendar month divided by the number of days in the month that the production or

. commercial facility wrs operating. Where less than daily sampling is required by this

- permit, the daily average discharge shall be determined by the summation of all the measured daily discharges by weight divided by the number of days during the calendar month when the measurements were made.

I

b. The " daily maximum" discharge means the total discharge by weight during any calendar day.
4. Test Procedures Test procedures for the analysis of pollutants shall conform te regulations published pursuant to Section 304(g) of the Act, under which such procedures may be required.
5. Recording of Results For each measurement or sample taken pursuant to the requirer ents of this permit, the permittee shall record the following information:

a.

The exa ' lace, date, and time of sampling;

b. The dates the analyses were performed;
c. De person (s) who performed the analyses:

5

+

~

PARTI r, 11 or 16

~ ~

Pumit No.

nR0001392

d. The analytical techniques or methods used; and e.

The results of all required analyses.

6. Addition.xlMonitoring by Permittee If the permittee moniton any pc'4utant at the location (s) designated herein more frequently than required by this permit, using approved analytical methods es specified above, the results of such monitoring shall be included in the calculation and reporting of the values required in the Eacharge Monitoring: Report Form (EPA No. 33201). Such increased freqi ye shall also be indicated.

-=.=..- -

7. Records Retention

~

^':..:'

[ -~-

~

All records and information resulting from the monitoring activities required by this '

permit including all records of analyses performed and calibration and maintenance of instrumentation and recordings from continuous monitoring instrumentation shall be retained for a minimum of three (3) years, or longer if requested by the Regional Administrator or the State water pollution control agency.

3 w

n m

m._,

  • -my v

.- m

PAFIT li rw 12 or 16 Permit No. AR0001392 A. MANAGEMENT REQUIREMENTS

1. Change in Discharge i

All discharges authorized herein shall be consistent with the terms and conditions of this permit. 'Ihe discharge of any pollutant identified in this permit more frequently than or at a level in excess of that authorized shall constitute a violation of the permit Any anticipated facility expansions, production increases,'or process modifications which will result in new, different, or increased discharges of pollutants must be reported by submission of a new NPDES application or, if such cisnges will not violate the effluent limitations specified in this permit, by notice to the permit issuing authority of such changes. Follo ring such notice, the permit may be modified to specify and limit any pollutants not previously limited.

2. Noncompliance Notification If, for any reason, the permittee does not comply with or will be unabs comply with any daily maximum effluent limitation specified in this permit, the permittee shall provide the Regional Administrator and the State with the following information, in writing, within five (5) days of becoming aware of such condition:

a.

A description of die discharge and cause of noncompliance; and

b. The period of noncompliance, including exact dates and times; or,if not corrected, the antici 4ted time the noncompliance is expected to continue, and steps being taken to reduce, e'.iminate and prevent recurrence of the noncomplying discharge.
3. FaciFties Operation The permittee shall at all times maintain in good working order and operate as efficiently as pos:.ible all treatment or control faci'ities or systems installed or used by the permittee to achieve compliance with the terms and conditions of this permit.
4. AdverseImpact The permittee shall take all reasonable steps to nunimize any adverse impact to navigable waters resulting from noncompliance with any effluent limitations specified in this permit, including such accelerated or additional monitoring as necessary to determine the nature and impact of the noncomplying discharge.
5. Bypassing Any diversion from or bypass of facilities necessary to maintain compliance with the terms and conditions of this permit is prohibited, except (i) where unavoidable to prevent loss of life or severe prope-tv damage, or '5) where excessive storm drainage or runoff would damage any facilities necessary for compliance with the effluent limitations and prohibitions of this permit. The permittee shall promptly notify the Regional Administrator and the State in wnting of each such diversion or bypass.

f-I a.

PART11 Pas. 13 or 16 Pumu No.

AR0001392

6. RemovedSubstances Solids, sludges, filter backwash, or other pollutants removed in the course of treatment or control of wastewaters shall be disposed of in a manner such as to prevent any pollutant f om such materials from entering navigable waters.
7. Power Failures In order to maintain compliance with the effluent limitations and prohibitions of this permit, the permittee shall either:

In accordance with the Schedule et Compliance contained in Part I, provide an a.

alternative power source sufficient to operate the wastewater control facilities; or,if such alternative power source is not in existence, and no date for its implementation appears in Part I,

b. Italt, reduce or ot.

We control production and/or all disc' ages upon the reduction, loss, or failure of the primary source of power to the wastewater control l

facilities.

r D. RESPONSIBILITIES

1. Right of Entry I

The permittee shall allow the head of the State water po!!ution control agency, the Regional Administrator, and/or their authorized representatives, upon the presentation of l

credentials:

To enter upon the permittee's premises where an effluent source is located or in a.

which any records are required to be kept under the terms and conditions of this permit;and 1

l

b. At reasonable times to have access to and copy any records required to be kept under the terms and conditions of this permit; to inspect any monitoring equipment or monitoring method required in this permit; and to sample any discharge of pollutants.
2. Transfer of Ownership or Control In the event of any changa in control or ownership of facilities from which the authorized q

discharges emanate, the permittee shall notify the succeeding owner or controller of the existence of this permit by letter, a copy of which shall be forwarded to the Regional Administrator and the State water pollution control agency.

3. Availability of Reports Except for data determined to be confidential under Section 308 of the Act, all reports prepared in accordance with the terms of this permit shall be available for public V

i

[

, '. ~

=

s e

? ART 11 ras. 14 or 16 rermit No.

AR0001392 inspection at the offices of the State water pollution control agency and the Regional Administrator. As required by the Act, effluent data shall not be considered confidential.

Knowingly making any false statement on any such report may result in the imposition of criminal penalties as provided for in Section 309 of the Act.

4. Permit Modification After notice and opportunity for a hearing, this permit may be modified, suspended, or revoked in whole or in part during its term for cause including, but not limited to, the following:

a.

Violation of any terms or conditions of this permit;

+

b. Obtaining this permit by misrepresentation or failure to disclose fully all relevant facts;or c.

A change in any condition that requires either a temporary or permanent reduction or elimination of the authorized discharge.

5.

Toxic Pollutants Notwithstanding Part II, B-4 above, if a toxic effluent standard or prohibition (includ in any schedule of compliance specified in such effluent standard or prohibition) is established under Section 307(a) of the Act for a toxic pollutant which is present in the discharge and such standard or prohibition is more stringent than any limitation for such pollutant in this permit, this permit shall be revised or modified in accordance with the toxic effluent standard or prohibition and the permittee so notified.

6. Civil and Criminal Liability Except as provided in permit conditions on " Bypassing" (Part II, A.5) and " Power Failures" (Part II, A 7), nothing in this permit shall be construed to relieve the permittee from civil or criminal penalties for noncompliance.
7. Gil and Hazardous Substance Liability Nothing in this permit shall be construed to preclude the institution of any legal action or relieve the permittee from any responsibilities, liabilities, or penalties to which the permittee is or may be subject under Section 311 of the Act.
8. State Laws Nothing in this permit shall be construed to preclude the institution of any legal action or relieve the permittee from any responsibilities, liabilities, or penalties established pursuant to any applicable State law or regulation under authority preserved by Section 510 of the Act.

PART 11 rwe 15 or 16 rermit No.

AP0001392

9. Property Rights The issuance of 'this permit does not convey any property rights in either real or personal property, or any exclusive privileges, nor does it authorize any injury to private property or any invasion of personal rights, nor any infringement of Federal, State or locallaws ur regulations.
10. Severability The provisions of this permit are severable, and if any provision of this permit, or the application of any provision of this permit to any circumstance, is held invalid, the application of such provision to other circumstances, and the remainder of this pc*mit,

. shall not be affected thereby.

PART III OTHER REQUIREMENTS A.

There shall be no discharge of polychlorinat1d biphenyl trans-former fluid.

B.

The " daily average" concentration means the arithmetic average (weighted by flow value) of all the daily determinations of concentra-tion made during a calendar month. Daily determinations of concentra-tion made using a composite sample shall be the concentration of the composite sample. When grab samples are used, the daily determination of concentration shall be the arithmetic average (weighted by flow value) of all the samples collected during that calendar day.

The " daily maximum" concentration means the daily determination of concer.tration for any calendar day.

C.

Daily average temperature is defined as the flow weighted average tenperature (FWAT) and shall be computed and recorded on a daily basis.

FWAT shall be computed at equal time intervals not greater than two hours. The method of calculating FWAT is as follows:

FWAT = S_UW4ATION (INSTANTANEOUS FLOW X INSTANTANEOUS TEMPERATURE)

SUMMATION (INSTANTANE0US FLOW)

D.

The term " free available chlorine" shall mean the value obtained using the amperometric titration method for free available chlorine described in " Standard Methods for the Examination of Water and Waste-i water," page 112 (13th edition).

PART III Page 16 of 16*

Permit No. AR0001392 Neither free available chlorine nor total residual chlorine may

'be discharged fron any unit for more than two hours in any one day and not more than one unit in any plant may discharge free available or total residual chlorine at any one time unless the permittee can dem-onstrate to the permitting Agency that the units in a particular loca-tion cannot operate at or below the limitations specified in this permit.

E.

The term " total residual chlorine" (or total residual oxidants

~"

.for intake water with-bromides) means the value obtained using-the am.

perometric method for total residual chlorine. described in " Standard-Methods for the Examination of Water and Wast 2 water."

p. 112 (13th edition).

G.

Noncompliance reporting for upsets and bypasses shall be made within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to EPA Region 6 followed by a written report in five days. Violations of daily maximum limitations for pollutants listed below will also be reported in 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> followed by a written report in five days.

Violations of daily maximum limitations for all other pollutants identified elsewhere in this permit shall be reported in writing within five days.

Chlorine H.

The conditions applicable to all permits under 40 CFR 122.7, 122.15,122.60,122.61 and 122.62 (as promulgated in the May 19, 1980, i

Federal Register) are hereby incorporated into this permit and prevail over any inconsistent requirements of this perTnit.

I.

There shall be do discharge of cooling tower maintenance chemi-cals which contain the 129 priority pollutants (Appendix B of 40 CFR, Part 423).

,.t g -

9tp

'A 9 UNITED CTATED ENVIRONMENTAL PROTECTION AGENCY

. l r.,

REGION Vi f

C 9 209 ELM STPECT l.

y f

!ft DALLAS, TEX AS 75270

f p

[

JU.y laa a

n Au,.;;, -

MCk',,

ii M N'@q lt NPDES DETERM!ftATI0tl After considering the facts and the requirements and policies expressed in PL 95-217 and implementing regulations, I have determined that proposed Permit flo. AR0001392, Arkansas Power and Light Company shall be modified and issued as indicated in a Public Notice of madification, subject to timely certification (or waiver thereof) by the state certifying agency, provided however, that any condition (s) contested in a request for an Evidentiary Hearing submitted within 30 days from receipt of this determination as in accordance with new 40 CFR 124.74 (45 Fed. Reg. 33498, May 19, 1980) may be stayed if the request for a Hearing is granted.

June 5, 1981 Dated:

O D

/

//

t iana Dutt n r

Director Enforcement Division (6AE) e

,s U.s. n;VInc:: MENTAL PRCyrECTIOt1 AGCICY STATn or ARKANSAS PUBLIC NOTICE JutlE 6,1981

=:

ge purpose of this notice is to state EPA's intention to modify authoriaation to discharge istewater heretofore issued to the applicant (s) identified in the attached list under the ethority of Section 402 of the Clean Water Act of 1977 (Public Law 95-217).. This proposed dification of heretofore issued authorization (s) has been made on the basis of staff ~

Micw by the Environmental Protection Agency, af ter consultation with the appropriate ats cgsney, and af ter determining that the original permit (s) does not represent current-

' cxisting discharge conditions.

is tha tentative determination of the Region VI staff to modify this permit (s) and it/

cy ehell become effective onSEPTEl'.BER 6,1981 unless:

,a2+ The state certifying agency denies certificatica

  • ~~ prior to that date.

b.

Comments received prior to JULY 6, 1981 warrant a substantial change from or denial of the proposed p ermit(s).

A public hearing is held requiring delay of the c.

effective date.

Irconn wishing to comment upon or orject to the proposed determination (s) are invited to bmit scme in writing to:

Ms. Mary Calahan Environmental Protection Agency i

Permits Branch (GAEPAP) Region VI First International Building 1201 Elm Street Dallas, Texas 75270

^

(thin thirty (30) days of publication date of the Public Notice of this application (s).

e application number should appear next to the above address 6n the first page of any itted comments.

All comments cr objections received within this 30-day period will be sidered in the formulation of final determination regarding the applications and a lic hearing shall be held where the Agency finds a significant degree of public interest.

Ey person may submit a request for an evidentiary hearing within 30 days from receipt of ke Agency's determination to issue, modify, or deny the permit.

The contested provisions thm proposed permit shall then be stayed pending final action of the Agency pursuant to 40 CFR 124.71 et seq. (Federal Register Volume 44, No.111, Thursday June 7, 1979,

'ga 32938).

quirements which must be satisfied prior to the granting of a reques't for an evidentiary

"'ng or for requests to be party at an evidentiary hearing may be obtained from new tyR 124.71.

Further information may be obtained at the above address, or telephone

14) 767-2765, between 8 a.m. and 4:30 p.m., Monday thru Priday.

s e

a

l.

Permit No. AR0001392 for NPDES Authorization to Discharge to waters of ti.c United States, Public notice of which was issued on February 13, 1981.

3.

The applicat's mailing address.is: Arkansas Power & Light Company.

P.O. Box 551 l

Little Rock, Arkansas 72203 The discharge is.made into Dardanelle Reservoir, a water of the United States which is suitabic for primary contact recreation, propagation of desirable species of fish, wildlife and other aquatic life; raw water sour-ces of public water supplies; and other compatible uses and is located va that water at the Arkansas Nuclear One Steam Electric Station on Lake A fact sheet is Dardanelle, near Russellville, Pope Cocnty, Arkansas.

available.

The applicant's activities, under the standard industrial classification (SIC) code 4911 which result in the existing discharge are the ger.eration of electrial power for transmission and sale.

The changes from the heretofore issued authorization to discharge wastewater are:

Effective July 1,1984 no discharge of total residual chlorine is 1.

allowed from Outf all 001, once-through cooling water.

Effective July 1,1984 chlorine discharge from Outfall 002, 2.

cooling tower blowdown, is limited to 0.14 mg/l total residual chlorine.

The substantial change from the proposed permit are as follows:

For outfall 001, the daily average flow limitation is increased to 1.

1123 MGD.

For outfall 002, totalized flow monitoring is deferred until Ju!y 2.

1, 1984 For outfall 004, daily average flow is changed to 0.15 MGD and 3.

daily maximun flow is changed to 0.3 MGD.

For total suspended solids the daily average mass discharge limitation is changed to 37.5 lbs/ day and the daily maximum mass discharge limitation is l

removed.

For oil and grease the daily average mass discharge limi-tation is changed to 18.8 lbs/ day and the daily maximum mass discharge limitation is removed.

4.

For outfall 005, daily average flow is changed to 0.025 MGD.

For outfall 001, effective July 1,1984 total residual chlorine 5.

limits are changed to 0.5 mg/l daily maximum.